SECTION 415 GROUPS H-1, H-2, H-3, H-4 AND H-5
[F] 415.4 Special provisions
for Group H-l occupancies. Group H -1 occupancies shall
be in buildings used for no other purpose, shall not exceed
one story in height and be without a basement, crawl spaces
or other under-floor spaces. Roofs shall be of lightweight
construction with suitable thermal insulation to prevent sensitive
material from reaching its decomposition temperature. Group
H -1 occupancies containing materials which are in themselves
both physical and health hazards in quantities exceeding the
maximum allowable quantities per control area in Table
307.1(2) shall comply with requirements for both Group
H -1 and H -4 occupancies.
[F] 415.4.1 Floors
in storage rooms. Floors in storage areas for organic
peroxides, pyrophoric materials and unstable (reactive) materials
shall be of liquid-tight, noncombustible construction.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|