| SECTION 719 THERMAL- AND SOUND-INSULATING
MATERIALS
719.1 General. Insulating
materials, including facings such as vapor retarders and vaporpermeable
membranes, similar coverings, and all layers of single and
multilayer reflective foil insulations, shall comply with
the requirements of this section. Where a flame spread index
or a smoke-developed index is specified in this section, such
index shall be determined in accordance with ASTM E 84. Any
material that is subject to an increase in flame spread index
or smoke-developed index beyond the limits herein established
through the effects of age, moisture, or other atmospheric
conditions shall not be permitted.
Exceptions:
1.Fiberboard insulation shall
comply with Chapter 23.
2.Foam plastic insulation shall
comply with Chapter 26.
3.Duct
and pipe insulation and duct and pipe coverings and linings
in plenums shall comply with the International Mechanical
Code.
719.2
Concealed installation. Insulating materials, where concealed
as installed in buildings of any type of construction, shall
have a flame spread index of not more than 25 and a smoke-developed
index of not more than 450.
Exception: Cellulose loose-fill insulation that is not
spray applied, complying with the requirements of Section
719.6, shall only be required to meet the smoke-developed
index of not more than 450.
719.2.1 Facings. Where such materials are installed
in concealed spaces in buildings of Type III, IV or V construction,
the flame spread and smoke-developed limitations do not
apply to facings, coverings, and layers of reflective foil
insulation that are installed behind and in substantial
contact with the unexposed surface of the ceiling, wall
or floor finish.
719.3
Exposed installation. Insulating materials, where exposed
as installed in buildings of any type of construction, shall
have a flame spread index of not more than 25 and a smoke-developed
index of not more than 450.
Exception: Cellulose loose-fill insulation that is not
spray applied complying with the requirements of Section 719.6
shall only be required to meet the smoke-developed index of
not more than 450.
719.3.1 Attic floors. Exposed insulation materials installed
on attic floors shall have a critical radiant flux of not
less than 0.12 watt per square centimeter when tested in
accordance with ASTM E 970.
719.4 Loose-fill insulation.
Loose-fill insulation materials that cannot be mounted in
the ASTM E 84 apparatus without a screen or artificial supports
shall comply with the flame spread and smoke-developed limits
of Sections 719.2 and 719.3 when tested in accordance with
CAN/ULC S 102.2.
Exception: Cellulose loose-fill insulation shall not be
required to comply with the flame spread index requirement
of CAN/ULC S 102.2, provided such insulation complies with
the requirements of Section 719.6.
719.5
Roof insulation. The use of combustible roof insulation
not complying with Sections 719.2 and 719.3 shall be permitted
in any type of construction provided it is covered with approved
roof coverings directly applied thereto.
719.6
Cellulose loose-fill insulation. Cellulose loose-fill
insulation shall comply with CPSC 16 CFR, Part 1209 and CPSC
16 CFR, Part 1404. Each package of such insulating material
shall be clearly labeled in accordance with CPSC 16 CFR, Part
1209 and CPSC 16 CFR, Part 1404.
719.7
Insulation and covering on pipe and tubing. Insulation
and covering on pipe and tubing shall have a flame spread
index of not more than 25 and a smoke-developed index of not
more than 450.
Exception: Insulation and covering on pipe and tubing
installed in plenums shall comply with the International Mechanical
Code.
|