| SECTION 2111 MASONRY FIREPLACES
2111.1 Definition. A masonry
fireplace is a fireplace constructed of concrete or masonry.
Masonry fireplaces shall be constructed in accordance with
this section.
2111.2 Footings and foundations.
Footings for masonry fireplaces and their chimneys shall be
constructed of concrete or solid masonry at least 12 inches
(305 mm) thick and shall extend at least 6 inches (153 mm)
beyond the face of the fireplace or foundation wall on all
sides. Footings shall be founded on natural undisturbed earth
or engineered fill below frost depth. In areas not subjected
to freezing, footings shall be at least 12 inches (305 mm)
below finished grade.
2111.2.1 Ash dump cleanout.
Cleanout openings, located within foundation walls below
fireboxes, when provided, shall be equipped with ferrous
metal or masonry doors and frames constructed to remain
tightly closed, except when in use. Cleanouts shall be accessible
and located so that ash removal will not create a hazard
to combustible materials.
2111.3 Seismic reinforcing.
Masonry or concrete fireplaces shall be constructed, anchored,
supported and reinforced as required in this chapter. In Seismic
Design Category D, masonry and concrete fireplaces shall be
reinforced and anchored as detailed in Sections 2111.3.1,
2111.3.2, 2111.4 and 2111.4.1 for chimneys serving fireplaces.
In Seismic Design Category A, B or C, reinforcement and seismic
anchorage is not required. In Seismic Design Category E or
F, masonry and concrete chimneys shall be reinforced in accordance
with the requirements of Sections 2101
through 2108.
2111.3.1 Vertical reinforcing.
For fireplaces with chimneys up to 40 inches (1016 mm) wide,
four No. 4 continuous vertical bars, anchored in the foundation,
shall be placed in the concrete between wythes of solid
masonry or within the cells of hollow unit masonry and grouted
in accordance with Section 2103.12.
For fireplaces with chimneys greater than 40 inches (1016
mm) wide, two additional No. 4 vertical bars shall be provided
for each additional 40 inches (1016 mm) in width or fraction
thereof.
2111.3.2 Horizontal reinforcing.
Vertical reinforcement shall be placed enclosed within 1/4-inch
(6.4 mm) ties or other reinforcing of equivalent net cross-sectional
area, spaced not to exceed 18 inches (457 mm) on center
in concrete; or placed in the bed joints of unit masonry
at a minimum of every 18 inches (457 mm) of vertical height.
Two such ties shall be provided at each bend in the vertical
bars.
2111.4 Seismic anchorage.
Masonry and concrete chimneys in Seismic Design Category
D shall be anchored at each floor, ceiling or roof line more
than 6 feet (1829 mm) above grade, except where constructed
completely within the exterior walls. Anchorage shall conform
to the following requirements.
2111.4.1 Anchorage. Two
3/16-inch by 1-inch (4.8 mm by 25.4
mm) straps shall be embedded a minimum of 12 inches (305
mm) into the chimney. Straps shall be hooked around the
outer bars and extend 6 inches (152 mm) beyond the bend.
Each strap shall be fastened to a minimum of four floor
joists with two 1/2-inch (12.7 mm)
bolts.
2111.5 Firebox walls.
Masonry fireboxes shall be constructed of solid masonry units,
hollow masonry units grouted solid, stone or concrete. When
a lining of firebrick at least 2 inches (51 mm) in thickness
or other approved lining is provided, the minimum thickness
of back and sidewalls shall each be 8 inches (203 mm) of solid
masonry, including the lining. The width of joints between
firebricks shall not be greater than 1/4
inch (6.4 mm). When no lining is provided, the total minimum
thickness of back and sidewalls shall be 10 inches (254 mm)
of solid masonry. Firebrick shall conform to ASTM C 27 or
ASTM C 1261 and shall be laid with medium-duty refractory
mortar conforming to ASTM C 199.
2111.5.1 Steel fireplace
units. Steel fireplace units are permitted to be installed
with solid masonry to form a masonry fireplace provided
they are installed according to either the requirements
of their listing or the requirements of this section. Steel
fireplace units incorporating a steel firebox lining shall
be constructed with steel not less than 1/4
inch (6.4 mm) in thickness, and an air-circulating chamber
which is ducted to the interior of the building. The firebox
lining shall be encased with solid masonry to provide a
total thickness at the back and sides of not less than 8
inches (203 mm), of which not less than 4 inches (102 mm)
shall be of solid masonry or concrete. Circulating air ducts
employed with steel fireplace units shall be constructed
of metal or masonry.
2111.6 Firebox dimensions.
The firebox of a concrete or masonry fireplace shall have
a minimum depth of 20 inches (508 mm). The throat shall not
be less than 8 inches (203 mm) above the fireplace opening.
The throat opening shall not be less than 4 inches (102 mm)
in depth. The cross-sectional area of the passageway above
the firebox, including the throat, damper and smoke chamber,
shall not be less than the cross-sectional area of the flue.
Exception: Rumford fireplaces
shall be permitted provided that the depth of the fireplace
is at least 12 inches (305 mm) and at least one-third of the
width of the fireplace opening, and the throat is at least
12 inches (305 mm) above the lintel, and at least 1/20
the cross-sectional area of the fireplace opening.
2111.7 Lintel and throat.
Masonry over a fireplace opening shall be supported by a lintel
of noncombustible material. The minimum required bearing length
on each end of the fireplace opening shall be 4 inches (102
mm). The fireplace throat or damper shall be located a minimum
of 8 inches (203 mm) above the top of the fireplace opening.
2111.7.1 Damper. Masonry
fireplaces shall be equipped with a ferrous metal damper
located at least 8 inches (203 mm) above the top of the
fireplace opening. Dampers shall be installed in the fireplace
or at the top of the flue venting the fireplace, and shall
be operable from the room containing the fireplace. Damper
controls shall be permitted to be located in the fireplace.
2111.8 Smoke chamber walls.
Smoke chamber walls shall be constructed of solid masonry
units, hollow masonry units grouted solid, stone or concrete.
Corbeling of masonry units shall not leave unit cores exposed
to the inside of the smoke chamber. The inside surface of
corbeled masonry shall be parged smooth. Where no lining is
provided, the total minimum thickness of front, back and sidewalls
shall be 8 inches (203 mm) of solid masonry. When a lining
of firebrick at least 2 inches (51 mm) thick, or a lining
of vitrified clay at least 5/8 inch
(15.9 mm) thick, is provided, the total minimum thickness
of front, back and sidewalls shall be 6 inches (152 mm) of
solid masonry, including the lining. Firebrick shall conform
to ASTM C 27 or ASTM C 1261 and shall be laid with refractory
mortar conforming to ASTM C 199.
2111.8.1 Smoke chamber dimensions.
The inside height of the smoke chamber from the fireplace
throat to the beginning of the flue shall not be greater
than the inside width of the fireplace opening. The inside
surface of the smoke chamber shall not be inclined more
than 45 degrees (0.76 rad) from vertical when prefabricated
smoke chamber linings are used or when the smoke chamber
walls are rolled or sloped rather than corbeled. When the
inside surface of the smoke chamber is formed by corbeled
masonry, the walls shall not be corbeled more than 30 degrees
(0.52 rad) from vertical.
2111.9 Hearth and hearth extension.
Masonry fireplace hearths and hearth extensions shall be constructed
of concrete or masonry, supported by noncombustible materials,
and reinforced to carry their own weight and all imposed loads.
No combustible material shall remain against the underside
of hearths or hearth extensions after construction.
2111.9.1 Hearth thickness.
The minimum thickness of fireplace hearths shall be 4 inches
(102 mm).
2111.9.2 Hearth extension
thickness. The minimum thickness of hearth extensions
shall be 2 inches (51 mm).
Exception: When the bottom
of the firebox opening is raised at least 8 inches (203 mm)
above the top of the hearth extension, a hearth extension
of not less than 3/8- inch-thick (9.5
mm) brick, concrete, stone, tile or other approved noncombustible
material is permitted.
2111.10 Hearth extension dimensions.
Hearth extensions shall extend at least 16 inches (406 mm)
in front of, and at least 8 inches (203 mm) beyond, each side
of the fireplace opening. Where the fireplace opening is 6
square feet (0.557 m2) or larger, the hearth extension
shall extend at least 20 inches (508 mm) in front of, and
at least 12 inches (305 mm) beyond, each side of the fireplace
opening.
2111.11 Fireplace clearance.
Any portion of a masonry fireplace located in the interior
of a building or within the exterior wall of a building shall
have a clearance to combustibles of not less than 2 inches
(51 mm) from the front faces and sides of masonry fireplaces
and not less than 4 inches (102 mm) from the back faces of
masonry fireplaces. The airspace shall not be filled, except
to provide fireblocking in accordance with Section 2111.12.
Exceptions:
1. Masonry fireplaces listed
and labeled for use in contact with combustibles in accordance
with UL 127 and installed in accordance with the manufacturers
installation instructions are permitted to have combustible
material in contact with their exterior surfaces.
2. When masonry fireplaces
are constructed as part of masonry or concrete walls, combustible
materials shall not be in contact with the masonry or concrete
walls less than 12 inches (306 mm) from the inside surface
of the nearest firebox lining.
3. Exposed combustible trim
and the edges of sheathing materials, such as wood siding,
flooring and drywall, are permitted to abut the masonry
fireplace sidewalls and hearth extension, in accordance
with Figure 2111.11, provided
such combustible trim or sheathing is a minimum of 12 inches
(306 mm) from the inside surface of the nearest firebox
lining.
4. Exposed combustible mantels
or trim is permitted to be placed directly on the masonry
fireplace front surrounding the fireplace opening, provided
such combustible materials shall not be placed within 6
inches (153 mm) of a fireplace opening. Combustible material
directly above and within 12 inches (305 mm) of the fireplace
opening shall not project more than 1/8
inch (3.2 mm) for each 1-inch (25 mm) distance from such
opening. Combustible materials located along the sides of
the fireplace opening that project more than 11/2
inches (38 mm) from the face of the fireplace shall have
an additional clearance equal to the projection.
2111.12 Fireplace fireblocking.
All spaces between fireplaces and floors and ceilings through
which fireplaces pass shall be fireblocked with noncombustible
material securely fastened in place. The fireblocking of spaces
between wood joists, beams or headers shall be to a depth
of 1 inch (25 mm) and shall only be placed on strips of metal
or metal lath laid across the spaces between combustible material
and the chimney.
2111.13 Exterior air.
Factory-built or masonry fireplaces covered in this section
shall be equipped with an exterior air supply to ensure proper
fuel combustion unless the room is mechanically ventilated
and controlled so that the indoor pressure is neutral or positive.
2111.13.1 Factory-built
fireplaces. Exterior combustion air ducts for factory-built
fireplaces shall be listed components of the fireplace,
and installed according to the fireplace manufacturers
instructions.
2111.13.2 Masonry fireplaces.
Listed combustion air ducts for masonry fireplaces shall
be installed according to the terms of their listing and
manufacturers instructions.
2111.13.3 Exterior air intake.
The exterior air intake shall be capable of providing
all combustion air from the exterior of the dwelling. The
exterior air intake shall not be located within the garage,
attic, basement or crawl space of the dwelling nor shall
the air intake be located at an elevation higher than the
firebox. The exterior air intake shall be covered with a
corrosion-resistant screen of 1/4-inch
(6.4 mm) mesh.
2111.13.4 Clearance.
Unlisted combustion air ducts shall be installed with a
minimum 1-inch (25 mm) clearance to combustibles for all
parts of the duct within 5 feet (1524 mm) of the duct outlet.
2111.13.5 Passageway.
The combustion air passageway shall be a minimum of 6 square
inches (3870 mm2) and not more than 55 square
inches (0.035 m2), except that combustion air
systems for listed fireplaces or for fireplaces tested for
emissions shall be constructed according to the fireplace
manufacturers instructions.
2111.13.6 Outlet. The
exterior air outlet is permitted to be located in the back
or sides of the firebox chamber or within 24 inches (610
mm) of the firebox opening on or near the floor. The outlet
shall be closable and designed to prevent burning material
from dropping into concealed combustible spaces.
|