2305.3.5 Shear wall height
definition. The height of a shear wall, h, shall be defined
as:
1. The maximum clear height
from the top of the foundation to the bottom of the diaphragm
framing above; or
2. The maximum clear height
from the top of the diaphragm to the bottom of the diaphragm
framing above [see Figure
2305.3.5(a)].
2305.3.5.1 Perforated shear
wall segment height definition. The height of a perforated
shear wall segment, h, shall be defined as specified in
Section 2305.3.5 for shear walls.
2305.3.5.2 Force transfer
shear wall pier height definition. The height, h, of
a wall pier in a shear wall with openings designed for force
transfer around openings shall be defined as the clear height
of the pier at the side of an opening [see Figure
2305.3.5(b)].
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|