| SECTION 509 SPECIAL PROVISIONS
509.2 Group S-2 enclosed
or open parking garage with Group A, B, M, R or S above.
A basement and/or the first story above grade plane of a building
shall be considered as a separate and distinct building for
the purpose of determining area limitations, continuity of
fire walls, limitation of number of stories and type of construction
when all of the following conditions are met:
1. The basement and/or the
first story above grade plane is of Type IA construction
and is separated from the building above with a horizontal
assembly having a minimum 3-hour fire-resistance rating.
2. Shaft, stairway, ramp or
escalator enclosures through the horizontal assembly shall
have not less than a 2-hour fire-resistance rating with
opening protectives in accordance with Table
715.4.
Exception: Where the enclosure
walls below the horizontal assembly have not less than a 3-hour
fire-resistance rating with opening protectives in accordance
with Table 715.4, the enclosure
walls extending above the horizontal assembly shall be permitted
to have a 1-hour fire-resistance rating, provided:
1. The building above the
horizontal assembly is not required to be of Type I construction;
2. The enclosure connects
less than four stories; and
3. The enclosure opening
protectives above the horizontal assembly have a minimum
1-hour fire protection rating.
3. The building above the horizontal
assembly shall be permitted to have multiple Group A uses,
each with an occupant load of less than 300, or Group B,
M, R or S uses.
4. The building below the horizontal
assembly is a Group S-2 enclosed or open parking garage,
used for the parking and storage of private motor vehicles.
Exceptions:
1. Entry lobbies, mechanical
rooms and similar uses incidental to the operation of the
building shall be permitted.
2. Multiple Group A uses, each
with an occupant load of less than 300, or Group B or M
uses shall be permitted, in addition to those uses incidental
to the operation of the building (including storage areas),
provided that the entire structure below the horizontal
assembly is protected throughout by an approved automatic
sprinkler system.
5. The maximum building height
in feet shall not exceed the limits set forth in
Section 503 for the building having the smaller allowable
height as measured from the grade plane.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|