SECTION 507 UNLIMITED AREA BUILDINGS
507.1 General.
The area of buildings of the occupancies and configurations
specified herein shall not be limited.
507.2 Nonsprinklered,
one story. The area of a one-story, Group F-2 or
S-2 building shall not be limited when the building
is surrounded and adjoined by public ways or yards not
less than 60 feet (18 288 mm) in width.
507.3 Sprinklered, one
story. The area of a one-story, Group B, F, M or
S building or a one-story Group A-4 building, of other
than Type V construction, shall not be limited when
the building is provided with an automatic sprinkler
system throughout in accordance with Section
903.3.1.1 and is surrounded and adjoined by public
ways or yards not less than 60 feet (18 288 mm) in width.
Exceptions:
1. Buildings and structures
of Type I and II construction for rack storage facilities
that do not have access by the public shall not be
limited in height, provided that such buildings conform
to the requirements of Sections 507.2 and 903.3.1.1
and NFPA 230.
2. The automatic sprinkler
system shall not be required in areas occupied for
indoor participant sports, such as tennis, skating,
swimming and equestrian activities in occupancies
in Group A-4, provided that:
2.1. Exit doors directly
to the outside are provided for occupants of the
participant sports areas; and
2.2. The building is
equipped with a fire alarm system with manual fire
alarm boxes installed in accordance with Section
907.
3. Group A-1 and A-2
occupancies of other than Type V construction shall
be permitted, provided:
3.1. All assembly occupancies
are separated from other spaces as required for
separated uses in Section
508.3.3.4 with no reduction allowed in the fire-resistance
rating of the separation based upon the installation
of an automatic sprinkler system;
3.2. Each Group A occupancy
shall not exceed the maximum allowable area permitted
in Section 503.1; and
3.3. All required exits
shall discharge directly to the exterior.
507.4 Two story.
The area of a two-story, Group B, F, M or S building
shall not be limited when the building is equipped throughout
with an automatic sprinkler system in accordance with
Section 903.3.1.1, and is
surrounded and adjoined by public ways or yards not
less than 60 feet (18 288 mm) in width.
507.5 Reduced open space.
The permanent open space of 60 feet (18 288 mm) required
in Sections 507.2, 507.3, 507.4, 507.6 and 507.10 shall
be permitted to be reduced to not less than 40 feet
(12 192 mm), provided the following requirements are
met:
1. The reduced open space
shall not be allowed for more than 75 percent of the
perimeter of the building.
2. The exterior wall
facing the reduced open space shall have a minimum
fire-resistance rating of 3 hours.
3. Openings in the exterior
wall facing the reduced open space shall have opening
protectives with a minimum fire protection rating
of 3 hours.
507.6 Group A-3 buildings. The area of a one-story,
Group A-3 building used as a place of religious worship,
community hall, dance hall, exhibition hall, gymnasium,
lecture hall, indoor swimming pool or tennis court of
Type II construction shall not be limited when all of
the following criteria are met:
1. The building shall
not have a stage other than a platform.
2. The building shall
be equipped throughout with an automatic sprinkler
system in accordance with Section
903.3.1.1.
3. The assembly floor
shall be located at or within 21 inches (533 mm) of
street or grade level and all exits are provided with
ramps complying with Section
1010.1 to the street or grade level.
4. The building shall
be surrounded and adjoined by public ways or yards
not less than 60 feet (18 288 mm) in width.
507.7 Group H occupancies.
Group H-2, H-3 and H-4 occupancies shall be permitted
in unlimited area buildings containing Group F and S
occupancies, in accordance with Sections 507.3 and 507.4
and the limitations of this section. The aggregate floor
area of the Group H occupancies located at the perimeter
of the unlimited area building shall not exceed 10 percent
of the area of the building nor the area limitations
for the Group H occupancies as specified in Table
503 as modified by Section 506.2,
based upon the percentage of the perimeter of each Group
H fire area that fronts on a street or other unoccupied
space. The aggregate floor area of Group H occupancies
not located at the perimeter of the building shall not
exceed 25 percent of the area limitations for the Group
H occupancies as specified in Table
503. Group H fire areas shall be separated from
the rest of the unlimited area building and from each
other in accordance with Table
508.3.3 For two-story unlimited area buildings,
the Group H fire areas shall not be located above the
first story unless permitted by the allowable height
in stories and feet as set forth in Table
503 based on the type of construction of the unlimited
area building.
507.8 Aircraft paint hangar. The area of a one-story,
Group H-2 aircraft paint hangar shall not be limited
where such aircraft paint hangar complies with the provisions
of Section 412.4 and is entirely
surrounded by public ways or yards not less in width
than one and one-half times the height of the building.
507.9 Group E buildings.
The area of a one-story Group E building of Type II,
III A or IV construction shall not be limited when the
following criteria are met:
1. Each classroom shall
have not less than two means of egress, with one of
the means of egress being a direct exit to the outside
of the building complying with Section
1018.
2. The building is equipped
throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1.
3. The building is surrounded
and adjoined by public ways or yards not less than
60 feet (18 288 mm) in width.
507.10 Motion picture
theaters. In buildings of Type II construction,
the area of a one-story motion picture theater shall
not be limited when the building is provided with an
automatic sprinkler system throughout in accordance
with Section 903.3.1.1 and
is surrounded and adjoined by public ways or yards not
less than 60 feet (18 288 mm) in width.
507.11 Covered mall
buildings and anchor stores. The area of covered
mall buildings and anchor stores not exceeding three
stories in height that comply with Section
402.6 shall not be limited.
|