| SECTION 2603 FOAM PLASTIC
INSULATION
2603.1 General. The provisions
of this section shall govern the requirements and uses of
foam plastic insulation in buildings and structures.
2603.2 Labeling and identification.
Packages and containers of foam plastic insulation and foam
plastic insulation components delivered to the job site shall
bear the label of an approved agency showing the manufacturers
name, the product listing, product identification and information
sufficient to determine that the end use will comply with
the code requirements.
2603.3 Surface-burning characteristics.
Unless otherwise indicated in this section, foam plastic insulation
and foam plastic cores of manufactured assemblies shall have
a flame spread index of not more than 75 and a smoke-developed
index of not more than 450 where tested in the maximum thickness
intended for use in accordance with ASTM E 84. Loose fill-type
foam plastic insulation shall be tested as board stock for
the flame spread index and smoke-developed index.
Exceptions:
1. Smoke-developed index for
interior trim as provided for in Section
2604.2.
2. In cold storage buildings,
ice plants, food plants, food processing rooms and similar
areas, foam plastic insulation where tested in a thickness
of 4 inches (102 mm) shall be permitted in a thickness up
to 10 inches (254 mm) where the building is equipped throughout
with an automatic fire sprinkler system in accordance with
Section 903.3.1.1. The approved
automatic sprinkler system shall be provided in both the
room and that part of the building in which the room is
located.
3. Foam plastic insulation
that is a part of a Class A, B or C roof-covering assembly
provided the assembly with the foam plastic insulation satisfactorily
passes FM 4450 or UL 1256. The smoke-developed index shall
not be limited for roof applications.
4. Foam plastic insulation
greater than 4 inches (102 mm) in thickness shall have a
maximum flame spread index of 75 and a smoke-developed index
of 450 where tested at a minimum thickness of 4 inches (102
mm), provided the end use is approved in accordance with
Section 2603.9 using the thickness and density intended
for use.
5. Flame spread and smoke-developed
indexes for foam plastic interior signs in covered mall
buildings provided the signs comply with Section
402.15.
2603.4 Thermal barrier.
Except as provided for in Sections 2603.4.1 and 2603.9, foam
plastic shall be separated from the interior of a building
by an approved thermal barrier of 0.5-inch (12.7 mm) gypsum
wallboard or equivalent thermal barrier material that will
limit the average temperature rise of the unexposed
surface to not more than 250°F (120°C) after 15 minutes of
fire exposure, complying with the standard time-temperature
curve of ASTM E 119. The thermal barrier shall be installed
in such a manner that it will remain in place for 15 minutes
based on FM 4880, UL 1040, NFPA 286 or UL 1715. Combustible
concealed spaces shall comply with Section
717.
2603.4.1 Thermal barrier not
required. The thermal barrier specified in Section 2603.4
is not required under the conditions set forth in Sections
2603.4.1.1 through 2603.4.1.13.
2603.4.1.1 Masonry or concrete
construction. A thermal barrier is not required for
foam plastic installed in a masonry or concrete wall, floor
or roof system where the foam plastic insulation is covered
on each face by a minimum of 1 inch (25 mm) thickness of
masonry or concrete.
2603.4.1.2 Cooler and freezer
walls. Foam plastic installed in a maximum thickness
of 10 inches (254 mm) in cooler and freezer walls shall:
1. Have a flame spread index
of 25 or less and a smoke-developed index of not more
than 450, where tested in a minimum 4 inch (102 mm) thickness.
2. Have flash ignition and
self-ignition temperatures of not less than 600°F and
800°F (316°C and 427°C), respectively.
3. Have a covering of not
less than 0.032-inch (0.8 mm) aluminum or corrosion-resistant
steel having a base metal thickness not less than 0.0160
inch (0.4 mm) at any point.
4. Be protected by an automatic
sprinkler system. Where the cooler or freezer is within
a building, both the cooler or freezer and that part of
the building in which it is located shall be sprinklered.
2603.4.1.3 Walk-in coolers.
In nonsprinklered buildings, foam plastic having a thickness
that does not exceed 4 inches (102 mm) and a maximum flame
spread index of 75 is permitted in walk-in coolers or freezer
units where the aggregate floor area does not exceed 400
square feet (37 m2) and the foam plastic is covered
by a metal facing not less than 0.032-inch-thick (0.81 mm)
aluminum or corrosion-resistant steel having a minimum base
metal thickness of 0.016 inch (0.41 mm). A thickness of
up to 10 inches (254 mm) is permitted where protected by
a thermal barrier.
2603.4.1.4 Exterior wallsone-story
buildings. For one-story buildings, foam plastic having
a flame spread index of 25 or less, and a smoke-developed
index of not more than 450, shall be permitted without thermal
barriers in or on exterior walls in a thickness not more
than 4 inches (102 mm) where the foam plastic is covered
by a thickness of not less than 0.032-inch-thick (0.81 mm)
aluminum or corrosion-resistant steel having a base metal
thickness of 0.0160 inch (0.41 mm) and the building is equipped
throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1.
2603.4.1.5 Roofing.
Foam plastic insulation under a roof assembly or roof covering
that is installed in accordance with the code and the manufacturers
instructions shall be separated from the interior of the
building by wood structural panel sheathing not less than
0.47 inch (11.9 mm) in thickness bonded with exterior glue,
with edges supported by blocking, tongue-and-groove joints
or other approved type of edge support, or an equivalent
material. A thermal barrier is not required for foam plastic
insulation that is a part of a Class A, B or C roof-covering
assembly, provided the assembly with the foam plastic insulation
satisfactorily passes FM 4450 or UL 1256.
2603.4.1.6 Attics and crawl
spaces. Within an attic or crawl space where entry is
made only for service of utilities, foam plastic insulation
shall be protected against ignition by 1.5-inch-thick (38
mm) mineral fiber insulation; 0.25-inch-thick (6.4 mm) wood
structural panel, particleboard or hardboard; 0.375-inch
(9.5 mm) gypsum wallboard, corrosion-resistant steel having
a base metal thickness of 0.016 inch (0.4 mm) or other approved
material installed in such a manner that the foam plastic
insulation is not exposed. The protective covering shall
be consistent with the requirements for the type of construction.
2603.4.1.7 Doors not required
to have a fire protection rating. Where pivoted or side-hinged
doors are permitted without a fire protection rating, foam
plastic insulation, having a flame spread index of 75 or
less and a smoke-developed index of not more than 450, shall
be permitted as a core material where the door facing is
of metal having a minimum thickness of 0.032-inch (0.8 mm)
aluminum or steel having a base metal thickness of not less
than 0.016 inch (0.4 mm) at any point.
2603.4.1.8 Exterior doors
in buildings of Group R-2 or R-3. In occupancies classified
as Group R-2 or R-3, foam-filled exterior entrance doors
to individual dwelling units that do not require a fire-resistance
rating shall be faced with wood or other approved materials.
2603.4.1.9 Garage doors.
Where garage doors are permitted without a fire-resistance
rating and foam plastic is used as a core material, the
door facing shall be metal having a minimum thickness of
0.032-inch (0.8 mm) aluminum or 0.010-inch (0.25 mm) steel
or the facing shall be minimum 0.125-inch-thick (3.2 mm)
wood. Garage doors having facings other than those described
above shall be tested in accordance with, and meet the acceptance
criteria of, DASMA 107.
Exception: Garage doors
using foam plastic insulation complying with Section 2603.3
in detached and attached garages associated with one- and
two-family dwellings need not be provided with a thermal barrier.
2603.4.1.10 Siding backer
board. Foam plastic insulation of not more than 2,000
British thermal units per square feet (Btu/sq. ft.) (22.7
MJ/m2) as determined by NFPA 259 shall be permitted
as a siding backer board with a maximum thickness of 0.5
inch (12.7 mm), provided it is separated from the interior
of the building by not less than 2 inches (51 mm) of mineral
fiber insulation or equivalent or where applied as insulation
with re-siding over existing wall construction.
2603.4.1.11 Interior trim.
Foam plastic used as interior trim in accordance with Section
2604 shall be permitted without a thermal barrier.
2603.4.1.12 Interior signs.
Foam plastic used for interior signs in covered mall buildings
in accordance with Section 402.15
shall be permitted without a thermal barrier. Foam plastic
signs that are not affixed to interior building surfaces
shall comply with Chapter 8 of the International Fire Code.
2603.4.1.13 Type V construction.
Foam plastic spray applied to a sill plate and header of
Type V construction is subject to all of the following:
1. The maximum thickness
of the foam plastic shall be 31/4
inches (82.6 mm).
2. The density of the foam
plastic shall be in the range of 1.5 to 2.0 pcf (24 to
32 kg/m3).
3. The foam plastic shall
have a flame spread index of 25 or less and an accompanying
smoke-developed index of 450 or less when tested in accordance
with ASTM E 84.
2603.5 Exterior walls of buildings
of any height. Exterior walls of buildings of Type I,
II, III or IV construction of any height shall comply with
Sections 2603.5.1 through 2603.5.7. Exterior walls of cold
storage buildings required to be constructed of noncombustible
materials, where the building is more than one story in height,
shall also comply with the provisions of Sections 2603.5.1
through 2603.5.7. Exterior walls of buildings of Type V construction
shall comply with Sections 2603.2, 2603.3 and 2603.4.
2603.5.1 Fire-resistance-rated
walls. Where the wall is required to have a fire-resistance
rating, data based on tests conducted in accordance with
ASTM E 119 shall be provided to substantiate that the fire-resistance
rating is maintained.
2603.5.2 Thermal barrier.
Any foam plastic insulation shall be separated from
the building interior by a thermal barrier meeting the provisions
of Section 2603.4, unless special approval is obtained on
the basis of Section 2603.8.
Exception: One-story buildings
complying with Section 2603.4.1.4.
2603.5.3 Potential heat.
The potential heat of foam plastic insulation in any portion
of the wall or panel shall not exceed the potential heat
expressed in Btu per square feet (mJ/m2) of the
foam plastic insulation contained in the wall assembly tested
in accordance with Section 2603.5.5. The potential heat
of the foam plastic insulation shall be determined by tests
conducted in accordance with NFPA259 and the results shall
be expressed in Btu per square feet (mJ/m2).
Exception: One-story buildings
complying with Section 2603.4.1.4.
2603.5.4 Flame spread and
smoke-developed indexes. Foam plastic insulation, exterior
coatings and facings shall be tested separately in the thickness
intended for use, but not to exceed 4 inches (102 mm), and
shall each have a flame spread index of 25 or less and a
smoke-developed index of 450 or less as determined in accordance
withASTME84.
Exception: Prefabricated
or factory-manufactured panels having minimum 0.020-inch (0.51
mm) aluminum facings and a total thickness of 0.25 inch (6.4
mm) or less are permitted to be tested as an assembly where
the foam plastic core is not exposed in the course of construction.
2603.5.5 Test standard.
The wall assembly shall be tested in accordance with and
comply with the acceptance criteria of NFPA 285.
Exception: One-story buildings
complying with Section 2603.4.1.4.
2603.5.6 Label required.
The edge or face of each piece of foam plastic insulation
shall bear the label of an approved agency. The label shall
contain the manufacturers or distributors identification,
model number, serial number or definitive information describing
the product or materials performance characteristics
and approved agencys identification.
2603.5.7 Ignition. Exterior
walls shall not exhibit sustained flaming where tested in
accordance with NFPA 268. Where a material is intended to
be installed in more than one thickness, tests of the minimum
and maximum thickness intended for use shall be performed.
Exception: Assemblies
protected on the outside with one of the following:
1. A thermal barrier complying
with Section 2603.4.
2. A minimum 1 inch (25 mm)
thickness of concrete or masonry.
3. Glass-fiber-reinforced concrete
panels of a minimum thickness of 0.375 inch (9.5 mm).
4. Metal-faced panels having
minimum 0.019- inch-thick (0.48 mm) aluminum or 0.016-inchthick
(0.41 mm) corrosion-resistant steel outer facings.
5. A minimum 0.875 inch (22.2
mm) thickness of stucco complying with Section
2510.
2603.6 Roofing. Foam plastic
insulation meeting the requirements of Sections 2603.2, 2603.3
and 2603.4 shall be permitted as part of a roof-covering assembly,
provided the assembly with the foam plastic insulation is
a Class A, B or C roofing assembly where tested in accordance
with ASTM E 108 or UL 790.
2603.7 Plenums. Foam plastic
insulation shall not be used as interior wall or ceiling finish
in plenums except as permitted in Section
2604 or when protected by a thermal barrier in accordance
with Section 2603.4.
2603.8 Protection against
termites. In areas where the probability of termite infestation
is very heavy in accordance with Figure
2603.8, extruded and expanded polystyrene, polyisocyanurate
and other foam plastics shall not be installed on the exterior
face or under interior or exterior foundation walls or slab
foundations located below grade. The clearance between foam
plastics installed above grade and exposed earth shall be
at least 6 inches (152 mm).
Exceptions:
1. Buildings where the structural
members of walls, floors, ceilings and roofs are entirely
of noncombustible materials or preservatively treated wood.
2. An approved method of protecting
the foam plastic and structure from subterranean termite
damage is provided.
3. On the interior side of
basement walls.
2603.9 Special approval.
Foam plastic shall not be required to comply with the requirements
of Sections 2603.4 through 2603.7 where specifically approved
based on large-scale tests such as, but not limited to, NFPA
286 (with the acceptance criteria of Section
803.2), FM 4880, UL 1040 or UL 1715. Such testing shall
be related to the actual end-use configuration and be performed
on the finished manufactured foam plastic assembly in the
maximum thickness intended for use. Foam plastics that are
used as interior finish on the basis of special tests shall
also conform to the flame spread requirements of Chapter 8.
Assemblies tested shall include seams, joints and other typical
details used in the installation of the assembly and shall
be tested in the manner intended for use.
|