| SECTION 2113 MASONRY CHIMNEYS
2113.1 Definition. A
masonry chimney is a chimney constructed of concrete or masonry,
hereinafter referred to as masonry. Masonry chimneys
shall be constructed, anchored, supported and reinforced as
required in this chapter.
2113.2 Footings and foundations.
Footings for masonry chimneys shall be constructed of
concrete or solid masonry at least 12 inches (305 mm) thick
and shall extend at least 6 inches (152 mm) beyond the face
of the foundation or support wall on all sides. Footings shall
be founded on natural undisturbed earth or engineered fill
below frost depth. In areas not subjected to freezing, footings
shall be at least 12 inches (305 mm) below finished grade.
2113.3 Seismic reinforcing.
Masonry or concrete chimneys shall be constructed, anchored,
supported and reinforced as required in this chapter. In Seismic
Design Category D, masonry and concrete chimneys shall be
reinforced and anchored as detailed in Sections 2113.3.1,
2113.3.2 and 2113.4. In Seismic Design Category A, B or C,
reinforcement and seismic anchorage is not required. In Seismic
Design Category E or F, masonry and concrete chimneys shall
be reinforced in accordance with the requirements of
Sections 2101 through 2108.
2113.3.1 Vertical reinforcing.
For chimneys up to 40 inches (1016 mm) wide, four No. 4
continuous vertical bars anchored in the foundation shall
be placed in the concrete between wythes of solid masonry
or within the cells of hollow unit masonry and grouted in
accordance with Section 2103.12.
Grout shall be prevented from bonding with the flue liner
so that the flue liner is free to move with thermal expansion.
For chimneys greater than 40 inches (1016 mm) wide, two
additional No. 4 vertical bars shall be provided for each
additional 40 inches (1016 mm) in width or fraction thereof.
2113.3.2 Horizontal reinforcing.
Vertical reinforcement shall be placed enclosed within 1/4-inch
(6.4 mm) ties, or other reinforcing of equivalent net cross-sectional
area, spaced not to exceed 18 inches (457 mm) o.c. in concrete,
or placed in the bed joints of unit masonry, at a minimum
of every 18 inches (457 mm) of vertical height. Two such
ties shall be provided at each bend in the vertical bars.
2113.4 Seismic anchorage.
Masonry and concrete chimneys and foundations in Seismic Design
Category D shall be anchored at each floor, ceiling or roof
line more than 6 feet (1829 mm) above grade, except where
constructed completely within the exterior walls. Anchorage
shall conform to the following requirements.
2113.4.1 Anchorage.
Two 3/16-inch by 1-inch (4.8 mm by
25 mm) straps shall be embedded a minimum of 12 inches (305
mm) into the chimney. Straps shall be hooked around the
outer bars and extend 6 inches (152 mm) beyond the bend.
Each strap shall be fastened to a minimum of four floor
joists with two 1/2-inch (12.7 mm)
bolts.
2113.5 Corbeling. Masonry
chimneys shall not be corbeled more than half of the chimneys
wall thickness from a wall or foundation, nor shall a chimney
be corbeled from a wall or foundation that is less than 12
inches (305 mm) in thickness unless it projects equally on
each side of the wall, except that on the second story of
a two-story dwelling, corbeling of chimneys on the exterior
of the enclosing walls is permitted to equal the wall thickness.
The projection of a single course shall not exceed one-half
the unit height or one-third of the unit bed depth, whichever
is less.
2113.6 Changes in dimension.
The chimney wall or chimney flue lining shall not change in
size or shape within 6 inches (152 mm) above or below where
the chimney passes through floor components, ceiling components
or roof components.
2113.7 Offsets. Where
a masonry chimney is constructed with a fireclay flue liner
surrounded by one wythe of masonry, the maximum offset shall
be such that the centerline of the flue above the offset does
not extend beyond the center of the chimney wall below the
offset. Where the chimney offset is supported by masonry below
the offset in an approved manner, the maximum offset limitations
shall not apply. Each individual corbeled masonry course of
the offset shall not exceed the projection limitations specified
in Section 2113.5.
2113.8 Additional load. Chimneys
shall not support loads other than their own weight unless
they are designed and constructed to support the additional
load. Masonry chimneys are permitted to be constructed as
part of the masonry walls or concrete walls of the building.
2113.9 Termination. Chimneys
shall extend at least 2 feet (610 mm) higher than any portion
of the building within 10 feet (3048 mm), but shall not be
less than 3 feet (914 mm) above the highest point where the
chimney passes through the roof.
2113.9.1 Spark arrestors.
Where a spark arrestor is installed on a masonry chimney,
the spark arrestor shall meet all of the following requirements:
1. The net free area of the
arrestor shall not be less than four times the net free
area of the outlet of the chimney flue it serves.
2. The arrestor screen shall
have heat and corrosion resistance equivalent to 19-gage
galvanized steel or 24-gage stainless steel.
3. Openings shall not permit
the passage of spheres having a diameter greater than
1/2 inch (13 mm) nor block the passage
of spheres having a diameter less than 3/8
inch (11 mm).
4. The spark arrestor shall
be accessible for cleaning and the screen or chimney cap
shall be removable to allow for cleaning of the chimney
flue.
2113.10 Wall thickness.
Masonry chimney walls shall be constructed of concrete, solid
masonry units or hollow masonry units grouted solid with not
less than 4 inches (102 mm) nominal thickness.
2113.10.1 Masonry veneer
chimneys. Where masonry is used as veneer for a framed
chimney, through flashing and weep holes shall be provided
as required by Chapter 14.
2113.11 Flue lining (material).
Masonry chimneys shall be lined. The lining material shall
be appropriate for the type of appliance connected, according
to the terms of the appliance listing and the manufacturers
instructions.
2113.11.1 Residential-type
appliances (general). Flue lining systems shall comply
with one of the following:
1. Clay flue lining complying
with the requirements of ASTM C 315, or equivalent.
2. Listed chimney lining
systems complying with UL 1777.
3. Factory-built chimneys
or chimney units listed for installation within masonry
chimneys.
4. Other approved materials
that will resist corrosion, erosion, softening or cracking
from flue gases and condensate at temperatures up to
1,800°F (982°C).
2113.11.1.1 Flue linings
for specific appliances. Flue linings other than those
covered in Section 2113.11.1 intended for use with specific
appliances shall comply with Sections 2113.11.1.2 through
2113.11.1.4 and Sections 2113.11.2 and 2113.11.3.
2113.11.1.2 Gas appliances.
Flue lining systems for gas appliances shall be in accordance
with the International Fuel Gas Code.
2113.11.1.3 Pellet fuel-burning
appliances. Flue lining and vent systems for use in
masonry chimneys with pellet fuel-burning appliances shall
be limited to flue lining systems complying with Section
2113.11.1 and pellet vents listed for installation within
masonry chimneys (see Section 2113.11.1.5 for marking).
2113.11.1.4 Oil-fired
appliances approved for use with L-vent. Flue lining
and vent systems for use in masonry chimneys with oil-fired
appliances approved for use with Type L vent shall be
limited to flue lining systems complying with Section
2113.11.1 and listed chimney liners complying with UL
641 (see Section 2113.11.1.5 for marking).
2113.11.1.5 Notice of
usage. When a flue is relined with a material not
complying with Section 2113.11.1, the chimney shall be
plainly and permanently identified by a label attached
to a wall, ceiling or other conspicuous location adjacent
to where the connector enters the chimney. The label shall
include the following message or equivalent language:
This chimney is for use only with (type or category
of appliance) that burns (type of fuel). Do not connect
other types of appliances.
2113.11.2 Concrete and masonry
chimneys for medium-heat appliances.
2113.11.2.1 General.
Concrete and masonry chimneys for medium-heat appliances
shall comply with Sections 2113.1 through 2113.5.
2113.11.2.2 Construction.
Chimneys for medium-heat appliances shall be constructed
of solid masonry units or of concrete with walls a minimum
of 8 inches (203 mm) thick, or with stone masonry a minimum
of 12 inches (305 mm) thick.
2113.11.2.3 Lining.
Concrete and masonry chimneys shall be lined with an approved
medium-duty refractory brick a minimum of 41/2
inches (114 mm) thick laid on the 41/2-inch
bed (114 mm) in an approved medium-duty refractory mortar.
The lining shall start 2 feet (610 mm) or more below the
lowest chimney connector entrance. Chimneys terminating
25 feet (7620 mm) or less above a chimney connector entrance
shall be lined to the top.
2113.11.2.4 Multiple passageway.
Concrete and masonry chimneys containing more than one
passageway shall have the liners separated by a minimum
4-inch-thick (102 mm) concrete or solid masonry wall.
2113.11.2.5 Termination
height. Concrete and masonry chimneys for medium-heat
appliances shall extend a minimum of 10 feet (3048 mm)
higher than any portion of any building within 25 feet
(7620 mm).
2113.11.2.6 Clearance.
A minimum clearance of 4 inches (102 mm) shall be provided
between the exterior surfaces of a concrete or masonry
chimney for medium-heat appliances and combustible material.
2113.11.3 Concrete and masonry
chimneys for high-heat appliances.
2113.11.3.1 General. Concrete
and masonry chimneys for high-heat appliances shall comply
with Sections 2113.1 through 2113.5.
2113.11.3.2 Construction.
Chimneys for high-heat appliances shall be constructed
with double walls of solid masonry units or of concrete,
each wall to be a minimum of 8 inches (203 mm) thick with
a minimum airspace of 2 inches (51 mm) between the walls.
2113.11.3.3 Lining. The
inside of the interior wall shall be lined with an approved
high-duty refractory brick, a minimum of 41/2
inches (114 mm) thick laid on the 41/2-inch
bed (114 mm) in an approved high-duty refractory mortar.
The lining shall start at the base of the chimney and
extend continuously to the top.
2113.11.3.4 Termination
height. Concrete and masonry chimneys for high-heat
appliances shall extend a minimum of 20 feet (6096 mm)
higher than any portion of any building within 50 feet
(15 240 mm).
2113.11.3.5 Clearance.
Concrete and masonry chimneys for high-heat appliances
shall have approved clearance from buildings and structures
to prevent overheating combustible materials, permit inspection
and maintenance operations on the chimney and prevent
danger of burns to persons.
2113.12 Clay flue lining (installation).
Clay flue liners shall be installed in accordance with
ASTMC 1283 and extend from a point not less than 8 inches
(203 mm) below the lowest inlet or, in the case of fireplaces,
from the top of the smoke chamber to a point above the enclosing
walls. The lining shall be carried up vertically, with a maximum
slope no greater than 30 degrees (0.52 rad) from the vertical.
Clay flue liners shall be laid in medium-duty refractory mortar
conforming to ASTM C 199 with tight mortar joints left smooth
on the inside and installed to maintain an air space or insulation
not to exceed the thickness of the flue liner separating the
flue liners from the interior face of the chimney masonry
walls. Flue lining shall be supported on all sides. Only enough
mortar shall be placed to make the joint and hold the liners
in position.
2113.13 Additional requirements.
2113.13.1 Listed materials.
Listed materials used as flue linings shall be installed
in accordance with the terms of their listings and the manufacturers
instructions.
2113.13.2 Space around lining.
The space surrounding a chimney lining system or vent installed
within a masonry chimney shall not be used to vent any other
appliance.
Exception: This shall
not prevent the installation of a separate flue lining in
accordance with the manufacturers instructions.
2113.14 Multiple flues.
When two or more flues are located in the same chimney, masonry
wythes shall be built between adjacent flue linings. The masonry
wythes shall be at least 4 inches (102 mm) thick and bonded
into the walls of the chimney.
Exception: When venting
only one appliance, two flues are permitted to adjoin each
other in the same chimney with only the flue lining separation
between them. The joints of the adjacent flue linings shall
be staggered at least 4 inches (102 mm).
2113.15 Flue area (appliance).
Chimney flues shall not be smaller in area than the area
of the connector from the appliance. Chimney flues connected
to more than one appliance shall not be less than the area
of the largest connector plus 50 percent of the areas of additional
chimney connectors.
Exceptions:
1. Chimney
flues serving oil-fired appliances sized in accordance with
NFPA 31.
2. Chimney
flues serving gas-fired appliances sized in accordance with
the International Fuel Gas Code.
2113.16 Flue area (masonry
fireplace). Flue sizing for chimneys serving fireplaces
shall be in accordance with Section 2113.16.1 or 2113.16.2.
2113.16.1 Minimum area.
Round chimney flues shall have a minimum net cross-sectional
area of at least 1/12 of the fireplace
opening. Square chimney flues shall have a minimum net cross-sectional
area of at least 1/10 of the fireplace
opening. Rectangular chimney flues with an aspect ratio
less than 2 to 1 shall have a minimum net cross-sectional
area of at least 1/10 of the fireplace
opening. Rectangular chimney flues with an aspect ratio
of 2 to 1 or more shall have a minimum net cross-sectional
area of at least 1/8 of the fireplace
opening.
2113.16.2 Determination of
minimum area. The minimum net cross-sectional area of the
flue shall be determined in accordance with Figure
2113.16. A flue size providing at least the equivalent
net cross-sectional area shall be used. Cross-sectional
areas of clay flue linings are as provided in Tables
2113.16(1) and 2113.16(2)
or as provided by the manufacturer or as measured in the
field. The height of the chimney shall be measured from
the firebox floor to the top of the chimney flue.
2113.17 Inlet. Inlets
to masonry chimneys shall enter from the side. Inlets shall
have a thimble of fireclay, rigid refractory material or metal
that will prevent the connector from pulling out of the inlet
or from extending beyond the wall of the liner.
2113.18 Masonry chimney cleanout
openings. Cleanout openings shall be provided within 6
inches (152 mm) of the base of each flue within every masonry
chimney. The upper edge of the cleanout shall be located at
least 6 inches (152 mm) below the lowest chimney inlet opening.
The height of the opening shall be at least 6 inches (152
mm). The cleanout shall be provided with a noncombustible
cover.
Exception: Chimney flues
serving masonry fireplaces, where cleaning is possible through
the fireplace opening.
2113.19 Chimney clearances.
Any portion of a masonry chimney located in the interior
of the building or within the exterior wall of the building
shall have a minimum airspace clearance to combustibles of
2 inches (51 mm). Chimneys located entirely outside the exterior
walls of the building, including chimneys that pass through
the soffit or cornice, shall have a minimum airspace clearance
of 1 inch (25 mm). The airspace shall not be filled, except
to provide fireblocking in accordance with Section 2113.20.
Exceptions:
1. Masonry chimneys equipped
with a chimney lining system listed and labeled for use
in chimneys in contact with combustibles in accordance with
UL 1777, and installed in accordance with the manufacturers
instructions, are permitted to have combustible material
in contact with their exterior surfaces.
2. Where masonry chimneys are
constructed as part of masonry or concrete walls, combustible
materials shall not be in contact with the masonry or concrete
wall less than 12 inches (305 mm) from the inside surface
of the nearest flue lining.
3. Exposed combustible trim
and the edges of sheathing materials, such as wood siding,
are permitted to abut the masonry chimney sidewalls, in
accordance with Figure 2113.19,
provided such combustible trim or sheathing is a minimum
of 12 inches (305 mm) from the inside surface of the nearest
flue lining. Combustible material and trim shall not overlap
the corners of the chimney by more than 1 inch (25 mm).
2113.20 Chimney fireblocking.
All spaces between chimneys and floors and ceilings through
which chimneys pass shall be fireblocked with noncombustible
material securely fastened in place. The fireblocking of spaces
between wood joists, beams or headers shall be to a depth
of 1 inch (25 mm) and shall only be placed on strips of metal
or metal lath laid across the spaces between combustible material
and the chimney.
|