| SECTION 1607 LIVE LOADS
1607.11.2
Reduction in roof live loads. The minimum uniformly distributed
roof live loads, Lo in Table
1607.1 are permitted to be reduced according to the following
provisions.
1607.11.2.1
Flat, pitched and curved roofs. Ordinary flat, pitched
and curved roofs are permitted to be designed for a reduced
roof live load as specified in the following equation or
other controlling combinations of loads in Section
1605, whichever produces the greater load. In structures
where special scaffolding is used as a work surface for
workers and materials during maintenance and repair operations,
a lower roof load than specified in the following equation
shall not be used unless approved by the building official.
Greenhouses shall be designed for a minimum roof live load
of 12 psf (0.58 kN/m2).
Lr = LoR1R2
(Equation 16-27)
where:
12 ≤ Lr ≤ 20
For
SI: Lr = Lo R1R2
where:
0.58 ≤ Lr ≤ 0.96
Lr
= Reduced live load per square foot (m2) of
horizontal projection in pounds per square foot (kN/m2).
The reduction factors R1 and R2 shall be determined
as follows:
R1 =
1 for At ≤ 200 square feet (18.58m2)
(Equation 16-28)
R1 =
1.2 0.001At for 200 square feet <At
< 600 square feet (Equation 16-29)
For SI: 1.2 0.011At
for 18.58 square meters < At < 55.74
square meters
R1 = 0.6 for At >
600 square feet (55.74m2)
(Equation 16-30)
where:
At
= Tributary area (span length multiplied by effective
width) in square feet (m2) supported by any
structural member,
and
R2
= 1 for F≤ 4 (Equation 16-31)
R2
= 1.2 0.05 F for 4 < F< 12 (Equation 16-32)
R2
= 0.6 for F > 12 (Equation 16-33)
where:
F
= For a sloped roof, the number of inches of rise
per foot (for SI: F = 0.12 × slope, with slope expressed
as a percentage), or for an arch or dome, the rise-to-span
ratio multiplied by 32.
1607.11.2.2 Special-purpose roofs. Roofs used for promenade
purposes, roof gardens, assembly purposes or other special
purposes shall be designed for a minimum live load as required
in Table 1607.1. Such roof
live loads are permitted to be reduced in accordance with
1607.9.
1607.11.2.3 Landscaped roofs. Where roofs are to be
landscaped, the uniform design live load in the landscaped
area shall be 20 psf (0.958 kN/m2). The weight
of the landscaping materials shall be considered as dead
load and shall be computed on the basis of saturation of
the soil.
1607.11.2.4 Awnings and canopies. Awnings and canopies
shall be designed for uniform live loads as required in
Table 1607.1 as well as for
snow loads and wind loads as specified in Sections
1608 and 1609.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|