| SECTION 1707 SPECIAL INSPECTIONS
FOR SEISMIC RESISTANCE
1707.1 Special inspections
for seismic resistance. Special inspections itemized in
Sections 1707.2 through 1707.10, unless exempted by the exceptions
of Section 1704.1, are required for
the following:
1. The seismic-force-resisting
systems in structures assigned to Seismic Design Category
C, D, E or F, as determined in Section
1613.
2. Designated seismic systems
in structures assigned to Seismic Design Category D, E or
F.
3. Architectural, mechanical
and electrical components in structures assigned to Seismic
Design Category C, D, E or F that are required in Sections
1707.7 and 1707.8.
1707.2 Structural steel.
Continuous special inspection is required for structural welding
in accordance with AISC 341. Exceptions:
1. Single-pass fillet welds
not exceeding 5/16 inch (7.9 mm) in
size.
2. Floor and roof deck welding.
1707.3 Structural wood.
Continuous special inspection is required during field gluing
operations of elements of the seismic- force-resisting system.
Periodic special inspection is required for nailing, bolting,
anchoring and other fastening of components within the seismic-force-resisting
system, including wood shear walls, wood diaphragms, drag
struts, braces, shear panels and hold-downs.
Exception: Special inspection
is not required for wood shear walls, shear panels and diaphragms,
including nailing, bolting, anchoring and other fastening
to other components of the seismic-force-resisting system,
where the fastener spacing of the sheathing is more than 4
inches (102 mm) on center (o.c.).
1707.4 Cold-formed steel framing.
Periodic special inspections is required during welding operations
of elements of the seismic-force-resisting system. Periodic
special inspection is required for screw attachment, bolting,
anchoring and other fastening of components within the seismic-force-resisting
system, including struts, braces, and hold-downs.
1707.5 Pier foundations.
Special inspection is required for pier foundations for buildings
assigned to Seismic Design Category C, D, E or F in accordance
with Section 1613. Periodic special
inspection is required during placement of reinforcement and
continuous special inspection is required during placement
of the concrete.
1707.6 Storage racks and access
floors. Periodic special inspection is required during
the anchorage of access floors and storage racks 8 feet (2438
mm) or greater in height in structures assigned to Seismic
Design Category D, E or F.
1707.7 Architectural components.
Periodic special inspection is required during the erection
and fastening of exterior cladding, interior and exterior
nonbearing walls and interior and exterior veneer in structures
assigned to Seismic Design Category D, E or F.
Exceptions:
1. Special inspection is not
required for architectural components in structures 30 feet
(9144 mm) or less in height.
2. Special inspection is not
required for cladding and veneer weighing 5 psf (24.5 N/m2)
or less.
3. Special inspection is not
required for interior nonbearing walls weighing 15 psf (73.5
N/m2) or less.
1707.8 Mechanical and electrical
components. Special inspection for mechanical and electrical
equipment shall be as follows:
1. Periodic special inspection
is required during the anchorage of electrical equipment
for emergency or standby power systems in structures assigned
to Seismic Design Category C, D, E or F;
2. Periodic special inspection
is required during the installation of anchorage of other
electrical equipment in structures assigned to Seismic Design
Category E or F;
3. Periodic special inspection
is required during installation of piping systems intended
to carry flammable, combustible or highly toxic contents
and their associated mechanical units in structures assigned
to Seismic Design Category C, D, E or F;
4. Periodic special inspection
is required during the installation of HVAC ductwork that
will contain hazardous materials in structures assigned
to Seismic Design Category C, D, E or F; and
5. Periodic special inspection
is required during the installation of vibration isolation
systems in structures assigned to Seismic Design Category
C, D, E or F where the construction documents require a
nominal clearance of 0.25 inches (6.4 mm) or less between
the equipment support frame and restraint.
1707.9 Designated seismic
system verifications. The special inspector shall examine
designated seismic systems requiring seismic qualification
in accordance with Section 1708.5
and verify that the label, anchorage or mounting conforms
to the certificate of compliance.
1707.10 Seismic isolation
system. Periodic special inspection is required during
the fabrication and installation of isolator units and energy
dissipation devices that are part of the seismic isolation
system.
|