|
SECTION
1025 ASSEMBLY
1025.1
General. Occupancies in Group A which contain seats, tables,
displays, equipment or other material shall comply with this
section.
1025.1.1
Bleachers. Bleachers, grandstands, and folding and telescopic
seating shall comply with ICC 300.
1025.2
Assembly main exit. Group A occupancies that have an occupant
load of greater than 300 shall be provided with a main exit.
The main exit shall be of sufficient width to accommodate
not less than one-half of the occupant load, but such width
shall not be less than the total required width of all means
of egress leading to the exit. Where the building is classified
as a Group A occupancy, the main exit shall front on at least
one street or an unoccupied space of not less than 10 feet
(3048 mm) in width that adjoins a street or public way.
Exception: In assembly occupancies where there is no well-defined
main exit or where multiple main exits are provided, exits
shall be permitted to be distributed around the perimeter
of the building provided that the total width of egress is
not less than 100 percent of the required width.
1025.3
Assembly other exits. In addition to having access to
a main exit, each level in a Group A occupancy having an occupant
load greater than 300 shall be provided with additional means
of egress that shall provide an egress capacity for at least
one-half of the total occupant load served by that level and
comply with Section 1015.2.
Exception: In assembly occupancies where there is no well-defined
main exit or where multiple main exits are provided, exits
shall be permitted to be distributed around the perimeter
of the building, provided that the total width of egress is
not less than 100 percent of the required width.
1025.4
Foyers and lobbies. In Group A-1 occupancies, where persons
are admitted to the building at times when seats are not available
and are allowed to wait in a lobby or similar space, such
use of lobby or similar space shall not encroach upon the
required clear width of the means of egress. Such waiting
areas shall be separated from the required means of egress
by substantial permanent partitions or by fixed rigid railings
not less than 42 inches (1067 mm) high. Such foyer, if not
directly connected to a public street by all the main entrances
or exits, shall have a straight and unobstructed corridor
or path of travel to every such main entrance or exit.
1025.5
Interior balcony and gallery means of egress. For balconies
or galleries having a seating capacity of 50 or more located
in Group A occupancies, at least two means of egress shall
be provided, with one from each side of every balcony or gallery
and at least one leading directly to an exit.
1025.5.1 Enclosure of balcony openings. Interior stairways
and other vertical openings shall be enclosed in an exit
enclosure as provided in Section 1020.1,
except that stair ways are permitted to be open between
the balcony and the main assembly floor in occupancies such
as theaters, places I of religious worship and auditoriums.
At least one accessible means of egress is required from
a balcony or gallery level containing accessible seating
locations in accordance with Section
1007.3 or 1007.4.
1025.6
Width of means of egress for assembly. The clear width
of aisles and other means of egress shall comply with Section
1025.6.1 where smoke-protected seating is not provided and
with Section 1025.6.2 or 1025.6.3 where smoke-protected seating
is provided. The clear width shall be measured to walls, edges
of seating and tread edges except for permitted projections.
1025.6.1 Without smoke protection. The clear width of
the means of egress shall provide suffIcient capacity in
accordance with all of the following, as applicable:
1. At least 0.3 inch (7.6 mm) of width for each occupant
served shall be provided on stairs having riser heights
7 inches (178 mm) or less and tread depths 11 inches (279
mm) or greater, measured horizontally between tread nosings.
2.
At least 0.005 inch (0.127 mm) of additional stair width
for each occupant shall be provided for each 0.10 inch
(2.5 mm) of riser height above 7 inches (178 mm).
3. Where egress requires stair descent, at least 0.075
inch (1.9 mm) of additional width for each occupant shall
be provided on those portions of stair width having no
handrail within a horizontal distance of 30 inches (762
mm).
4. Ramped means of egress, where slopes are steeper
than one unit vertical in 12 units horizontal (8-percent
slope), shall have at least 0.22 inch (5.6 mm) of clear
width for each occupant served. Level or ramped means
of egress, where slopes are not steeper than one unit
vertical in 12 units horizontal (8-percent slope), shall
have at least 0.20 inch (5.1 mm) of clear width for each
occupant served.
1025.6.2 Smoke-protected seating. The clear width of
the means of egress for smoke-protected assembly seating
shall not be less than the occupant load served by the egress
element multiplied by the appropriate factor in Table
1025.6.2. The total number of seats specified shall
be those within the space exposed to the same smoke-protected
environment. Interpolation is permitted between the specific
values shown. A life safety evaluation, complying with NFPA
101, shall be done for a facility utilizing the reduced
width requirements of Table
1025.6.2 for smoke-protected assembly seating.
Exception: For an outdoor
smoke-protected assembly with an occupant load not greater
than 18,000, the clear width shall be determined using the
factors in Section 1025.6.3.
1025.6.2.1 Smoke control.
Means of egress serving a smoke-protected assembly seating
area shall be provided with a smoke control system complying
with Section 909 or natural ventilation
designed to maintain the smoke level at least 6 feet (1829
mm) above the floor of the means of egress.
1025.6.2.2 Roof height.
A smoke-protected assembly seating area with a roof shall
have the lowest portion of the roof deck not less
than 15 feet (4572 mm) above the highest aisle or aisle
accessway.
Exception: A roof canopy in an outdoor stadium shall be
permitted to be less than 15 feet (4572 mm) above the highest
aisle or aisle accessway provided that there are no objects
less than 80 inches (2032 mm) above the highest aisle or aisle
access way.
1025.6.2.3 Automatic sprinklers. Enclosed areas
with walls and ceilings in buildings or structures containing
smoke-protected assembly seating shall be protected with
an approved automatic sprinkler system in accordance with
Section 903.3.1.1.
Exceptions:
1. The floor area used for contests, performances or entertainment
provided the roof construction is more than 50 feet (15
240 mm) above the floor level and the use is restricted
to low fire hazard uses.
2. Press boxes and storage facilities less than 1,000
square feet (93 m2) in area.
3. Outdoor seating facilities where seating and the means
of egress in the seating area are essentially open to
the outside.
1025.6.3 Width of means of egress for outdoor smoke-protected
assembly. The clear width in inches (mm) of aisles and
other means of egress shall be not less than the total occupant
load served by the egress element multiplied by 0.08 (2.0
mm) where egress is by aisles and stairs and multiplied
by 0.06 (1.52 mm) where egress is by ramps, corridors, tunnels
or vomitories.
Exception: The clear width in inches (mm) of aisles and
other means of egress shall be permitted to comply with Section
1025.6.2 for the number of seats in the outdoor smoke-protected
assembly where Section 1025.6.2 permits less width.
1025.7
Travel distance. Exits and aisles shall be so located
that the travel distance to an exit door shall not be greater
than 200 feet (60 960 mm) measured along the line of travel
in non sprinkle red buildings. Travel distance shall not be
more than 250 feet (76 200 mm) in sprinkle red buildings.
Where aisles are provided for seating, the distance shall
be measured along the aisles and aisle accessway without travel
over or on the seats.
Exceptions:
1. Smoke-protected assembly seating: The travel distance
from each seat to the nearest entrance to a vomitory or
concourse shall not exceed 200 feet (60 960 mm). The travel
distance from the entrance to the vomitory or concourse
to a stair, ramp or walk on the exterior of the building
shall not exceed 200 feet (60 960 mm).
2. Open-air seating: The travel distance from each seat
to the building exterior shall not exceed 400 feet (122
m). The travel distance shall not be limited in facilities
of Type I or II construction.
1025.8
Common path of travel. The common path of egress travel
shall not exceed 30 feet (9144 mm) from any seat to a point
where an occupant has a choice of two paths of egress travel
to two exits.
Exceptions:
1. For areas serving less than 50 occupants, the
common path of egress travel shall not exceed 75 feet
(22 860 mm).
2. For smoke-protected assembly seating, the common
path of egress travel shall not exceed 50 feet (15240
mm).
1025.8.1 Path through adjacent row. Where one of the
two paths of travel is across the aisle through a row of
seats to another aisle, there shall be not more than 24
seats between the two aisles, and the minimum clear width
between rows for the row between the two aisles shall be
12 inches (305 mm) plus 0.6 inch (15.2 mm) for each additional
seat above seven in the row between aisles.
Exception:
For smoke-protected assembly seating there shall not be more
than 40 seats between the two aisles and the minimum clear
width shall be 12 inches (305 mm) plus 0.3 inch (7.6 mm) for
each additional seat.
1025.9
Assembly aisles are required. Every occupied portion of
any occupancy in Group A that contains seats, tables, displays,
similar fixtures or equipment shall be provided with aisles
leading to exits or exit access doorways in accordance with
this section. Aisle accessways for tables and seating shall
comply with Section 1014.4.3.
1025.9.1 Minimum aisle width. The minimum clear width
for aisles shall be as shown:
1. Forty-eight inches (1219 mm) for aisle stairs having
seating on each side .
Exception:
Thirty-six inches (914 mm) where the aisle serves less
than 50 seats.
2.
Thirty-six inches (914 mm) for aisle stairs having seating
on only one side.
3. Twenty-three
inches (584 mm) between an aisle stair handrail or guard
and seating where the aisle is subdivided by a handrail.
4.
Forty-two inches (1067 mm) for level or ramped aisles
having seating on both sides.
Exceptions:
1. Thirty-six
inches (914 mm) where the aisle serves less that 50
seats.
2. Thirty
inches (762 mm) where the aisle does not serve more
than 14 seats.
5. Thirty-six
inches (914 mm) for level or ramped aisles having seating
on only one side.
Exceptions:
1.
Thirty inches (762 mm) where the aisle does not serve
more than 14 seats.
2.
Twenty-three inches (584 mm) between an aisle stair
handrail and seating where an aisle does not serve more
than five rows on one side.
1025.9.2 Aisle width.
The aisle width shall provide sufficient egress capacity
for the number of persons accommodated by the catchment
area served by the aisle. The catchment area served by an
aisle is that portion of the total space that is served
by that section of the aisle. In establishing catchment
areas, the assumption shall be made that there is a balanced
use of all means of egress, with the number of persons in
proportion to egress capacity.
1025.9.3
Converging aisles. Where aisles converge to form a single
path of egress travel, the required egress capacity of that
path shall not be less than the combined required capacity
of the converging aisles.
1025.9.4
Uniform width. Those portions of aisles, where egress
is possible in either of two directions, shall be uniform
in required width.
1025.9.5
Assembly aisle termination. Each end of an aisle shall
terminate at cross aisle, foyer, doorway, vomitory or concourse
having access to an exit.
Exceptions:
1. Dead-end aisles shall not be greater than 20 feet (6096
mm) in length.
2. Dead-end aisles longer than 20 feet (6096 mm)
are permitted where seats beyond the 20-foot (6096 mm)
dead-end aisle are no more than 24 seats from another
aisle, measured along a row of seats having a minimum
clear width of 12 inches (305 mm) plus 0.6 inch (15.2
mm) for each additional seat above seven in the row.
3. For smoke-protected assembly seating, the dead-end
aisle length of vertical aisles shall not exceed a distance
of 21 rows.
4. For smoke-protected assembly seating, a longer
dead-end aisle is permitted where seats beyond the 21-row
dead-end aisle are not more than 40 seats from another
aisle, measured along a row of seats having an aisle accessway
with a minimum clear width of 12 inches (305 mm) plus
0.3 inch (7.6 mm) for each additional seat above seven
in the row.
1025.9.6
Assembly aisle obstructions. There shall be no obstructions
in the required width of aisles except for handrails as
provided in Section 1025.13.
1025.10
Clear width of aisle accessways serving seating. Where
seating rows have 14 or fewer seats, the minimum clear aisle
accessway width shall not be less than 12 inches (305 mm)
measured as the clear horizontal distance from the back of
the row ahead and the nearest projection of the row behind.
Where chairs have automatic or self-rising seats, the measurement
shall be made with seats in the raised position. Where any
chair in the row does not have an automatic or self-rising
seat, the measurements shall be made with the seat in the
down position. For seats with folding tablet arms, row spacing
shall be determined with the tablet arm down.
1025.10.1 Dual access. For rows of seating served by
aisles or doorways at both ends, there shall not be more
than 100 seats per row. The minimum clear width of 12 inches
(305 mm) between rows shall be increased by 0.3 inch (7.6
mm) for every additional seat beyond 14 seats, but the minimum
clear width is not required to exceed 22 inches (559 mm).
Exception: For smoke-protected assembly seating, the row
length limits for a 12-inch-wide (305 mm) aisle accessway,
beyond which the aisle accessway minimum clear width shall
be increased, are in Table 1025.10.1.
1025.10.2
Single access. For rows of seating served by an aisle
or doorway at only one end of the row, the minimum clear
width of 12 inches (305 mm) between rows shall be increased
by 0.6 inch (15.2 mm) for every additional seat beyond seven
seats, but the minimum clear width is not required to exceed
22 inches (559 mm).
Exception: For smoke-protected assembly seating, the row
length limits for a 12-inch-wide (305 mm) aisle accessway,
beyond which the aisle accessway minimum clear width shall
be increased, are in Table 1025.10.1.
1025.11
Assembly aisle walking surfaces. Aisles with a slope not
exceeding one unit vertical in eight units horizontal (12.5-percent
slope) shall consist of a ramp having a slip-resistant walking
surface. Aisles with a slope exceeding one unit vertical in
eight units horizontal (12.5-percent slope) shall consist
of a series of risers and treads that extends across the full
width of aisles and complies with Sections 1025.11.1 through
1025.11.3.
1025.11.1
Treads. Tread depths shall be a minimum of 11 inches
(279 mm) and shall have dimensional uniformity.
Exception: The tolerance between adjacent treads shall
not exceed 0.188 inch (4.8 mm).
1025.11.2 Risers. Where the gradient of aisle stairs
is to be the same as the gradient of adjoining seating areas,
the riser height shall not be less than 4 inches (102 mm)
nor more than 8 inches (203 mm) and shall be uniform within
each flight.
Exceptions:
1. Riser height non uniformity shall be limited to the
extent necessitated by changes in the gradient of the
adjoining seating area to maintain adequate sightlines.
Where non uniformities exceed 0.188 inch (4.8 mm) between
adjacent risers, the exact location of such non uniformities
shall be indicated with a distinctive marking stripe on
each tread at the nosing or leading edge adjacent to the
non uniform risers. Such stripe shall be a minimum of
1 inch (25 mm), and a maximum of 2 inches (51 mm), wide.
The edge marking stripe shall be distinctively different
from the contrasting marking stripe.
2. Riser heights not exceeding 9 inches (229 mm) shall
be permitted where they are necessitated by the slope
of the adjacent seating areas to maintain sightlines.
1025.11.3 Tread contrasting marking stripe. A contrasting
marking stripe shall be provided on each tread at the nosing
or leading edge such that the location of each tread is
readily apparent when viewed in descent. Such stripe shall
be a minimum of 1 inch (25 mm), and a maximum of 2 inches
(51 mm), wide.
Exception:
The contrasting marking stripe is permitted to be omitted
where tread surfaces are such that the location of each tread
is readily apparent when viewed in descent.
1025.12
Seat stability. In places of assembly, the seats shall
be securely fastened to the floor.
Exceptions:
1. In
places of assembly or portions thereof without ramped or
tiered floors for seating and with 200 or fewer seats, the
seats shall not be required to be fastened to the floor.
2. In
places of assembly or portions thereof with seating at tables
and without ramped or tiered floors for seating, the seats
shall not be required to be fastened to the floor.
3. In places of assembly or
portions thereof without ramped or tiered floors for seating
and with greater than 200 seats, the seats shall be fastened
together in groups of not less than three or the seats shall
be securely fastened to the floor.
4.
In places of assembly where flexibility of the seating arrangement
is an integral part of the design and function of the space
and seating is on tiered levels, a maximum of 200 seats
shall not be required to be fastened to the floor. Plans
showing seating, tiers and aisles shall be submitted for
approval.
5.
Groups of seats within a place of assembly separated from
other seating by railings, guards, partial height walls
or similar barriers with level floors and having no more
than 14 seats per group shall not be required to be fastened
to the floor.
6.
Seats intended for musicians or other performers and separated
by railings, guards, partial height walls or similar barriers
shall not be required to be fastened to the floor.
1025.13
Handrails. Ramped aisles having a slope exceeding one
unit vertical in 15 units horizontal (6.7-percent slope) and
aisle stairs shall be provided with handrails located either
at the side or within the aisle width.
Exceptions:
1.Handrails
are not required for ramped aisles having a gradient no
greater than one unit vertical in eight units horizontal
(12.5-percent slope) and seating on both sides.
2. Handrails
are not required if, at the side of the aisle, there is
a guard that complies with the grasp ability requirements
of handrails.
1025.13.1 Discontinuous handrails. Where there is seating
on both sides of the aisle, the handrails shall be discontinuous
with gaps or breaks at intervals not exceeding five rows
to facilitate access to seating and to permit crossing from
one side of the aisle to the other. These gaps or breaks
shall have a clear width of at least 22 inches (559 mm)
and not greater than 36 inches (914 mm), measured horizontally,
and the handrail shall have rounded terminations or bends.
1025.13.2
Intermediate handrails. Where handrails are provided
in the middle of aisle stairs, there shall be an additional
intermediate handrail located approximately 12 inches (305
mm) below the main handrail.
1025.14
Assembly guards. Assembly guards shall comply with Sections
1025.14.1 through 1025.14.3.
1025.14.1 Cross aisles. Cross aisles located more than
30 inches (762 mm) above the floor or grade below shall
have guards in accordance with Section
1013.
Where
an elevation change of 30 inches (762 mm) or less occurs
between a cross aisle and the adjacent floor or grade below,
guards not less than 26 inches (660 mm) above the aisle
floor shall be provided.
Exception: Where
the backs of seats on the front of the cross aisle project
24 inches (610 mm) or more above the adjacent floor of the
aisle, a guard need not be provided.
1025.14.2 Sightline constrained guard heights. Unless
subject to the requirements of Section 1025.14.3, a fascia
or railing system in accordance with the guard requirements
of Section 1013 and having a minimum
height of 26 inches (660 mm) shall be provided where the
floor or footboard elevation is more than 30 inches (762
mm) above the floor or grade below and the fascia or railing
would otherwise interfere with the sightlines of immediately
adjacent seating. At bleachers, a guard must be provided
where the floor or footboard elevation is more than 24
inches (610 mm) above the floor or grade below and the fascia
or railing would otherwise interfere with the sightlines
of the immediately adjacent seating.
1025.14.3 Guards at the end of aisles. A fascia or railing
system complying with the guard requirements of
Section 1013 shall be provided for the full width of
the aisle where the foot of the aisle is more than 30 inches
(762 mm) above the floor or grade below. The fascia or railing
shall be a minimum of 36 inches (914 mm) high and shall
provide a minimum 42 inches (1067 mm) measured diagonally
between the top of the rail and the nosing of the nearest
tread.
1025.15
Bench seating. Where bench seating is used, the number
of persons shall be based on one person for each 18 inches
(457 mm) of length of the bench.
|