1. The minimum and maximum
width shall not apply to door openings that are not part
of the required means of egress in Group R-2 and R-3 occupancies.
2. Door openings to resident
sleeping units in Group I-3 occupancies shall have a clear
width of not less than 28 inches (711 mm).
3. Door openings to storage
closets less than 10 square feet (0.93m2) in
area shall not be limited by the minimum width.
4. Width of door leafs in revolving
doors that comply with Section
1008.1.3.1 shall not be limited.
5. Door openings within a dwelling
unit or sleeping unit shall not be less than 78 inches (1981
mm) in height.
6. Exterior door openings in
dwelling units and sleeping units, other than the required
exit door, shall not be less than 76 inches (1930 mm) in
height.
7. In other than Group R-1
occupancies, the minimum widths shall not apply to interior
egress doors within a dwelling unit or sleeping unit that
is not required to be an Accessible unit, Type A unit or
Type B unit.
8. Door openings required to
be accessible within Type B units shall have a minimum clear
width of 31.75 inches (806 mm).