SECTION
1008 DOORS, GATES AND TURNSTILES
1008.1 Doors. Means of egress doors shall meet the
requirements of this section. Doors serving a means of egress
system shall meet the requirements of this section and Section
1017.2. Doors provided for egress purposes in numbers
greater than required by this code shall meet the requirements
of this section.
Means of egress doors shall be readily distinguishable from
the adjacent construction and finishes such that the doors
are easily recognizable as doors. Mirrors or similar reflecting
materials shall not be used on means of egress doors. Means
of egress doors shall not be concealed by curtains, drapes,
decorations or similar materials.
1008.1.1
Size of doors. The minimum width of each door opening
shall be sufficient for the occupant load thereof and
shall provide a clear width of not less than 32 inches
(813 mm). Clear openings of doorways with swinging doors
shall be measured between the face of the door and the
stop, with the door open 90 degrees (1.57 rad). Where
this section requires a minimum clear width of 32 inches
(813 mm) and a door opening includes two door leaves without
a mullion, one leaf shall provide a clear opening width
of 32 inches (813 mm). The maximum width of a swinging
door leaf shall be 48 inches (1219 mm) nominal. Means
of egress doors in a Group 1-2 occupancy used for the
movement of beds shall provide a clear width not less
than 41.5 inches (1054 mm). The height of doors shall
not be less than 80 inches (2032 mm).
Exceptions:
1.
The minimum and maximum width shall not apply to door
openings that are not part of the required means of egress
in Group R-2 and R-3 occupancies.
2. Door
openings to resident sleeping units in Group 1-3 occupancies
shall have a clear width of not less than 28 inches (711
mm).
3. Door
openings to storage closets less than 10 square feet (0.93
m2) in area shall not be limited by the minimum
width.
4. Width
of door leafs in revolving doors that comply with Section
1008.1.3.1 shall not be limited.
5. Door
openings within a dwelling unit or sleeping unit shall
not be less than 78 inches (1981 mm) in height.
6. Exterior
door openings in dwelling units and sleeping units, other
than the required exit door, shall not be less than 76
inches (1930 mm) in height.
7. In
other than Group R-l occupancies, the minimum widths shall
not apply to interior egress doors within a dwelling unit
or sleeping unit that is not required to be an Accessible
unit, Type A unit or Type B unit.
8. Door
openings required to be accessible within Type B units
shall have a minimum clear width of 31.75 inches (806
mm).
1008.1.1.1 Projections into clear width. There shall
not be projections into the required clear width lower
than 34 inches (864 mm) above the floor or ground. Projections
into the clear opening width between 34 inches (864
mm) and 80 inches (2032 mm) above the floor or ground
shall not exceed 4 inches (102 mm).
1008.1.2
Door swing. Egress doors shall be side-hinged swinging.
Exceptions:
1. Private
garages, office areas, factory and storage areas with
an occupant load of 10 or less.
2. Group
1-3 occupancies used as a place of detention.
3. Critical
or intensive care patient rooms within suites of health
care facilities.
4. Doors
within or serving a single dwelling unit in Groups R-2
and R-3.
5. In
other than Group H occupancies, revolving doors complying
with Section 1008.1.3.1.
6. In
other than Group H occupancies, horizontal sliding doors
complying with Section 1008.1.3.3 are permitted in a means
of egress.
7. Power-operated doors in accordance with
Section 1008.1.3.2.
8. Doors
serving a bathroom within an individual sleeping unit
in Group R-1. Doors shall swing in the direction of egress
travel where serving an occupant load of 50 or more persons
or a Group H occupancy.
The
opening force for interior side-swinging doors with-out
closers shall not exceed a 5-pound (22 N) force. For other
side-swinging, sliding and folding doors, the door latch
shall release when subjected to a I 5-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound
(133 N) force. The door shall swing to a full-open position
when subjected to a I 5-pound (67 N) force. Forces shall
be applied to the latch side.
1008.1.3
Special doors. Special doors and security grilles
shall comply with the requirements of Sections 1008.1.3.1
through 1008.1.3.5.
1008.1.3.1 Revolving doors. Revolving doors shall
comply with the following:
1.
Each revolving door shall be capable of collapsing
into a book fold position with parallel egress paths
providing an aggregate width of 36 inches (914 mm).
2. A
revolving door shall not be located within 10 feet
(3048 mm) of the foot of or top of stairs or escalators.
A dispersal area shall be provided between the stairs
or escalators and the revolving doors.
3. The
revolutions per minute (rpm) for a revolving door
shall not exceed those shown in Table
1008.1.3.1.
4. Each revolving door shall have a side-hinged
swinging door which complies with Section 1008.1 in
the same wall and within 10 feet (3048 mm) of the
revolving door.
1008.1.3.1.1 Egress
component. A revolving door used as a component
of a means of egress shall comply with Section 1008.1.3.1
and the following three conditions:
1. Revolving doors
shall not be given credit for more than 50 percent
of the required egress capacity.
2. Each
revolving door shall be credited with no more
than a 50-person capacity.
3. Each
revolving door shall be capable of being collapsed
when a force of not more than 130 pounds (572)
is applied within 3 inches (76 mm) of the outer
edge of a wing.
1008.1.3.1.2 Other than egress component.
A revolving door used as other than a component
of a means of egress shall comply with Section 1008.1.3.1.
The collapsing force of a revolving door not used
as a component of a means of egress shall not be
more than 180 pounds (801 N).
Exception:
A collapsing force in excess of 180 pounds (801 N) is permitted
if the collapsing force is reduced to not more than 130
pounds (572) when at least one of the following conditions
is satisfied:
1.
There is a power failure or power is removed to the device
holding the door wings in position.
2. There
is an actuation of the automatic sprinkler system where
such system is provided.
3. There
is an actuation of a smoke detection system which is installed
in accordance with Section 907 to
provide coverage in areas within the building which are
within 75 feet (22 860 mm) of the revolving doors.
4.
There is an actuation of a manual control switch, in an
approved location and clearly defined, which reduces the
holding force to below the 130-pound (572) force level.
1008.1.3.2 Power-operated doors. Where means of
egress doors are operated by power, such as doors with
a photoelectric-actuated mechanism to open the door
upon the approach of a person, or doors with power-assisted
manual operation, the design shall be such that in the
event of power failure, the door is capable of being
opened manually to permit means of egress travel or
closed where necessary to safeguard means of egress.
The forces required to open these doors manually shall
not exceed those specified in Section 1008.1.2, except
that the force to set the door in motion shall not exceed
50 pounds (220 N). The door shall be capable of swinging
from any position to the full width of the opening in
which such door is installed when a force is applied
to the door on the side from which egress is made. Full-power-operated
doors shall comply with BHMA AI56.1O. Power-assisted
and low-energy doors shall comply with BHMA AI56.19.
Exceptions:
1. Occupancies in Group 1-3.
2. Horizontal
sliding doors complying with Section 1008.1.3.3.
3. For a biparting door in
the emergency breakout mode, a door leaf located within
a multiple-leaf opening shall be exempt from the minimum
32-inch (813 mm) single-leaf requirement of Section 1008.1.1,
provided a minimum 32-inch (813 mm) clear opening is provided
when the two biparting leaves meeting in the center are
broken out.
1008.1.3.3
Horizontal sliding doors. In other than Group H
occupancies, horizontal sliding doors permitted to be
a component of a means of egress in accordance with
Exception 5 to Section 1008.1.2 shall comply with all
of the following criteria:
1.
The doors shall be power operated and shall be capable
of being operated manually in the event of power failure.
2. The
doors shall be openable by a simple method from both
sides without special knowledge or effort.
3. The
force required to operate the door shall not exceed
30 pounds (133 N) to set the door in motion and 15
pounds (67 N) to close the door or open it to the
minimum required width.
4. The
door shall be openable with a force not to exceed
15 pounds (67 N) when a force of 250 pounds (1100
N) is applied perpendicular to the door adjacent to
the operating device.
5. The door assembly
shall comply with the applicable fire protection rating
and, where rated, shall be self-closing or automatic
closing by smoke detection in accordance with Section
715.4.7.3, shall be installed in accordance with
NFP A 80 and shall comply with Section
715.
6. The
door assembly shall have an integrated standby power
supply.
7.
The door assembly power supply shall be electrically
supervised.
8. The
door shall open to the minimum required width within
10 seconds after activation of the operating device.
1008.1.3.4 Access-controlled egress doors. The entrance
doors in a means of egress in buildings with an occupancy
in Group A, B, E, M, R or R -2 and entrance doors to
tenant spaces in occupancies in Groups A, B, E, M, R-l
and R-2 are permitted to be equipped with an approved
entrance and egress access control system which shall
be installed in accordance with all of the following
criteria:
1. A
sensor shall be provided on the egress side arranged
to detect an occupant approaching the doors. The doors
shall be arranged to unlock by a signal from or loss
of power to the sensor.
2. Loss of power to that part of the access control
system which locks the doors shall automatically unlock
the doors.
3. The
doors shall be arranged to unlock from a manual unlocking
device located 40 inches to 48 inches (1016 mm to
1219 mm) vertically above the floor and within 5 feet
(1524 mm) of the secured doors. Ready access shall
be provided to the manual unlocking device and the
device shall be clearly identified by a sign that
reads "PUSH TO EXIT." When operated,
the manual unlocking device shall result in direct
interruption of power to the lockindependent of the
access control system electronics and the doors shall
remain unlocked for a minimum of 30 seconds.
4. Activation of the building fire alarm system,
if provided, shall automatically unlock the doors,
and the doors shall remain unlocked until the fire
alarm system has been reset.
5. Activation of the building automatic sprinkler
or fire detection system, if provided, shall automatically
unlock the doors. The doors shall remain unlocked
until the fire alarm system has been reset.
6. Entrance doors in buildings with an occupancy
in Group A, B, E or M shall not be secured from the
egress side during periods that the building is open
to the general public.
1008.1.3.5 Security grilles. In Groups B, F, M and
S, horizontal sliding or vertical security grilles are
permitted at the main exit and shall be openable from
the inside without the use of a key or special knowledge
or effort during periods that the space is occupied.
The grilles shall remain secured in the full-open position
during the period of occupancy by the general public.
Where two or more means of egress are required, not
more than one-half of the exits or exit access doorways
shall be equipped with horizontal sliding or vertical
security grilles.
1008.1.4
Floor elevation. There shall be a floor or landing
on each side of a door. Such floor or landing shall be
at the same elevation on each side of the door. Landings
shall be level except for exterior landings, which are
permitted to have a slope not to exceed 0.25 unit vertical
in 12 units horizontal (2-percent slope).
Exceptions:
1.
Doors serving individual dwelling units in Groups R-2
and R-3 where the following apply:
1.1. A door is permitted to open at the top step
of an interior flight of stairs, provided the door
does not swing over the top step.
1.2. Screen doors and storm doors are permitted
to swing over stairs or landings.
2. Exterior doors as provided for in Section
1003.5, Exception 1, and Section
1018.2, which are not on an accessible route.
3. In
Group R-3 occupancies not required to be Accessible
units, Type A units or Type B units, the landing at
an exterior doorway shall not be more than 7.75 inches
(197 mm) below the top of the threshold, provided the
door, other than an exterior storm or screen door, does
not swing over the landing.
4. Variations in elevation due to differences in
finish materials, but not more than 0.5 inch (12.7 mm).
5. Exterior decks, patios or balconies that are
part of Type B dwelling units, have impervious surfaces
and that are not more than 4 inches (102 mm) below the
finished floor level of the adjacent interior space
of the dwelling unit.
1008.1.5
Landings at doors. Landings shall have a width not
less than the width of the stairway or the door, whichever
is greater. Doors in the fully open position shall not
reduce a required dimension by more than 7 inches (178
mm). When a landing serves an occupant load of 50 or more,
doors in any position shall not reduce the landing to
less than one-half its required width. Landings shall
have a length measured in the direction of travel of not
less than 44 inches (1118 mm).
Exception: Landing length in the direction of travel
in Groups R-3 and U and within individual units of Group
R-2 need not exceed 36 inches (914 mm).
1008.1.6
Thresholds. Thresholds at doorways shall not exceed
0.75 inch (19.1 mm) in height for sliding doors serving
dwelling units or 0.5 inch (12.7 mm) for other doors.
Raised thresholds and floor level changes greater than
0.25 inch (6.4 mm) at doorways shall be beveled with a
slope not greater than one unit vertical in two units
horizontal (50-percent slope).
Exception:
The threshold height shall be limited to 7.75 inches (197
mm) where the occupancy is Group R-2 or R-3; the door is
an exterior door that is not a component of the required
means of egress; the door, other than an exterior storm
or screen door does not swing over the landing or step;
and the doorway is not on an accessible route as required
by Chapter 11 and is not part of an Accessible unit, Type
A unit or Type B unit.
1008.1.7
Door arrangement. Space between two doors in a series
shall be 48 inches (1219 mm) minimum plus the width of
a door swinging into the space. Doors in a series shall
swing either in the same direction or away from the space
between the doors.
Exceptions:
1.
The minimum distance between horizontal sliding power-operated
doors in a series shall be 48 inches (1219 mm).
2.
Storm and screen doors serving individual dwelling units
in Groups R - 2 and R - 3 need not be spaced 48 inches
(1219 mm) from the other door.
3. Doors
within individual dwelling units in Groups R-2 and R-3
other than within Type A dwelling units.
1008.1.8
Door operations. Except as specifically permitted
by this section egress doors shall be readily open able
from the egress side without the use of a key or special
knowledge or effort.
1008.1.8.1 Hardware. Door handles, pulls, latches,
locks and other operating devices on doors required
to be accessible by Chapter 11 shall not require tight
grasping, tight pinching or twisting of the wrist to
operate.
1008.1.8.2 Hardware height. Door handles, pulls,
latches, locks and other operating devices shall be
installed 34 inches (864 mm) minimum and 48 inches (1219
mm) maximum above the finished floor. Locks used only
for security purposes and not used for normal operation
are permitted at any height.
Exception:
Access doors or gates in barrier walls and fences protecting
pools, spas and hot tubs shall be permitted to have operable
parts of the release of latch on self-latching devices at
54 inches (1370 mm) maximum above the finished floor or
ground, provided the self-latching devices are not also
self-locking devices operated by means of a key, electronic
opener or integral combination lock.
1008.1.8.3 Locks and latches. Locks and latches
shall be permitted to prevent operation of doors where
any of the following exists:
1. Places of detention
or restraint.
2.
In buildings in occupancy Group A having an occupant
load of 300 or less, Groups B, F, M and S, and in
places of religious worship, the main exterior door
or doors are permitted to be equipped with key-operated
locking devices from the egress side provided:
2.1. The locking device is readily distinguishable
as locked,
2.2. A readily visible
durable sign is posted on the egress side on or
adjacent to the door stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS OCCUPIED. The sign
shall be in letters 1 inch (25 mm) high on a contrasting
background,
2.3. The use of the
key-operated locking device is revokable by the
building official for due cause.
3. Where egress doors
are used in pairs, approved automatic flush bolts
shall be permitted to be used, provided that the door
leaf having the automatic flush bolts has no doorknob
or surface-mounted hardware.
4. Doors from individual
dwelling or sleeping units of Group R occupancies
having an occupant load of 10 or less are permitted
to be equipped with a night latch, dead bolt or security
chain, provided such devices are open able from the
inside without the use of a key or tool.
1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not
permitted.
Exceptions:
1. On
doors not required for egress in individual dwelling units
or sleeping units.
2. Where
a pair of doors serves a storage or equipment room, manually
operated edge- or surface-mounted bolts are permitted
on the inactive leaf.
1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require
more than one operation.
Exceptions:
1. Places of detention or
restraint.
2. Where
manually operated bolt locks are permitted by Section
1008.1.8.4.
3.
Doors with automatic flush bolts as permitted by Section
1008.1.8.3, Exception 3.
4. Doors
from individual dwelling units and sleeping units of Group
R occupancies as permitted by Section 1008.1.8.3, Exception
4.
1008.1.8.6 Delayed egress locks. Approved, listed,
delayed egress locks shall be permitted to be installed
on doors serving any occupancy except Group A, E and
H occupancies in buildings that are equipped throughout
with an automatic sprinkler system in accordance with
Section 903.3.1.1 or an
approved automatic smoke or heat detection system installed
in accordance with Section 907,
provided that the doors unlock in accordance with Items
1 through 6 below. A building occupant shall not be
required to pass through more than one door equipped
with a delayed egress lock before entering an exit.
1.The doors unlock upon
actuation of the automatic sprinkler system or automatic
fire detection system.
2. The doors unlock
upon loss of power controlling the lock or lock mechanism.
3. The
door locks shall have the capability of being unlocked
by a signal from the fire command center.
4. The
initiation of an irreversible process which will release
the latch in not more than 15 seconds when a force
of not more than 15 pounds (67 N) is applied for 1
second to the release device. Initiation of the irreversible
process shall activate an audible signal in the vicinity
of the door. Once the door lock has been released
by the application of force to the releasing device,
relocking shall be by manual means only.
Exception:
Where approved, a delay of not more than 30 seconds is permitted.
5. A
sign shall be provided on the door located above and
within 12 inches (305 mm) of the release device reading:
PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN
15 [30] SECONDS.
6. Emergency lighting
shall be provided at the door.
1008.1.8.7 Stairway
doors. Interior stairway means of egress doors shall
be open able from both sides without the use of a key
or special knowledge or effort.
Exceptions:
1.
Stairway discharge doors shall be open able from the
egress side and shall only be locked from the opposite
side.
2.
This section shall not apply to doors arranged in accordance
with Section 403.12.
3.
In stairways serving not more than four stories, doors
are permitted to be locked from the side opposite the
egress side, provided they are open able from the egress
side and capable of being unlocked simultaneously without
unlatching upon a signal from the fire command center,
if present, or a signal by emergency personnel from
a single location inside the main entrance to the building.
1008.1.9
Panic and fire exit hardware. Where panic and fire
exit hardware is installed, it shall comply with the following:
1.
The actuating portion of the releasing device shall
extend at least one half of the door leaf width.
2.
The maximum unlatching force shall not exceed 15 pounds
(67 N). Each door in a means of egress from a Group
A or E occupancy having an occupant load of 50 or more
and any Group H occupancy shall not be provided with
a latch or lock unless it is panic hardware or fire
exit hardware.
Exception: A main exit of a Group A occupancy in
compliance with Section 1008.1.8.3, Item 2. Electrical
rooms with equipment rated 1,200 amperes or more and over
6 feet (1829 mm) wide that contain over current devices,
switching devices or control devices with exit access doors
must be equipped with panic hard ware and doors must swing
in the direction of egress. If balanced doors are used and
panic hardware is required, the panic hardware shall be
the push-pad type and the pad shall not extend more then
one-half the width of the door measured from the latch side.