SECTION 907 FIRE ALARM AND
DETECTION SYSTEMS
[F]
907.2.12.1 Automatic fire detection. Smoke detectors
shall be provided in accordance with this section. Smoke detectors
shall be connected to an automatic fire alarm system. The
activation of any detector required by this section shall
operate the emergency voice/alarm communication system. Smoke
detectors shall be located as follows:
1.
In each mechanical equipment, electrical, transformer, telephone
equipment or similar room which is not provided with sprinkler
protection, elevator machine rooms and in elevator lobbies.
2.
In the main return air and exhaust air plenum of each air-conditioning
system having a capacity greater than 2,000 cubic feet per
minute (cfm) (0.94 m3/s). Such detectors shall
be located in a serviceable area downstream of the last
duct inlet.
3. At
each connection to a vertical duct or riser serving two
or more stories from a return air duct or plenum of an air-conditioning
system. In Group R -1 and R -2 occupancies a listed smoke
detector is allowed to be used in each return air riser
carrying not more than 5,000 cfm (2.4 m3/s) and
serving not more than 10 air inlet openings.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|