SECTION 414 HAZARDOUS
MATERIALS
[F] 414.5.4 Standby or emergency
power. Where mechanical ventilation, treatment systems,
temperature control, alarm, detection or other electrically
operated systems are required, such systems shall be provided
with an emergency or standby power system in accordance with
this code or the ICC Electrical Code.
Exceptions:
1. Storage areas for Class
I and II oxidizers.
2. Storage areas for Class III, IV and V organic peroxides.
3. Storage, use and handling areas for highly toxic or toxic
materials as provided for in the International Fire Code.
4. Standby power for mechanical ventilation, treatment systems
and temperature control systems shall not be required where
an approved fail-safe engineered system is installed.
|
|
|