|
|
|
|
|
SECTION 715 OPENING PROTECTIVES
715.1 General. Opening
protectives required by other sections of this code shall
comply with the provisions of this section.
715.2 Fire-resistance-rated
glazing. Labeled fire-resistance-rated glazing tested
as part of a fire-resistance-rated wall assembly in accordance
with ASTM E 119 shall not be required to comply with this
section.
715.3 Alternative methods
for determining fire protection ratings. The application
of any of the alternative methods listed in this section shall
be based on the fire exposure and acceptance criteria specified
in NFPA 252 or NFPA 257. The required fire resistance of an
opening protective shall be permitted to be established by
any of the following methods or procedures:
1.
Designs documented in approved sources. 2.
Calculations performed in an approved manner.
3.
Engineering analysis based on a comparison of opening protective
designs having fire-protection ratings as determined by the
test procedures set forth in NFP A 252 orNFPA257.
4.
Alternative protection methods as allowed by Section
104.11.
715.4 Fire door and shutter
assemblies. Approved fire door and fire shutter assemblies
shall be constructed of any material or assembly of component
materials that conforms to the test requirements of Section
715.4.1, 715.4.2 or 715.4.3 and the fire-protection rating
indicated in Table 715.4. Fire
door assemblies and shutters shall be installed in accordance
with the provisions of this section and NFPA 80.
Exceptions:
1.Labeled
protective assemblies that conform to the requirements of
this section or UL lOA, UL 14 Band UL 14C for tin-clad fire
door assemblies.
2.Floor
fire door assemblies in accordance with Section
711.8.
715.4.1 Side-hinged or pivoted
swinging doors. Sidehinged and pivoted swinging doors
shall be tested in accordance with NFPA 252 or UL lOCo After
5 minutes into the NFPA 252 test, the neutral pressure level
in the furnace shall be established at 40 inches (l0 16
mm) or less above the sill.
715.4.2 Other types of doors.
Other types of doors, including swinging elevator doors,
shall be tested in accordance withNFPA252 or UL lOB. The
pressure in the furnace shall be maintained as nearly equal
to the atmospheric pressure as possible. Once established,
the pressure shall be maintained during the entire test
period.
715.4.3 Door assemblies
in corridors and smoke barriers. Fire door assemblies
required to have a minimum fire protection rating of 20
minutes where located in corridor walls or smoke-barrier
walls having a fire-resistance rating in accordance with
Table 715.4 shall be tested
in accordance with NFPA 252 or UL lOC without the hose stream
test.
Exceptions:
1.View
ports that require a hole not larger than 1 inch (25 mm) in
diameter through the door, have at least a 0.25-inch-thick
(6.4 mm) glass disc and the holder is of metal that will not
melt out where subject to temperatures
of 1,700°F (927°C). 2.Corridor
door assemblies in occupancies of Group 1-2 shall be in accordance
with Section 407.3.1.
3.Unprotected
openings shall be permitted for corridors
in multithreaded complexes where each motion picture auditorium
has at least one-half of its required exit or exit access
doorways opening directly to the exterior or into an exit
passageway.
715.4.3.1 Smoke
and draft control. Fire door assemblies shall also
meet the requirements for a smoke and draft control door
assembly tested in accordance with UL 1784. Louvers shall
be prohibited. Installation of smoke doors shall be in accordance
with NFPA 105.
715.4.3.2 Glazing
in door assemblies. In a 20-minute fire door assembly,
the glazing material in the door itself shall have a minimum
fire-protection rating of 20 minutes and shall be exempt
from the hose stream test. Glazing material in any other
part of the door assembly, including transom lites and side
lites, shall be tested in accordance with NFPA 257, including
the hose stream test, in accordance with Section
715.5.
715.4.4 Doors in
exit enclosures and exit passageways. Fire door assemblies
in exit enclosures and exit passageways shall have a maximum
transmitted temperature end point of not more than 450°F (250°
C) above ambient at the end of 30 minutes of standard fire
test exposure.
Exception: The maximum transmitted
temperature rise
I is not limited in
buildings equipped throughout with an automatic sprinkler system
installed in accordance with Section
903.3.1.1 or 903.3.1.2.
715.4.4.1 Glazing
in doors. Fire-protection-rated glazing in excess of
100 square inches (0.065 m2) shall be permitted
in fire door assemblies when tested in accordance with NFPA
252 as components of the door assemblies and not as glass
lights, and shall have a maximum transmitted temperature
rise of 450°F (250°C) in accordance with Section 715.4.4.
Exception: The maximum
transmitted temperature end point is not required in buildings
equipped throughout with an automatic sprinkler system installed
in accordance with Section 903.3.1.1
or 903.3.1.2.
715.4.5 Labeled
protective assemblies. Fire door assemblies shall be
labeled by an approved agency. The labels shall comply with
NFPA 80, and shall be permanently affixed to the door or frame.
715.4.5.1 Fire door labeling
requirements. Fire doors shall be labeled showing
the name of the manufacturer, the name of the third-party
inspection agency, the fire protection rating and, where
required for fire doors in exit enclosures and exit passageways
by Section 715.4.4, the maximum transmitted temperature
end point. Smoke and draft control doors complying with
UL 1784 shall be labeled as such. Labels shall be approved
and permanently affixed. The label shall be applied at
the factory or location where fabrication and assembly
are performed.
715.4.5.2 Oversized doors.
Oversized fire doors shall bear an oversized fire door
label by an approved agency or shall be provided with
a certificate of inspection furnished by an approved testing
agency. When a certificate of inspection is furnished
by an approved testing agency, the certificate shall state
that the door conforms to the requirements of design,
materials and construction, but has not been subjected
to the fire test.
715.4.5.3 Smoke and draft
control door labeling requirements. Smoke and draft
control doors complying with UL 1784 shall be labeled
in accordance with Section 715.4.5.1 and shall show the
letter "S" on the fire rating label of the door.
This marking shall indicate that the door and frame assembly
are in compliance when listed or labeled gasketing is
also installed.
715.4.5.4 Fire door frame
labeling requirements. Fire door frames shall be labeled
showing the names of the manufacturer and the third-party
inspection agency.
715.4.6 Glazing
material. Fire-protection-rated glazing conforming to
the opening protection requirements in Section 715.4 shall
be permitted in fire door assemblies.
715.4.6.1 Size
limitations. Wired glass used in fire doors shall comply
with Table 715.5.3. Other
fire-protection-rated glazing shall comply with the size
limitations of NFPA 80.
Exceptions:
I.
Fire-protection-rated glazing
in fire doors located in fire walls shall be prohibited except
that where serving as a horizontal exit, a self- losing swinging
door shall be permitted to have a vision panel of not more
than 100 square inches (0.065 m'2) without a dimension
exceeding 10 inches (254 mm).
2.Fire-protection-rated
glazing shall not be installed in fire doors having a 11/2-hour
fire protection rating intended for installation in fire barriers,
unless the glazing is not more than 100 square inches (0.065
m2) in area.
715.4.6.2 Exit
and elevator protectives. Approved fire-protection-rated
glazing used in fire door assemblies in elevator and exit
enclosures shall be so located as to furnish clear vision
of the passageway or approach to the elevator, ramp or stairway.
715.4.6.3 Labeling.
Fire-protection-rated glazing shall bear a label or other
identification showing the name of the manufacturer, the
test standard and information required in Section 715.5.8.1
that shall be issued by an approved agency and shall be
permanently affixed to the glazing.
715.4.6.3.1
Identification. For fire-protection-rated glazing,
the label shall bear the following four-part identification:
"D - H or NH - T or NT - XXX." "D"
indicates that the glazing shall be used in fire door
assemblies and that the glazing meets the fire resistance
requirements of the test standard. "H" shall
indicate that the glazing meets the hose stream requirements
of the test standard. "NH" shall indicate that
the glazing does not meet the hose stream requirements
of the test. "T" shall indicate that the glazing
meets the temperature requirements of Section 715.4.4.1.
"NT" shall indicate that the glazing does not
meet the temperature requirements of Section 715.4.4.1.
The placeholder "XXX" shall specify the fire-protection-rating
period, in minutes.
715.4.6.4 Safety
glazing. Fire-protection-rated glazing installed in
fire doors or fire window assemblies in areas subject to
human impact in hazardous locations shall comply with Chapter
24.
715.4.7 Door closing.
Fire doors shall be self- or automatic closing in accordance
with this section.
Exceptions:
I. Fire
doors located in common walls separating sleeping units in
Group R-I shall be permitted without automatic- or self-closing
devices.
2. The
elevator car doors and the associated hoist way
I
enclosure doors at the floor level
designated for recall in accordance with Section
3003.2 shall be permitted to remain open during Phase
I emergency recall operation.
715.4.7.1 Latch required.
Unless otherwise specifically permitted, single fire doors
and both leaves of pairs of side-hinged swinging fire
doors shall be provided with an active latch bolt that
will secure the door when it is closed.
715.4.7.2 Automatic-closing
fire door assemblies. Automatic-closing fire door
assemblies shall be self-closing in accordance with NFPA
80.
715.4.7.3 Smoke-activated
doors. Automatic-closing doors installed in the following
locations shall be automatic closing by the actuation
of smoke detectors installed in accordance with Section
907.10 or by loss of power to the smoke detector or
hold open device. Doors that are automatic closing by
smoke detection shall not have more than a 10-second delay
before the door starts to close after the smoke detector
is actuated:
I. Doors installed across
a corridor.
2.Doors
that protect openings in exits or corridors required
to be of fire-resistance-rated construction.
3.Doors
that protect openings in walls that are capable of resisting
the passage of smoke in accordance with Section
508.2.2.1.
4.Doors
installed in smoke barriers in accordance with Section
709.5.
5.Doors
installed in fire partitions in accordance with Section
708.6.
6.Doors
installed in a fire wall in accordance with Section
705.8.
7.Doors
installed in shaft enclosures in accordance with Section
707.7.
8.Doors
installed in refuse and laundry chutes and access and
termination rooms in accordance with Section
707.13.
9.Doors
installed in the walls for compartmentation of underground
buildings in accordance with Section
405.4.2.
10.Doors
installed in the elevator lobby walls of underground
buildings in accordance with Section
405.4.3.
11.Doors
installed in smoke partitions in accordance
with Section
710.5.3.
715.4.7.4 Doors
in pedestrian ways. Vertical sliding or vertical rolling
steel fire doors in openings through which pedestrians travel
shall be heat activated or activated by smoke detectors
with alarm verification.
715.4.8 Swinging
fire shutters. Where fire shutters of the swinging type
are installed in exterior openings, not less than one row
in every three vertical rows shall be arranged to be readily
opened from the outside, and shall be identified by distinguishing
marks or letters not less than 6 inches (152 mm) high.
715.4.9 Rolling
fire shutters. Where fire shutters of the rolling type
are installed, such shutters shall include approved automatic-closing
devices.
715.5 Fire- protection-rated
glazing. Glazing in fire window assemblies shall be fire-protection
rated in accordance with this section and Table
715.5. Glazing in fire door assemblies shall comply with
Section 715.4.6. Fire-protection-rated glazing shall be tested
in accordance with and shall meet the acceptance criteria
of NFPA 257. Fire-protection-rated glazing shall also comply
with NFPA 80. Openings in non fire-resistance-rated exterior
wall assemblies that require protection in accordance with
Section 704.3, 704.8,
704.9 or 704.10
shall have a fire-protection rating of not less than 3/4
hour.
Exceptions:
1.Wired
glass in accordance with Section 715.5.3.
2.Fire-protection-rated
glazing in 0.5-hour fire-resistance-rated
partitions is permitted to have an 0.33-hour fire-protection
rating.
715.5.1 Testing under positive
pressure. NFPA 257 shall evaluate fire-protection-rated
glazing under positive pressure. Within the first 10 minutes
of a test, the pressure in the furnace shall be adjusted
so at least two-thirds of the test specimen
is above the neutral pressure plane, and the neutral pressure
plane shall be maintained at that height for the balance
of the test.
715.5.2 Nonsymmetrical
glazing systems. Nonsymmetrical fire-protection-rated
glazing systems in fire partitions, fire barriers or in
exterior walls with a fire separation distance of 5 feet
(1524 mm) or less pursuant to Section
704 shall be tested with both faces exposed to the furnace,
and the assigned fire protection rating shall be the shortest
duration obtained from the two tests conducted in compliance
with NFPA257.
715.5.3 Wired glass.
Steel window frame assemblies of 0.125-inch (3.2 mm) minimum
solid section or of not less than nominal 0.048-inch-thick
(1.2 mm) formed sheet steel members fabricated by pressing,
mitering, riveting, interlocking or welding and having
provision for glazing with 1/4-inch
(6.4 mm) wired glass where securely installed in the building
construction and glazed with 1/4-inch
(6.4 mm) labeled wired glass shall be deemed to meet the
requirements for a %-hour fire window assembly. Wired glass
panels shall conform to the size limitations set forth in
Table 715.5.3.
715.5.4 Non wired glass.
Glazing other than wired glass in fire window assemblies
shall be fire-protection-rated glazing installed in accordance
with and complying with the size limitations set forth in
NFPA 80.
715.5.5 Installation. Fire-protection-rated
glazing shall be in the fixed position or be automatic-closing
and shall be installed in approved frames.
715.5.6 Window mullions.
Metal mullions that exceed a nominal height of 12 feet (3658
mm) shall be protected with materials to afford the same
fire-resistance rating as required for the wall construction
in which the protective is located.
715.5.7 Interior fire window
assemblies. Fire-protection-rated glazing used in fire
window assemblies located in fire partitions and fire barriers
shall be limited to use in assemblies with a maximum fire-resistance
rating of 1 hour in accordance with this section.
715.5.7.1 Where permitted.
Fire-protection-rated glazing shall be limited to fire
partitions designed in accordance with Section
708 and fire barriers utilized in the applications
set forth in Sections 706.3.6
and 706.3.8 where the fire-resistance
rating does not exceed 1 hour.
715.5.7.2 Size limitations.
The total area of windows shall not exceed 25 percent
of the area of a common wall with any room.
715.5.8 Labeling requirements.
Fire-protection-rated glazing shall bear a label or other
identification showing the name of the manufacturer, the test
standard and information required in Section 715.5.8.1 that
shall be issued by an approved agency and shall be permanently
affixed to the glazing.
715.5.8.1 Identification.
For fire-protection-rated glazing, the label shall bear
the following two-part identification: "OH - XXX."
"OH" indicates that the glazing meets both the
fire-resistance and the hose-stream requirements of NFPA
257 and is permitted to be used in openings. "XXX"
represents the fire-protection rating period, in minutes,
that was tested.
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|