|
|
|
|
|
SECTION
903 AUTOMATIC SPRINKLER SYSTEMS
[F] 903.3 Installation requirements.
Automatic sprinkler systems shall be designed and installed
in accordance with Sections 903.3.1 through 903.3.7.
[F] 903.3.1 Standards.
Sprinkler systems shall be designed and installed in accordance
with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
[F] 903.3.1.1 NFPA 13
sprinkler systems. Where the provisions of this code
require that a building or portion thereof be equipped
throughout with an automatic sprinkler system in accordance
with this section, sprinklers shall be installed throughout
in accordance with NFPA 13 except as provided in Section.
[F] 903.3.1.1.1 Exempt
locations. Automatic sprinklers shall not be required
in the following rooms or areas where such rooms or
areas are protected with an approved automatic fire
detection system, in accordance with Section
907.2, that will respond to visible or invisible
particles of combustion. Sprinklers shall not be omitted
from any room merely because it is damp, of fire-resistance-rated
construction or contains electrical equipment.
1. Any room where the
application of water, or flame and water, constitutes
a serious life or fire hazard.
2. Any room or space
where sprinklers are considered undesirable because
of the nature of the contents, when approved by the
fire code official.
3. Generator and transformer
rooms separated from the remainder of the building
by walls and floor/ceiling or roof/ceiling assemblies
having a fire-resistance rating of not less than 2
hours.
4.
In rooms or areas that are of noncombustible construction
with wholly noncombustible contents.
[F] 903.3.1.2 NFPA 13R sprinkler systems. Where
allowed in buildings of Group R, up to and including four
stories in height, automatic sprinkler systems shall be
installed throughout in accordance with NFPA 13R.
[F]
903.3.1.2.1 Balconies and decks. Sprinkler protection
shall be provided for exterior balconies, decks and
ground floor patios of dwelling units where the building
is of Type V construction. Sidewall sprinklers that
are used to protect such areas shall be permitted to
be located such that their deflectors are within 1 inch
(25 mm) to 6 inches (152 mm) below the structural members
and a maximum distance of 14 inches (356 mm) below the
deck of the exterior balconies and decks that are constructed
of open wood joist construction.
[F]
903.3.1.3 NFPA 13D sprinkler systems. Where allowed,
automatic sprinkler systems in one- and two-family dwellings
shall be installed throughout in accordance with NFPA
13D.
[F] 903.3.2 Quick-response
and residential sprinklers. Where automatic sprinkler
systems are required by this code, quick-response or residential
automatic sprinklers shall be installed in the following
areas in accordance with Section 903.3.1 and their listings:
1.
Throughout all spaces within a smoke compartment containing
patient sleeping units in Group 1-2 in accordance with
this code.
2. Dwelling units, and sleeping units in Group R and 1-1
occupancies.
3. Light-hazard occupancies
as defined in NFPA 13.
[F] 903.3.3 Obstructed locations.
Automatic sprinklers shall be installed with due regard to
obstructions that will delay activation or obstruct the water
distribution pattern. Automatic sprinklers shall be installed
in or under covered kiosks, displays, booths, concession stands,
or equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible fibers.
Exception:
Kitchen equipment under exhaust hoods protected with a fire-extinguishing
system in accordance with Section 904.
[F]
903.3.4 Actuation. Automatic sprinkler systems shall
be automatically actuated unless specifically provided for
in this code.
[F]
903.3.5 Water supplies. Water supplies for automatic
sprinkler systems shall comply with this section and the
standards referenced in Section 903.3.1. The potable water
supply shall be protected against backflow in accordance
with the requirements of this section and the International
Plumbing Code.
[F] 903.3.5.1 Domestic services. Where the domestic
service provides the water supply for the automatic sprinkler
system, the supply shall be in accordance with this section.
[F]
903.3.5.1.1 Limited area sprinkler systems. Limited
area sprinkler systems serving fewer than 20 sprinklers
on any single connection are permitted to be connected
to the domestic service where a wet automatic standpipe
is not available. Limited area sprinkler systems connected
to domestic water supplies shall comply with each of
the following requirements:
1.Valves
shall not be installed between the domestic water riser
control valve and the sprinklers .
Exception: An approved indicating control valve
supervised in the open position in accordance with Section
903.4.
2.The
domestic service shall be capable of supplying the simultaneous
domestic demand and the sprinkler demand required to
be hydraulically calculated by NFPA 13, NFPA 13R or
NFPA 13D.
[F]
903.3.5.1.2 Residential combination services. A
single combination water supply shall be allowed provided
that the domestic demand is added to the sprinkler demand
as required by NFPA 13R.
[F]
903.3.5.2 Secondary water supply. A secondary on-site
water supply equal to the hydraulically calculated sprinkler
demand, including the hose stream requirement, shall
be provided for high-rise buildings in Seismic Design
Category C, D, E or F as determined by this code. The
secondary water supply shall have a duration of not
less than 30 minutes as determined by the occupancy
hazard classification in accordance with NFPA 13.
Exception: Existing buildings.
[F] 903.3.6 Hose threads. Fire hose threads and
fittings used in connection with automatic sprinkler systems
shall be as prescribed by the fire code official.
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|