| SECTION 2113 MASONRY CHIMNEYS
2113.3 Seismic reinforcing.
Masonry or concrete chimneys shall be constructed, anchored,
supported and reinforced as required in this chapter. In Seismic
Design Category D, masonry and concrete chimneys shall be
reinforced and anchored as detailed in Sections 2113.3.1,
2113.3.2 and 2113.4. In Seismic Design
Category A, B or C, reinforcement and seismic anchorage is
not required. In Seismic Design Category E or F, masonry and
concrete chimneys shall be reinforced in accordance with the
requirements of Sections 2101 through
2108.
2113.3.1 Vertical reinforcing.
For chimneys up to 40 inches (1016 mm) wide, four No. 4
continuous vertical bars anchored in the foundation shall
be placed in the concrete between wythes of solid masonry
or within the cells of hollow unit masonry and grouted in
accordance with Section 2103.12.
Grout shall be prevented from bonding with the flue liner
so that the flue liner is free to move with thermal expansion.
For chimneys greater than 40 inches (1016 mm) wide, two
additional No. 4 vertical bars shall be provided for each
additional 40 inches (1016 mm) in width or fraction thereof.
2113.3.2 Horizontal reinforcing.
Vertical reinforcement shall be placed enclosed within 1/4-inch
(6.4 mm) ties, or other reinforcing of equivalent net cross-sectional
area, spaced not to exceed 18 inches (457 mm) o.c. in concrete,
or placed in the bed joints of unit masonry, at a minimum
of every 18 inches (457 mm) of vertical height. Two such
ties shall be provided at each bend in the vertical bars.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|