| SECTION 2308 CONVENTIONAL
LIGHT-FRAME CONSTRUCTION
2308.3 Braced wall lines.
Buildings shall be provided with exterior and interior braced
wall lines as described in Section
2308.9.3 and installed in accordance with Sections 2308.3.1
through 2308.3.4.
2308.3.1 Spacing. Spacing
of braced wall lines shall not exceed 35 feet (10 668 mm)
o.c. in both the longitudinal and transverse directions
in each story.
2308.3.2 Braced wall panel
connections. Forces shall be transferred from the roofs
and floors to braced wall panels and from the braced wall
panels in upper stories to the braced wall panels in the
story below by the following:
1. Braced wall panel top
and bottom plates shall be fastened to joists, rafters
or full-depth blocking. Braced wall panels shall be extended
and fastened to roof framing at intervals not to exceed
50 feet (15 240 mm) between parallel braced wall lines.
Exception: Where roof
trusses are used, lateral forces shall be transferred from
the roof diaphragm to the braced wall by blocking of the ends
of the trusses or by other approved methods.
2. Bottom plate fastening
to joist or blocking below shall be with not less than
3-16d nails at 16 inches (406 mm) o.c.
3. Blocking shall be nailed
to the top plate below with not less than 3-8d toenails
per block.
4. Joists parallel to the
top plates shall be nailed to the top plate with not less
than 8d toenails at 6 inches (152 mm) o.c. In addition,
top plate laps shall be nailed with not less than 8-16d
face nails on each side of each break in the top plate.
2308.3.3 Sill anchorage.
Where foundations are required by Section 2308.3.4, braced
wall line sills shall be anchored to concrete or masonry
foundations. Such anchorage shall conform to the requirements
of Section 2308.6 except that such
anchors shall be spaced at not more than 4 feet (1219 mm)
o.c. for structures over two stories in height. The anchors
shall be distributed along the length of the braced wall
line. Other anchorage devices having equivalent capacity
are permitted.
2308.3.3.1 Anchorage to
all-wood foundations. Where all-wood foundations are
used, the force transfer from the braced wall lines shall
be determined based on calculation and shall have a capacity
greater than or equal to the connections required by Section
2308.3.3.
2308.3.4 Braced wall line
support. Braced wall lines shall be supported by continuous
foundations.
Exception: For structures
with a maximum plan dimension not over 50 feet (15 240 mm),
continuous foundations are required at exterior walls only.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|