|
|
|
|
|
|
|
| SECTION 2105 QUALITY ASSURANCE
2105.1 General. A quality
assurance program shall be used to ensure that the constructed
masonry is in compliance with the construction documents.
The quality assurance program shall comply with the inspection
and testing requirements of Chapter 17.
2105.2 Acceptance relative
to strength requirements.
2105.2.1 Compliance with
f m and f AAC. Compressive strength
of masonry shall be considered satisfactory if the compressive
strength of each masonry wythe and grouted collar joint
equals or exceeds the value of f m for clay
and concrete masonry and f AAC for AAC masonry.
For partially grouted clay and concrete masonry, the compressive
strength of both the grouted and ungrouted masonry shall
equal or exceed the applicable f m . At the time
of prestress, the compressive strength of the masonry shall
equal or exceed f mi, which shall be less than
or equal to f m.
2105.2.2 Determination of
compressive strength. The compressive strength for each
wythe shall be determined by the unit strength method or
by the prism test method as specified herein.
2105.2.2.1 Unit strength
method.
2105.2.2.1.1 Clay masonry.
The compressive strength of masonry shall be determined
based on the strength of the units and the type of mortar
specified using Table
2105.2.2.1.1, provided:
1. Units conform to ASTM
C 62, ASTM C 216 or ASTM C 652 and are sampled and
tested in accordance with ASTM C 67.
2. Thickness of bed joints
does not exceed 5/8 inch (15.9
mm).
3. For grouted masonry,
the grout meets one of the following requirements:
3.1. Grout conforms
to ASTM C 476.
3.2. Minimum grout
compressive strength equals or exceeds f m
but not less than 2,000 psi (13.79MPa). The compressive
strength of grout shall be determined in accordance
with ASTM C 1019.
2105.2.2.1.2 Concrete
masonry. The compressive strength of masonry shall
be determined based on the strength of the unit and
type of mortar specified using Table
2105.2.2.1.2, provided:
1. Units conform to ASTM
C 55 or ASTM C 90 and are sampled and tested in accordance
with ASTM C 140.
2. Thickness of bed joints
does not exceed 5/8 inch (15.9
mm).
3. For grouted masonry,
the grout meets one of the following requirements:
3.1. Grout conforms
to ASTM C 476.
3.2. Minimum grout
compressive strength equals or exceeds f m but not
less than 2,000 psi (13.79 MPa). The compressive
strength of grout shall be determined in accordance
with ASTM C 1019.
2105.2.2.1.3 AAC masonry. The compressive strength
of AAC masonry shall be based on the strength of the
AAC masonry unit only and the following shall be met:
1. Units conform to ASTM
C 1386.
2. Thickness of bed joints
does not exceed 1/8 inch (3.2
mm).
3. For grouted masonry,
the grout meets one of the following requirements:
3.1. Grout conforms
to ASTM C 476.
3.2. Minimum grout
compressive strength equals or exceeds f AAC
but not less than 2,000 psi (13.79 MPa). The compressive
strength of grout shall be determined in accordance
with ASTM C 1019.
2105.2.2.2 Prism test
method.
2105.2.2.2.1 General.
The compressive strength of clay and concrete masonry
shall be determined by the prism test method:
1. Where specified in
the construction documents.
2. Where masonry does
not meet the requirements for application of the unit
strength method in Section 2105.2.2.1.
2105.2.2.2.2 Number
of prisms per test. A prism test shall consist of
three prisms constructed and tested in accordance with
ASTM C 1314.
2105.3 Testing prisms from
constructed masonry. When approved by the building official,
acceptance of masonry that does not meet the requirements
of Section 2105.2.2.1 or 2105.2.2.2 shall be permitted to
be based on tests of prisms cut from the masonry construction
in accordance with Sections 2105.3.1, 2105.3.2 and 2105.3.3.
2105.3.1 Prism sampling
and removal. A set of three masonry prisms that are
at least 28 days old shall be saw cut from the masonry for
each 5,000 square feet (465 m2) of the wall area
that is in question but not less than one set of three masonry
prisms for the project. The length, width and height dimensions
of the prisms shall comply with the requirements of ASTM
C 1314. Transporting, preparation and testing of prisms
shall be in accordance with ASTM C 1314.
2105.3.2 Compressive strength
calculations. The compressive strength of prisms shall
be the value calculated in accordance ASTM C 1314, except
that the net cross- sectional area of the prism shall be
based on the net mortar bedded area.
2105.3.3 Compliance.
Compliance with the requirement for the specified compressive
strength of masonry, f m, shall be considered satisfied
provided the modified compressive strength equals or exceeds
the specified f m. Additional testing of specimens cut from
locations in question shall be permitted.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|