[F] SECTION 3003 EMERGENCY
OPERATIONS
[F] 3003.1 Standby power.
In buildings and structures where standby power is required
or furnished to operate an elevator, the operation shall be
in accordance with Sections 3003.1.1 through 3003.1.4.
[F] 3003.1.1 Manual transfer.
Standby power shall be manually transferable to all elevators
in each bank.
[F] 3003.1.2 One elevator.
Where only one elevator is installed, the elevator shall
automatically transfer to standby power within 60 seconds
after failure of normal power.
[F] 3003.1.3 Two or more
elevators. Where two or more elevators are controlled
by a common operating system, all elevators shall automatically
transfer to standby power within 60 seconds after failure
of normal power where the standby power source is of sufficient
capacity to operate all elevators at the same time. Where
the standby power source is not of sufficient capacity to
operate all elevators at the same time, all elevators shall
transfer to standby power in sequence, return to the designated
landing and disconnect from the standby power source. After
all elevators have been returned to the designated level,
at least one elevator shall remain operable from the standby
power source.
[F] 3003.1.4 Venting.
Where standby power is connected to elevators, the machine
room ventilation or air conditioning shall be connected
to the standby power source.
[F] 3003.2 Fire-fighters
emergency operation. Elevators shall be provided with
Phase I emergency recall operation and Phase II emergency
in-car operation in accordance with ASME A17.1.
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|