SECTION 415 GROUPS H-1,
H-2, H-3, H-4 AND H-5
[F] 415.1 Scope. The provisions
of this section shall apply to the storage and use of hazardous
materials in excess of the maximum allowable quantities per
control area listed in Section 307.1.
Buildings and structures with an occupancy in Group H shall
also comply with the applicable provisions of Section
414 and the International Fire Code.
[F] 415.2 Definitions.
The following words and terms shall, for the purposes of this
chapter and as used elsewhere in the code, have the meanings
shown herein.
[F] CONTINUOUS GAS-DETECTION
SYSTEM. A gas detection system where the analytical instrument
is maintained in continuous operation and sampling is performed
without interruption. Analysis is allowed to be performed
on a cyclical basis at intervals not to exceed 30 minutes.
[F] EMERGENCY CONTROL STATION.
An approved location on the premises where signals from emergency
equipment are received and which is staffed by trained personnel.
[F] EXHAUSTED ENCLOSURE.
An appliance or piece of equipment that consists of a top,
a back and two sides providing a means of local exhaust for
capturing gases, fumes, vapors and mists. Such enclosures
include laboratory hoods, exhaust fume hoods and similar appliances
and equipment used to locally retain and exhaust the gases,
fumes, vapors and mists that could be released. Rooms or areas
provided with general ventilation, in themselves, are not
exhausted enclosures.
[F] FABRICATION AREA.
An area within a semiconductor fabrication facility and related
research and development areas in which there are processes
using hazardous production materials. Such areas are allowed
to include ancillary rooms or areas such as dressing rooms
and offices that are directly related to the fabrication area
processes.
[F] FLAMMABLE VAPORS OR FUMES.
The concentration of flammable constituents in air that exceed
25 percent of their lower flammable limit (LFL).
[F] GAS CABINET. A fully
enclosed, noncombustible enclosure used to provide an isolated
environment for compressed gas cylinders in storage or use.
Doors and access ports for exchanging cylinders and accessing
pressure-regulating controls are allowed to be included.
[F] GAS ROOM. A separately
ventilated, fully enclosed room in which only compressed gases
and associated equipment and supplies are stored or used.
[F] HAZARDOUS PRODUCTION MATERIAL
(HPM). A solid, liquid or gas associated with semiconductor
manufacturing that has a degree-of-hazard rating in health,
flammability or reactivity of Class 3 or 4 as ranked by NFPA
704 and which is used directly in research, laboratory or
production processes that have as their end product materials
that are not hazardous.
[F] HPM FLAMMABLE LIQUID.
An HPM liquid that is defined as either a Class I flammable
liquid or a Class II or Class IlI A combustible liquid.
[F] HPM ROOM. A room used
in conjunction with or serving a Group H-5 occupancy, where
HPM is stored or used and which is classified as a Group H-2,
H-3 or H-4 occupancy.
[F] IMMEDIATELY DANGEROUS
TO LIFE AND HEALTH (IDLH). The concentration of air-borne
contaminants which poses a threat of death, immediate or
delayed permanent adverse health effects, or effects that
could prevent escape from such an environment. This contaminant
concentration level is established by the National Institute
of Occupational Safety and Health (NIOSH) based on both toxicity
and flammability. It generally is expressed in parts per million
by volume (ppm v/v) or milligrams per cubic meter (mg/rn3).
If adequate data do not exist for precise establishment of
IDLH concentrations, an independent certified industrial hygienist,
industrial toxicologist, appropriate regulatory agency or
other source approved by the code official shall make such
determination.
[F] LIQUID. A material
that has a melting point that is equal to or less than 68°F
(20°C) and a boiling point that is greater than 68°F (20°C)
at 14.7 pounds per square inch absolute (psia) (101 kPa).
When not otherwise identified, the term "liquid"
includes both flammable and combustible liquids.
[F] LIQUID STORAGE ROOM.
A room classified as a Group H-3 occupancy used for the storage
of flammable or combustible liquids in a closed condition.
[F] LIQUID USE, DISPENSING
AND MIXING ROOMS. Rooms in which Class I, II and IlIA
flammable or combustible liquids are used, dispensed or mixed
in open containers.
[F] LOWER FLAMMABLE LIMIT
(LFL). The minimum concentration of vapor in air at which
propagation of flame will occur in the presence of an ignition
source. The LFL is sometimes referred to as "LEL"
or "lower explosive limit.
NORMAL TEMPERATURE AND PRESSURE
(NTP). A temperature of 70°F (21°C) and a pressure of
1 atmosphere [14.7 psia (101 kPa)].
[F] PHYSIOLOGICAL WARNING
THRESHOLD LEVEL. A concentration of airborne contaminants,
normally expressed in parts per million (ppm) or milligrams
per cubic meter, that represents the concentration at which
persons can sense the presence of the contaminant due to odor,
irritation or other quick-acting physiological response. When
used in conjunction with the permissible exposure limit (PEL)
the physiological warning threshold levels are those consistent
with the classification system used to establish the PEL.
See the definition of "Permissible exposure limit (pEL)"
in the International Fire Code.
[F] SERVICE CORRIDOR.
A fully enclosed passage used for transporting HPM and purposes
other than required means of egress.
[F] SOLID. A material
that has a melting point, decomposes or sublimes at a temperature
greater than 68°F (20°C).
[F] STORAGE, HAZARDOUS MATERIALS.
1. The
keeping, retention or leaving of hazardous materials in closed
containers, tanks, cylinders or similar vessels, or
2. Vessels
supplying operations through closed connections
to the vessel.
[F] USE (MATERIAL). Placing
a material into action, including solids, liquids and gases.
[F] WORKSTATION. A defined
space or an independent principal piece of equipment using
HPM within a fabrication area where a specific function, laboratory
procedure or research activity occurs. Approved or listed
hazardous materials storage cabinets, flammable liquid storage
cabinets or gas cabinets serving a workstation are included
as part of the workstation. A workstation is allowed to contain
ventilation equipment, fire protection devices, detection
devices, electrical devices and other processing and scientific
equipment.
[F] 415.3 Fire separation
distance. Group H occupancies shall
be located on property in accordance with the other provisions
of this chapter. In Groups H-2 and H-3, not less than 25 percent
of the perimeter wall of the occupancy shall be an exterior
wall.
Exceptions:
1. Liquid
use, dispensing and mixing rooms having a floor area of not
more than 500 square feet (46.5 m2)
need not be located on the outer perimeter of the building
where they are in accordance with the International
Fire Code and NFP A 30.
2. Liquid
storage rooms having a floor area of not more than 1,000 square
feet (93 m2)
need not be located on the outer perimeter where they are
in accordance with the International Fire Code and
NFP A 30.
3. Spray
paint booths that comply with the International
Fire Code need not be
located on the outer perimeter.
[F] 415.3.1 Group
H occupancy minimum fire separation distance. Regardless
of any other provisions, buildings containing Group H occupancies
shall be set back to the minimum fire separation distance
as set forth in Items 1 through 4 below. Distances shall be
measured from the walls enclosing the occupancy to lot lines,
including those on a public way. Distances to assumed lot
lines established for the purpose of determining exterior
wall and opening protection are not to be used to establish
the minimum fire separation distance for buildings on sites
where explosives are manufactured or used when separation
is provided in accordance with the quantity distance tables
specified for explosive materials in the International Fire
Code.
1.
Group H-1. Not less than 75 feet (22 860 mm) and not less
than required by the International Fire Code.
Exceptions: 1. Fireworks
manufacturing buildings separated
in accordance with NFP A 1124.
2. Buildings
containing the following materials
when separated in accordance with Table
415.3.1:
2.1. Organic peroxides, unclassified
detonable.
2.2. Unstable reactive materials,
Class 4.
2.3. Unstable reactive materials,
Class 3 detonable.
2.4. Detonable pyrophoric materials.
2. Group
H-2. Not less than 30 feet (9144 mm) where the area of the
occupancy exceeds 1,000 square feet (93 m2)
and it is not required to be located in a detached building.
3. Groups
H-2 and H-3. Not less than 50 feet (15 240 mm) where a detached
building is required (see Table
415.3.2). 4. Groups
H-2 and H-3. Occupancies containing materials
with explosive characteristics shall be separated as required
by the International Fire Code. Where separations
are not specified, the distances required shall not be less
than the distances required by Table
415.3.1.
[F] 415.3.2 Group H-l and
H-2 or H-3 detached buildings. Where a detached building
is required by Table 415.3.2,
there are no requirements for wall and opening protection
based on fire separation distance.
[F] 415.4 Special provisions
for Group H-l occupancies. Group H -1 occupancies shall
be in buildings used for no other purpose, shall not exceed
one story in height and be without a basement, crawl spaces
or other under-floor spaces. Roofs shall be of lightweight
construction with suitable thermal insulation to prevent sensitive
material from reaching its decomposition temperature. Group
H -1 occupancies containing materials which are in themselves
both physical and health hazards in quantities exceeding the
maximum allowable quantities per control area in Table
307.1(2) shall comply with requirements for both Group
H -1 and H -4 occupancies.
[F] 415.4.1 Floors in storage
rooms. Floors in storage areas for organic peroxides,
pyrophoric materials and unstable (reactive) materials shall
be of liquid-tight, noncombustible construction.
[F] 415.5 Special provisions
for Group H-2 and H-3 occupancies. Group H-2 and H-3 occupancies
containing quantities of hazardous materials in excess of
those set forth in Table 415.3.2
shall be in buildings used for no other purpose, shall not
exceed one story in height and shall be without basements,
crawl spaces or other under-floor spaces. Group H-2 and H-3
occupancies containing water-reactive materials shall be resistant
to water penetration. Piping for conveying liquids shall not
be over or through areas containing water reactives, unless
isolated by approved liquid-tight construction.
Exception: Fire protection
piping.
[F] 415.5.1 Floors in storage
rooms. Floors in storage areas for organic peroxides,
oxidizers, pyrophoric materials, unstable (reactive) materials
and water-reactive solids and liquids shall be of liquid-tight,
noncombustible construction.
a. For materials that are detonable,
the distance to other buildings or lot lines shall be as
specified in Table 415.3.1
based on trinitrotoluene (1NT) equivalence of the material.
For materials classified as explosives, see Chapter 33 the
International Fire Code. For all other materials, the distance
shall be as indicated in Section 415.3.1.
b. Maximum Allowable
Quantity" means the maximum allowable quantity per
control area set forth in Table
307.7(1).
c. Limited to Division
1.4 materials and articles, including articles packaged
for shipment, that are not regulated as an explosive under
Bureau of Alcohol, Tobacco and Firearms (BATF) regulations
or unpackaged articles used in process operations that do
not propagate a detonation or deflagration between articles,
providing the net explosive weight of individual articles
does not exceed 1 pound.
[F] 415.5.2 Waterproof room.
Rooms or areas used for the storage of water-reactive solids
and liquids shall be constructed in a manner that resists
the penetration of water through the use of waterproof materials.
Piping carrying water for other than approved automatic fire
sprinkler systems shall not be within such rooms or areas.
[F] 415.6 Group H-2.
Occupancies in Group H-2 shall be constructed in accordance
with Sections 415.6.1 through 415.6.4 and the International
Fire Code.
[F] 415.6.1 Combustible dusts,
grain processing and storage. The provisions of Sections
415.6.1.1 through 415.6.1.6 shall apply to buildings in which
materials that produce combustible dusts are stored or handled.
Buildings that store or handle combustible dusts shall comply
with the applicable provisions of NFPA 61, NFPA 120, NFPA
651, NFPA 654, NFPA 655, NFPA 664 and NFPA 85, and the International
Fire Code.
[F] 415.6.1.1 Type of construction
and height exceptions. Buildings shall be constructed
in compliance with the height and area limitations of Table
503 for Group H - 2; except that where erected of Type
I or II construction, the heights and areas of grain elevators
and similar structures shall be unlimited, and where of
Type IV construction, the maximum height shall be 65 feet
(19 812 mm) and except further that, in isolated areas,
the maximum height of Type IV structures shall be increased
to 85 feet (25 908 mm).
[F] 415.6.1.2 Grinding rooms.
Every room or space occupied for grinding or other operations
that produce combustible dusts shall be enclosed with fire
barriers that have not less than a 2-hour fire-resistance
rating where the area is not more than 3,000 square feet
(279 m2),
and not less than a 4-hour fire-resistance rating where
the area is greater than 3,000 square feet (279 m2).
[F] 415.6.1.3 Conveyors.
Conveyors, chutes, piping and similar equipment passing
through the enclosures of rooms or spaces shall be constructed
dirt tight and vapor tight, and be of approved noncombustible
materials complying with Chapter 30.
[F] 415.6.1.4 Explosion
control. Explosion control shall be provided as specified
in the International Fire Code, or spaces shall be
equipped with the equivalent mechanical ventilation complying
with the International Mechanical Code.
[F] 415.6.1.5 Grain elevators.
Grain elevators, malt houses and buildings for similar occupancies
shall not be located within 30 feet (9144 mm) of interior
lot lines or structures on the same lot, except where erected
along a railroad right-of-way.
[F] 415.6.1.6 Coal pockets.
Coal pockets located less than 30 feet (9144 mm) from interior
lot lines or from structures on the same lot shall be constructed
of not less than Type IE construction. Where more than 30
feet (9144 mm) from interior lot lines, or where erected
along a railroad right-of-way, the minimum type of construction
of such structures not more than 65 feet (19 812 mm) in
height shall be Type IV.
[F] 415.6.2 Flammable
and combustible liquids. The storage, handling, processing
and transporting of flammable and combustible liquids shall
be in accordance with the International Mechanical Code and
the International Fire Code.
[F] 415.6.2.1 Mixed occupancies.
Where the storage tank area is located in a building of
two or more occupancies, and the quantity of liquid exceeds
the maximum allowable quantity for one control area, the
use shall be completely separated from adjacent fire areas
in accordance with the requirements of Section
508.3.3.
[F] 415.6.2.1.1 Height
exception. Where storage tanks are located within
only a single-story building, the height limitation of
Section 503 shall not apply for
Group H. [F] 415.6.2.2
Tank protection. Storage tanks shall be noncombustible
and protected from physical damage. A fire barrier wall
or horizontal assemblies or both around the storage tank
(s) shall be permitted as the method of protection from
physical damage.
[F] 415.6.2.3 Tanks.
Storage tanks shall be approved tanks conforming to the
requirements of the International Fire Code.
[F] 415.6.2.4 Suppression.
Group H shall be equipped throughout with an approved
automatic sprinkler system, installed in accordance with
Section 903.
[F] 415.6.2.5 Leakage
containment. A liquid-tight containment area compatible
with the stored liquid shall be provided. The method of
spill control, drainage control and secondary containment
shall be in accordance with the International Fire Code.
Exception: Rooms where only
double-wall storage tanks conforming to Section 415.6.2.3 are
used to store Class I, II and IlI A flammable and combustible
liquids shall not be required to have a leakage containment
area.
[F] 415.6.2.6 Leakage
alarm. An approved automatic alarm shall be provided
to indicate a leak in a storage tank and room. The alarm
shall sound an audible signal, 15 dBa above the ambient
sound level, at every point of entry into the room in
which the leaking storage tank is located. An approved
sign shall be posted on every entry door to the tank storage
room indicating the potential hazard of the interior room
environment, or the sign shall state:
WARNING, WHEN ALARM SOUNDS,
THE ENVIRONMENT WITHIN THE ROOM MAY BE HAZARDOUS.
The leakage alarm shall also be supervised in accordance
with Chapter 9 to transmit a trouble signal.
[F] 415.6.2.7 Tank vent.
Storage tank vents for Class I, II or IlIA liquids shall
terminate to the outdoor air in accordance with the International
Fire Code.
[F] 415.6.2.8 Room ventilation.
Storage tank areas storing Class I, II or IlIA liquids
shall be provided with mechanical ventilation. The mechanical
ventilation system shall be in accordance with the International
Mechanical Code and the International Fire Code.
[F] 415.6.2.9 Explosion
venting. Where Class I liquids are being stored, explosion
venting shall be provided in accordance with the International
Fire Code.
[F] 415.6.2.10 Tank openings
other than vents. Tank openings other than vents from
tanks inside buildings shall be designed to ensure that
liquids or vapor concentrations are not released inside
the building.
[F] 415.6.3 Liquefied
petroleum gas-distribution facilities. The design and
construction of propane, butane, propylene, butylene and other
liquefied petroleum gas-distribution facilities shall conform
to the applicable provisions of Sections 415.6.3.1 through
415.6.3.5.2. The storage and handling of liquefied petroleum
gas systems shall conform to the International Fire Code.
The design and installation of piping, equipment and systems
that utilize liquefied petroleum gas shall be in accordance
with the International Fuel Gas Code. Liquefied petroleum
gas-distribution facilities shall be ventilated in accordance
with the International Mechanical Code and Section 415.6.3.1.
[F] 415.6.3.1 Air movement.
Liquefied petroleum gas distribution facilities shall
be provided with air inlets and outlets arranged so that
air movement across the floor of the facility will be
uniform. The total area of both inlet and outlet openings
shall be at least 1 square inch (645 mm2)
for each 1 square foot (0.093 m2)
of floor area. The bottom of such openings shall not be
more than 6 inches (152 mm) above the floor.
[F] 415.6.3.2 Construction.
Liquefied petroleum gas-distribution facilities shall
be constructed in accordance with Section 415 .6.3.3 for
separate buildings, Section 415.6.3.4 for attached buildings
or Section 415.6.3.5 for rooms within buildings.
[F] 415.6.3.3 Separate
buildings. Where located in separate buildings, liquefied
petroleum gas-distribution facilities shall be occupied
exclusively for that purpose or for other purposes having
similar hazards. Such buildings shall be limited to one
story in height and shall conform to Sections 415.6.3.3.1
through 415.6.3.3.3.
[F] 415.6.3.3.1 Floors.
The floor shall not be located below ground level and
any spaces beneath the floor shall be solidly filled
or shall be unenclosed.
[F] 415.6.3.3.2 Materials.
Walls, floors, ceilings, columns and roofs shall be
constructed of noncombustible materials.
[F] 415.6.3.3.3 Explosion
venting. Explosion venting shall be provided in
accordance with the International Fire Code.
[F] 415.6.3.4
Attached buildings. Where liquefied petroleum gas-distribution
facilities are located in an attached structure, the attached
perimeter shall not exceed 50 percent of the perimeter of
the space enclosed and the facility shall comply with Sections
415.6.3.3 and 415.6.3.4.1. Where the attached perimeter
exceeds 50 percent, such facilities shall comply with Section
415.6.3.5.
[F] 415.6.3.4.1
Fire separation. Separation of the attached structures
shall be provided by fire barriers having a fire-resistance
rating of not less than 1
hour and shall
not have openings. Fire barriers between attached structures
occupied only for the storage of LP-gas are permitted
to have fire door assemblies that comply with Section
715. Such fire barriers shall be designed to withstand
a static pressure of at least 100 pounds per square foot
(psf) (4788 Pa), except where the building to which the
structure is attached is occupied by operations or processes
having a similar hazard.
[F] 415.6.3.5
Rooms within buildings. Where liquefied petroleum gas-distribution
facilities are located in rooms within buildings, such rooms
shall be located in the first story above grade plane and
shall have at least one exterior wall with sufficient exposed
area to provide explosion venting as required in the International
Fire Code. The building in which the room is located
shall not have a basement or unventilated crawl space and
the room shall comply with Sections 415.6.3.5.1 and 415.6.3.5.2.
[F] 415.6.3.5.1 Materials.
Walls, floors, ceilings and roofs of such rooms shall
be constructed of approved noncombustible materials.
[F] 415.6.3.5.2 Common
construction. Walls and floor/ceiling assemblies
common to the room and to the building where the room
is located shall be fire barriers with not less than
a l-hour fire-resistance rating and without openings.
Common walls for rooms occupied only for storage of
LP-gas are permitted to have opening protectives complying
with Section 715. The walls and
ceilings shall be designed to withstand a static pressure
of at least 100 psf (4788 Pa).
Exception: Where the building,
within which the room is located, is occupied by operations
or processes having a similar hazard.
[F] 415.6.4 Dry
cleaning plants. The construction and installation of
dry cleaning plants shall be in accordance with the requirements
of this code, the International Mechanical Code, the International
Plumbing Code and NFPA 32. Dry cleaning solvents and
systems shall be classified in accordance with the International
Fire Code.
[F]
415.7 Groups H-3 and H-4. Groups H-3 and H-4 shall be constructed
in accordance with the applicable provisions of this code and
the International Fire Code.
[F] 415.7.1 Gas rooms.
When gas rooms are provided, such rooms shall be separated
from other areas by not less than a l-hour fire barrier.
[F] 415.7.2 Floors in storage
rooms. Floors in storage areas for corrosive liquids
and highly toxic or toxic materials shall be of liquid-tight,
noncombustible construction.
[F] 415.7.3 Separation-highly
toxic solids and liquids. Highly toxic solids and liquids
not stored in approved hazardous materials storage cabinets
shall be isolated from other hazardous materials storage
by a fire barrier having a fire-resistance rating of not
less than 1 hour.
[F] 415.8 Group H-5.
[F] 415.8.1 General.
In addition to the requirements set forth elsewhere in this
code, Group H-5 shall comply with the provisions of Section
415.8 and the International Fire Code.
[F] 415.8.2 Fabrication
areas.
[F] 415.8.2.1
Hazardous materials in fabrication areas.
[F] 415.8.2.1.1
Aggregate quantities. The aggregate quantities of
hazardous materials stored and used in a single fabrication
area shall not exceed
the quantities set forth in Table
415.8.2.1.1.
Exception: The quantity limitations
for any hazard category in Table
415.8.2.1.1 shall not apply where the fabrication area contains
quantities of hazardous materials not exceeding the maximum
allowable quantities per control area established by Tables
307.1(1) and 307.1(2).
[F] 415.8.2.1.2
Hazardous production materials. The maximum quantities
of hazardous production materials (HPM) stored in a single
fabrication area shall not exceed the maximum allowable
quantities per control area established by Tables
307.1(1) and 307.1(2).
[F] 415.8.2.2
Separation. Fabrication areas, whose sizes are limited
by the quantity of hazardous materials allowed by Table
415.8.2.1.1, shall be
separated from each other, from corridors and from other
parts of the building by not less than l-hour fire barriers.
Exceptions:
1. Doors within
such fire barrier walls, including doors to corridors, shall
be only self-closing fire door assemblies having a fire protection
rating of not less than 3/4 hour. 2. Windows
between fabrication areas and corridors are permitted to be
fixed glazing listed and labeled for a fire protection rating
of at least 3/4 hour in accordance with
Section 715.
[F] 415.8.2.3
Location of occupied levels. Occupied levels of fabrication
areas shall be located at or above the first story above
grade plane.
[F] 415.8.2.4 Floors.
Except for surfacing, floors within fabrication areas
shall be of noncombustible construction.Openings through
floors of fabrication areas are permitted to be unprotected
where the interconnected levels are used solely for
mechanical equipment directly related to such fabrication
areas (see also Section 415.8.2.5). Floors forming
a part of an occupancy separation shall be liquid tight.
[F] 415.8.2.5 Shafts
and openings through floors. Elevator shafts, vent
shafts and other openings through floors shall be enclosed
when required by Section 707.
Mechanical, duct and piping penetrations within a fabrication
area shall not extend through more than two floors.
The annular space around penetrations for cables, cable
trays, tubing, piping, conduit or ducts shall be sealed
at the floor level to restrict the movement of air.
The fabrication area, including the areas through which
the ductwork and piping extend, shall be considered
a single conditioned environment.
[F] 415.8.2.6 Ventilation.
Mechanical exhaust ventilation at the rate of not less
than 1 cubic foot per minute per square foot (0.044
L/s/m2) of floor area shall be provided throughout
the portions of the fabrication area where HPM are used
or stored. The exhaust air duct system of one fabrication
area shall not connect to another duct system outside
that fabrication area within the building. A ventilation
system shall be provided to capture and exhaust gases,
fumes and vapors at workstations. Two or more operations
at a workstation shall not be connected to the same
exhaust system where either one or the combination of
the substances removed could constitute a fire, explosion
or hazardous chemical reaction within the exhaust duct
system. Exhaust ducts penetrating occupancy separations
shall be contained in a shaft of equivalent fire-resistance-rated
construction. Exhaust ducts shall not penetrate fire
walls. Fire dampers shall not be installed in
exhaust ducts .
[F] 415.8.2.7 Transporting
hazardous production materials to fabrication areas.
HPM shall be transported to fabrication areas through
enclosed piping or tubing systems that comply with Section
415.8.6.1, through service corridors complying with
Section 415.8.4, or in corridors as permitted in the
exception to Section 415.8.3. The handling or transporting
of HPM within service corridors shall comply with the
International Fire Code.
[F] 415.8.2.8
Electrical.
[F] 415.8.2.8.1 General.
Electrical equipment and devices within the fabrication
area shall comply with the ICC Electrical Code.
The requirements for hazardous locations need
not be applied where the average air change is at
least four times that set forth in Section 415.8.2.6
and where the number of air changes at any location
is not less than three times that required by Section
415.8.2.6. The use of recalculated air shall be permitted.
[F] 415.8.2.8.2 Workstations.
Workstations shall not be energized without adequate
exhaust ventilation. See Section 415.8.2.6 for workstation
exhaust ventilation requirements.
[F] 415.8.3 Corridors.
Corridors shall comply with Chapter 10 and shall be separated
from fabrication areas as specified in Section 415.8.2.2.
Corridors shall not contain HPM and shall not be used for
transporting such materials, except through closed piping
systems as provided in Section 415.8.6.3.
Exception: Where existing
fabrication areas are altered or modified, HPM is allowed to
be transported in existing corridors, subject to the following
conditions:
1. Corridors.
Corridors adjacent to the fabrication area where the alteration
work is to be done shall comply with Section
1017 for a length determined as follows:
1.1 The length of
the common wall of the corridor and the fabrication
area; and
1.2. For the distance along
the corridor to the point of entry of HPM into the corridor
serving that fabrication area.
2. Emergency alarm system.
There shall be an emergency telephone system, a local
manual alarm station or other approved alarm-initiating
device within corridors at not more than ISO-foot (45
720 mm) intervals and at each exit and doorway. The signal
shall be relayed to an approved central, proprietary or
remote station service or the emergency control station
and shall also initiate a local audible alarm.
3. Pass throughs. Self-closing
doors having a fire protection rating of not less than
1 hour shall separate pass-throughs from existing corridors.
Pass-throughs shall be constructed as required for the
corridors and protected by an approved automatic fire-extinguishing
system.
[F] 415.8.4 Service
corridors.
[F] 415.8.4.1 Occupancy.
Service corridors shall be classified as Group H-5.
[F] 415.8.4.2 Use conditions.
Service corridors shall be separated from corridors as
required by Section 415.8.2.2. Service corridors shall
not be used as a required corridor.
[F] 415.8.4.3 Mechanical
ventilation. Service corridors shall be mechanically
ventilated as required by Section 415.8.2.6 or at not
less than six air changes per hour, whichever is greater.
[F] 415.8.4.4 Means of
egress. The maximum distance of travel from any point
in a service corridor to an exit, exit access corridor
or door into a fabrication area shall not exceed 75 feet
(22 860 mm). Dead ends shall not exceed 4 feet (1219 mm)
in length. There shall be not less than two exits, and
not more than one-half of the required means of egress
shall require travel into a fabrication area. Doors from
service corridors shall swing in the direction of egress
travel and shall be self-closing.
[F] 415.8.4.5 Minimum
width. The minimum clear width of a service corridor
shall be 5 feet (1524 mm), or 33 inches (838 mm) wider
than the widest cart or truck used in the corridor, whichever
is greater.
[F] 415.8.4.6 Emergency
alarm system. Emergency alarm systems shall be provided
in accordance with this section and Sections
414.7.1 and 414.7.2. The
maximum allowable quantity per control area provisions
shall not apply to emergency alarm systems required for
HPM.
[F] 415.8.4.6.1 Service
corridors. An emergency alarm system shall be provided
in service corridors, with at least one alarm device
in each service corridor.
[F] 415.8.4.6.2 Exit
access corridors and exit enclosures. Emergency
alarms for exit access corridors and exit enclosures
shall comply with Section 414.7.2.
[F] 415.8.4.6.3 Liquid
storage rooms, RPM rooms and gas rooms. Emergency
alarms for liquid storage rooms, HPM rooms and gas rooms
shall comply with Section 414.7.1.
[F] 415.8.4.6.4 Alarm-initiating
devices. An approved emergency telephone system,
local alarm manual pull stations, or other approved
alarm-initiating devices are allowed to be used as emergency
alarm-initiating devices.
[F] 415.8.4.6.5 Alarm
signals. Activation of the emergency alarm system
shall sound a local alarm and transmit a signal to the
emergency control station.
[F] 415.8.5 Storage of hazardous
production materials.
[F] 415.8.5.1 General.
Storage of HPM in fabrication areas shall be within
approved or listed storage cabinets or gas cabinets
or within a workstation. The storage of HPM in quantities
greater than those listed in Section
1804.2 of the International Fire Code shall be
in liquid storage rooms, HPM rooms or gas rooms as
appropriate for the materials stored. The storage
of other hazardous materials shall be in accordance
with other applicable provisions of this code and
the International Fire Code.
[F] 415.8.5.2 Construction.
[F] 415.8.5.2.1
RPM rooms and gas rooms. HPM rooms and gas rooms
shall be separated from other areas by not less
than a 2-hour fire barrier where the area is 300
square feet (27.9 m2)
or more and not less than a l-hour fire barrier
where the area is less than 300 square feet (27.9
m2),
[F] 415.8.5.2.2
Liquid storage rooms. Liquid storage rooms
shall be constructed in accordance with the following
requirements:
1. Rooms
in excess of 500 square feet (46.5 m2)
shall have at least one exterior door approved
for fire department access.
2. Rooms
shall be separated from other areas by fire barriers
having a fire-resistance rating of not less than
1-hour for rooms up to 150 square feet (13.9 m2)
in area and not less than 2 hours where the room
is more than 150 square feet (13.9 m2)
in area.
3. Shelving,
racks and wainscoting in such areas shall be of
noncombustible construction or wood of not less
than 1 inch (25 mm) nominal thickness. 4. Rooms
used for the storage of Class I flammable
liquids shall not be located in a basement.
[F] 415.8.5.2.3 Floors.
Except for surfacing, floors of HPM rooms and liquid
storage rooms shall be of noncombustible liquid-tight
construction. Raised grating over floors shall be
of noncombustible materials.
[F] 415.8.5.3 Location.
Where HPM rooms, liquid storage rooms and gas rooms
are provided, they shall have at least one exterior
wall and such wall shall be not less than 30 feet (9144
mm) from lot lines, including lot lines adjacent to
public ways.
[F] 415.8.5.4 Explosion
control. Explosion control shall be provided where
required by Section 414.5.1.
[F] 415.8.5.5 Exits.
Where two exits are required from HPM rooms, liquid
storage rooms and gas rooms, one shall be directly to
the outside of the building.
[F] 415.8.5.6 Doors.
Doors in a fire barrier wall, including doors to corridors,
shall be self-closing fire door assemblies having a
fire-protection rating of not less than 3/4
hour.
[F] 415.8.5.7 Ventilation.
Mechanical exhaust ventilation shall be provided in
liquid storage rooms, HPM rooms and gas rooms at the
rate of not less than 1 cubic foot per minute per square
foot (0.044 L/s/m2)
of floor area or six air changes per hour, whichever
is greater, for categories of material. Exhaust ventilation
for gas rooms shall be designed to operate at a negative
pressure in relation to the surrounding areas and direct
the exhaust ventilation to an exhaust system.
[F] 415.8.5.8 Emergency
alarm system. An approved emergency alarm system
shall be provided for HPM rooms, liquid storage rooms
and gas rooms. Emergency alarm-initiating devices shall
be installed outside of each interior exit door of such
rooms. Activation of an emergency alarm-initiating device
shall sound a local alarm and transmit a signal to the
emergency control station. An approved emergency telephone
system, local alarm manual pull stations or other approved
alarm-initiating devices are allowed to be used as
emergency alarm-initiating devices.
[F] 415.8.6 Piping
and tubing.
[F] 415.8.6.1 General.
Hazardous production materials piping and tubing shall
comply with this section and ASME B31.3.
[F] 415.8.6.2 Supply piping
and tubing.
[F] 415.8.6.2.1 RPM
having a health-hazard ranking of 3 or 4. Systems
supplying HPM liquids or gases having a health-hazard
ranking on or 4 shall be welded throughout, except for
connections, to the systems that are within a ventilated
enclosure if the material is a gas, or an approved method
of drainage or containment is provided for the connections
if the material is a liquid.
[F] 415.8.6.2.2 Location
in service corridors. Hazardous production materials
supply piping or tubing in service corridors shall be
exposed to view.
[F] 415.8.6.2.3 Excess
flow control. Where HPM gases or liquids are carried
in pressurized piping above 15 pounds per square inch
gauge (psig) (103.4 kPa), excess flow control shall
be provided. Where the piping originates from within
a liquid storage room, HPM room or gas room, the excess
flow control shall be located within the liquid storage
room, HPM room or gas room. Where the piping originates
from a bulk source, the excess flow control shall be
located as close to the bulk source as practical.
[F] 415.8.6.3 Installations
in corridors and above other
occupancies. The installation of HPM piping and tubing
within the space defined by the walls of corridors and the
floor or roof above, or in concealed spaces above other
occupancies, shall be in accordance with Section 415.8.6.2
and the following conditions:
1. Automatic
sprinklers shall be installed within the space unless
the space is less than 6 inches (152 mm) in the least
dimension.
2. Ventilation
not less than six air changes per hour shall be provided.
The space shall not be used to convey air from any other
area.
3. Where
the piping or tubing is used to transport HPM liquids,
a receptor shall be installed below such piping or tubing.
The receptor shall be designed to collect any discharge
or leakage and drain it to an approved location. The
I-hour enclosure shall
not be used as part of the receptor.
4. HPM
supply piping and tubing and nonmetallic waste lines
shall be separated from the corridor and from occupancies
other than Group H-5 by fire barriers that have a fire-resistance
rating of not
less than 1 hour.
Where gypsum wallboard is used, joints on the piping
side of the enclosure are not required to be taped,
provided the joints occur over framing members. Access
openings into the enclosure shall be protected by approved
fire protection-rated assemblies.
5. Readily accessible
manual or automatic remotely activated fail-safe emergency
shutoff valves shall be installed on piping and tubing
other than waste lines at the following locations:
5.1. At branch
connections into the fabrication area. 5.2.
At entries into corridors.
Exception: Transverse crossings
of the corridors by supply piping that is enclosed within a
ferrous pipe or tube for the width of the corridor need not
comply with Items 1 through 5.
[F] 415.8.6.4
Identification. Piping, tubing and HPM waste lines shall
be identified in accordance with ANSI A13.1 to indicate
the material being transported.
[F] 415.8.7 Continuous
gas detection systems. A continuous gas detection system
shall be provided for HPM gases when the physiological warning
threshold level of the gas is at a higher level than the accepted
PEL for the gas and for flammable gases in accordance with
this section.
[F] 415.8.7.1
Where required. A continuous gas-detection system shall
be provided in the areas identified in Sections 415.8.7.1.1
through 415.8.7.1.4.
[F] 415.8.7.1.1
Fabrication areas. A continuous gas-detection system
shall be provided in fabrication areas when gas is used
in the fabrication area.
[F] 415.8.7.1.2 RPM rooms.
A continuous gas-detection system shall be provided in
HPM rooms when gas is used in the room.
[F] 415.8.7.1.3 Gas cabinets,
exhausted enclosures and gas rooms. A continuous gas-detection
system shall be provided in gas cabinets and exhausted
enclosures. A continuous gas-detection system shall be
provided in gas rooms when gases are not located in gas
cabinets or exhausted enclosures.
[F] 415.8.7.1.4 Corridors.
When gases are transported in piping placed within the
space defined by the walls of a corridor and the floor
or roof above the corridor, a continuous gas-detection
system shall be provided where piping is located and in
the corridor.
Exception: A continuous gas-detection
system is not required for occasional transverse crossings of
the corridors by supply piping that is enclosed in a ferrous
pipe or tube for the width of the corridor.
[F] 415.8.7.2 Gas-detection
system operation. The continuous gas-detection system
shall be capable of monitoring the room, area or equipment
in which the gas is located at or below the PEL or ceiling
limit of the gas for which detection is provided. For flammable
gases, the monitoring detection threshold level shall be vapor
concentrations in excess of 20 percent of the lower explosive
limit (LEL). Monitoring for highly toxic and toxic gases shall
also comply with the requirements for such material in the
International Fire Code.
[F] 415.8.7.2.1 Alarms.
The gas detection system shall initiate a local alarm
and transmit a signal to the emergency control station
when a short-term hazard condition is detected. The alarm
shall be both visual and audible and shall provide warning
both inside and outside the area where the gas is detected.
The audible alarm shall be distinct from all other alarms.
[F] 415.8.7.2.2 Shutoff
of gas supply. The gas detection system shall automatically
close the shutoff valve at the source on gas supply piping
and tubing related to the system being monitored for which
gas is detected when a short-term hazard condition is
detected. Automatic closure of shutoff valves shall comply
with the following:
1. Where
the gas-detection sampling point initiating
the gas detection system alarm is within a gas cabinet
or exhausted enclosure, the shutoff valve in the gas cabinet
or exhausted enclosure for the specific gas detected shall
automatically close.
2. Where
the gas-detection sampling point initiating
the gas detection system alarm is within a room and compressed
gas containers are not in gas cabinets or an exhausted
enclosure, the shutoff valves on all gas lines for the
specific gas detected shall automatically close.
3. Where
the gas-detection sampling point initiating
the gas detection system alarm is within a piping distribution
manifold enclosure, the shutoff valve supplying the manifold
for the compressed gas container of the specific gas detected
shall automatically close.
Exception: Where the gas-detection
sampling point initiating the gas detection system alarm is
at the use location or within a gas valve enclosure of a branch
line downstream of a piping distribution manifold, the shutoff
valve for the branch line located in the piping distribution
manifold enclosure shall automatically close.
[F] 415.8.8 Manual fire
alarm system. An approved manual fire alarm system shall
be provided throughout buildings containing Group H-5. Activation
of the alarm system shall initiate a local alarm and transmit
a signal to the emergency control station. The fire alarm
system shall be designed and installed in accordance with
Section 907.
415.8.9 Emergency control
station. An emergency control station shall be provided
in accordance with Sections 415.8.9.1 through 415.8.9.3.
415.8.9.1 Location.
The emergency control station shall be located on the
premises at an approved location outside the fabrication
area.
415.8.9.2 Staffing.
Trained personnel shall continuously staff the emergency
control station.
415.8.9.3 Signals.
The emergency control station shall receive signals from
emergency equipment and alarm and detection systems. Such
emergency equipment and alarm and detection systems shall
include, but not be limited to, the following where such
equipment or systems are required to be provided either
in this chapter or else where in this code:
I. Automatic
fire sprinkler system alarm and monitoring
systems.
2. Manual
fire alarm systems.
3. Emergency
alarm systems.
4. Continuous
gas-detection systems.
5. Smoke
detection systems.
6. Emergency
power system.
7. Automatic
detection and alarm systems for pyrophoric liquids and
Class 3 water-reactive liquids
required in Section 1805.2.3.5
of the International Fire Code.
8. Exhaust
ventilation flow alarm devices for pyrophoric liquids
and Class 3 water-reactive liquids
cabinet exhaust ventilation systems required in Section
1805.2.3.5 of the International Fire Code.
[F] 415.8.10 Emergency
power system. An emergency power system shall be provided
in Group H-5 occupancies where required in Section 415.8.10.1.
The emergency power system shall be designed to supply power
automatically to required electrical systems when the normal
electrical supply system is interrupted.
[F] 415.8.10.1
Required electrical systems. Emergency power shall be
provided for electrically operated equipment and connected
control circuits for the following systems:
1. HPM
exhaust ventilation systems.
2. HPM
gas cabinet ventilation systems.
3. HPM
exhausted enclosure ventilation systems.
4. HPM
gas room ventilation systems.
5. HPM
gas detection systems.
6. Emergency
alarm systems.
7. Manual
fire alarm systems.
8.
Automatic
sprinkler system monitoring and alarm systems.
9. Automatic
alarm and detection systems for pyrophoric liquids and
Class 3 water-reactive liquids required in Section
1805.2.3.5 of the International Fire Code.
10. Flow
alarm switches for pyrophoric liquids and Class 3 water-reactive
liquids cabinet exhaust ventilation systems required
in Section 1805.2.3.5 of
the International Fire Code.
11. Electrically
operated systems required elsewhere in this code or
in the International Fire Code
applicable to the use, storage
or handling of HPM.
[F] 415.8.10.2
Exhaust ventilation systems. Exhaust ventilation systems
are allowed to be designed to operate at not less than one-half
the normal fan speed on the emergency power system where
it is demonstrated that the level of exhaust will maintain
a safe atmosphere.
[F] 415.8.11 Automatic
sprinkler system protection in exhaust ducts for RPM.
[F] 415.8.11.1 Exhaust
ducts for RPM. An approved automatic sprinkler system
shall be provided in exhaust ducts conveying gases, vapors,
fumes, mists or dusts generated
from HPM in accordance with this section and the International
Mechanical Code.
[F] 415.8.11.2 Metallic
and noncombustible nonmetallic exhaust ducts. An approved
automatic sprinkler system shall be provided in metallic
and noncombustible nonmetallic exhaust ducts when all
of the following conditions apply:
1. Where
the largest cross-sectional diameter is equal to or
greater than 10 inches (254 mm).
2. The dusts are within
the building.
3. The
ducts are conveying flammable gases, vapors
or fumes.
[F] 415.8.11.3 Combustible
nonmetallic exhaust ducts. Automatic sprinkler system
protection shall be provided in combustible nonmetallic
exhaust ducts where the largest cross-sectional diameter
of the duct is equal to or greater than 10 inches (254 mm).
Exceptions:
1. Ducts listed or approved
for applications without automatic fire sprinkler system
protection.
2. Ducts not more than
12 feet (3658 mm) in length installed below ceiling level.
[F] 415.8.11.4
Automatic sprinkler locations. Sprinkler systems shall
be installed at 12-foot (3658 mm) intervals in horizontal
ducts and at changes in direction. In vertical ducts, sprinklers
shall be installed at the top and at alternate floor levels.
|