2603.4.1.1 Masonry or concrete
construction. A thermal barrier is not required for
foam plastic installed in a masonry or concrete wall, floor
or roof system where the foam plastic insulation is covered
on each face by a minimum of 1 inch (25 mm) thickness of
masonry or concrete.
2603.4.1.2 Cooler and freezer
walls. Foam plastic installed in a maximum thickness
of 10 inches (254 mm) in cooler and freezer walls shall:
1. Have a flame spread index
of 25 or less and a smoke-developed index of not more
than 450, where tested in a minimum 4 inch (102 mm) thickness.
2. Have flash ignition and
self-ignition temperatures of not less than 600°F and
800°F (316°C and 427°C), respectively.
3. Have a covering of not
less than 0.032-inch (0.8 mm) aluminum or corrosion-resistant
steel having a base metal thickness not less than 0.0160
inch (0.4 mm) at any point.
4. Be protected by an automatic
sprinkler system. Where the cooler or freezer is within
a building, both the cooler or freezer and that part of
the building in which it is located shall be sprinklered.
2603.4.1.3 Walk-in coolers.
In nonsprinklered buildings, foam plastic having a thickness
that does not exceed 4 inches (102 mm) and a maximum flame
spread index of 75 is permitted in walk-in coolers or freezer
units where the aggregate floor area does not exceed 400
square feet (37 m2) and the foam plastic is covered
by a metal facing not less than 0.032-inch-thick (0.81 mm)
aluminum or corrosion-resistant steel having a minimum base
metal thickness of 0.016 inch (0.41 mm). A thickness of
up to 10 inches (254 mm) is permitted where protected by
a thermal barrier.
2603.4.1.4 Exterior wallsone-story
buildings. For one-story buildings, foam plastic having
a flame spread index of 25 or less, and a smoke-developed
index of not more than 450, shall be permitted without thermal
barriers in or on exterior walls in a thickness not more
than 4 inches (102 mm) where the foam plastic is covered
by a thickness of not less than 0.032-inch-thick (0.81 mm)
aluminum or corrosion-resistant steel having a base metal
thickness of 0.0160 inch (0.41 mm) and the building is equipped
throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1.
2603.4.1.5 Roofing.
Foam plastic insulation under a roof assembly or roof covering
that is installed in accordance with the code and the manufacturers
instructions shall be separated from the interior of the
building by wood structural panel sheathing not less than
0.47 inch (11.9 mm) in thickness bonded with exterior glue,
with edges supported by blocking, tongue-and-groove joints
or other approved type of edge support, or an equivalent
material. A thermal barrier is not required for foam plastic
insulation that is a part of a Class A, B or C roof-covering
assembly, provided the assembly with the foam plastic insulation
satisfactorily passes FM 4450 or UL 1256.
2603.4.1.6 Attics and crawl
spaces. Within an attic or crawl space where entry is
made only for service of utilities, foam plastic insulation
shall be protected against ignition by 1.5-inch-thick (38
mm) mineral fiber insulation; 0.25-inch-thick (6.4 mm) wood
structural panel, particleboard or hardboard; 0.375-inch
(9.5 mm) gypsum wallboard, corrosion-resistant steel having
a base metal thickness of 0.016 inch (0.4 mm) or other approved
material installed in such a manner that the foam plastic
insulation is not exposed. The protective covering shall
be consistent with the requirements for the type of construction.
2603.4.1.7 Doors not required
to have a fire protection rating. Where pivoted or side-hinged
doors are permitted without a fire protection rating, foam
plastic insulation, having a flame spread index of 75 or
less and a smoke-developed index of not more than 450, shall
be permitted as a core material where the door facing is
of metal having a minimum thickness of 0.032-inch (0.8 mm)
aluminum or steel having a base metal thickness of not less
than 0.016 inch (0.4 mm) at any point.
2603.4.1.8 Exterior doors
in buildings of Group R-2 or R-3. In occupancies classified
as Group R-2 or R-3, foam-filled exterior entrance doors
to individual dwelling units that do not require a fire-resistance
rating shall be faced with wood or other approved materials.
2603.4.1.9 Garage doors.
Where garage doors are permitted without a fire-resistance
rating and foam plastic is used as a core material, the
door facing shall be metal having a minimum thickness of
0.032-inch (0.8 mm) aluminum or 0.010-inch (0.25 mm) steel
or the facing shall be minimum 0.125-inch-thick (3.2 mm)
wood. Garage doors having facings other than those described
above shall be tested in accordance with, and meet the acceptance
criteria of, DASMA 107.
2603.4.1.10 Siding backer
board. Foam plastic insulation of not more than 2,000
British thermal units per square feet (Btu/sq. ft.) (22.7
MJ/m2) as determined by NFPA 259 shall be permitted
as a siding backer board with a maximum thickness of 0.5
inch (12.7 mm), provided it is separated from the interior
of the building by not less than 2 inches (51 mm) of mineral
fiber insulation or equivalent or where applied as insulation
with re-siding over existing wall construction.
2603.4.1.11 Interior trim.
Foam plastic used as interior trim in accordance with Section
2604 shall be permitted without a thermal barrier.
2603.4.1.12 Interior signs.
Foam plastic used for interior signs in covered mall buildings
in accordance with Section 402.15
shall be permitted without a thermal barrier. Foam plastic
signs that are not affixed to interior building surfaces
shall comply with Chapter 8 of the International Fire Code.
2603.4.1.13 Type V construction.
Foam plastic spray applied to a sill plate and header of
Type V construction is subject to all of the following:
1. The maximum thickness
of the foam plastic shall be 31/4
inches (82.6 mm).
2. The density of the foam
plastic shall be in the range of 1.5 to 2.0 pcf (24 to
32 kg/m3).
3. The foam plastic shall
have a flame spread index of 25 or less and an accompanying
smoke-developed index of 450 or less when tested in accordance
with ASTM E 84.