SECTION
721 CALCULATED FIRE RESISTANCE
721.3.2
Concrete masonry walls. The fire-resistance rating of
walls and partitions constructed of concrete masonry units
shall be determined from Table
721.3.2. The rating shall be based on the equivalent thickness
of the masonry and type of aggregate used.
721.3.2.1
Finish on nonfire-exposed side. Where pIaster or gypsum
wallboard is applied to the side of the wall not exposed
to fire, the contribution of the finish to the total fire-resistance
rating shall be determined as follows:
The
thickness of gypsum wallboard or plaster shall be corrected
by multiplying the actual thickness of the finish by applicable
factor determined from Table
721.2.1.4(1). This corrected thickness of finish shall
be added to the equivalent thickness of masonry and the
fire-resistance rating of the masonry and finish determined
from Table 721.3.2.
721.3.2.2
Finish on fire-exposed side. Where plaster or gypsum
wallboard is applied to the fire-exposed side of the wall,
the contribution of the finish to the total fire-resistance
rating shall be determined as follows:
The
time assigned to the finish as established by Table
721.2.1.4(2) shall be added to the fire-resistance rating
determined in Section 721.3.2 for the masonry alone, or
in Section 721.3.2.1 for the masonry and finish on the nonfire-exposed
side.
721.3.2.3 Nonsymmetrical
assemblies. For a wall having no finish on one side
or having different types or thicknesses of finish on each
side, the calculation procedures of this section shall be
performed twice, assuming either side of the wall to be
the fire-exposed side. The fire-resistance rating of the
wall shall not exceed the lower of the two values calculated.
Exception: For exterior walls with more than 5 feet (1524
mm) of horizontal separation, the fire shall be assumed to
occur on the interior side only.
721.3.2.4 Minimum concrete masonry fire-resistance
rating. Where the finish applied to a concrete masonry
wall contributes to its fire-resistance rating, the masonry
alone shall provide not less than one-half the total required
fire-resistance rating.
721.3.2.5 Attachment of finishes. Installation
of finishes shall be as follows:
I. Gypsum
wallboard and gypsum lath applied to concrete masonry
or concrete walls shall be secured to wood or steel
furring members spaced not more than 16 inches (406
mm) on center (o.c.).
2. Gypsum
wallboard shall be installed with the long dimension
parallel to the furring members and shall have all joints
finished.
3. Other
aspects of the installation of finishes shall comply
with the applicable provisions of Chapters 7 and 25.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|