| SECTION 1805 FOOTINGS AND
FOUNDATIONS
1805.5 Foundation walls.
Concrete and masonry foundation walls shall be designed in
accordance with Chapter 19 or 21, respectively. Foundation
walls that are laterally supported at the top and bottom and
within the parameters of Tables
1805.5(1) through 1805.5(5)
are permitted to be designed and constructed in accordance
with Sections 1805.5.1 through 1805.5.5.
1805.5.1 Foundation wall
thickness. The minimum thickness of concrete and masonry
foundation walls shall comply with Sections 1805.5.1.1 through
1805.5.1.3.
1805.5.1.1 Thickness at
top of foundation wall. The thickness of foundation
walls shall not be less than the thickness of the wall
supported, except that foundation walls of at least 8-inch
(203 mm) nominal width are permitted to support brick-veneered
frame walls and 10-inch-wide (254 mm) cavity walls provided
the requirements of Section 1805.5.1.2 are met. Corbeling
of masonry shall be in accordance with Section
2104.2. Where an 8-inch (203 mm) wall is corbeled,
the top corbel shall not extend higher than the bottom
of the floor framing and shall be a full course of headers
at least 6 inches (152 mm) in length or the top course
bed joint shall be tied to the vertical wall projection.
The tie shall be W2.8 (4.8 mm) and spaced at a maximum
horizontal distance of 36 inches (914 mm); the hollow
space behind the corbelled masonry shall be filled with
mortar or grout.
1805.5.1.2 Thickness based
on soil loads, unbalanced backfill height and wall height.
The thickness of foundation walls shall comply with
the requirements of Table
1805.5(5) for concrete walls, Table
1805.5(1) for plain masonry walls or Table
1805.5(2), 1805.5(3)
or 1805.5(4) for masonry
walls with reinforcement. When using the tables, masonry
shall be laid in running bond and the mortar shall be
Type M or S. Unbalanced backfill height is the difference
in height between the exterior finish ground level and
the lower of the top of the concrete footing that supports
the foundation wall or the interior finish ground level.
Where an interior concrete slab on grade is provided and
is in contact with the interior surface of the foundation
wall, the unbalanced backfill height is permitted to be
measured from the exterior finish ground level to the
top of the interior concrete slab.
1805.5.1.3 Rubble stone.
Foundation walls of rough or random rubble stone shall
not be less than 16 inches (406 mm) thick. Rubble stone
shall not be used for foundations for structures in Seismic
Design Category C, D, E or F.
1805.5.2 Foundation wall
materials. Concrete foundation walls constructed in
accordance with Table 1805.5(5)
shall comply with Section 1805.5.2.1. Masonry foundation
walls constructed in accordance with Table
1805.5(1), 1805.5(2),
1805.5(3) or 1805.5(4)
shall comply with Section 1805.5.2.2.
1805.5.2.1 Concrete foundation
walls. Concrete foundation walls shall comply with
the following:
1. The size and spacing
of vertical reinforcement shown in Table
1805.5(5) is based on the use of reinforcement with
a minimum yield strength of 60,000 psi (414 MPa). Vertical
reinforcement with a minimum yield strength of 40,000
psi (276 MPa) or 50,000 psi (345 MPa) is permitted,
provided the same size bar is used and the spacing shown
in the table is reduced by multiplying the spacing by
0.67 or 0.83, respectively.
2. Vertical reinforcement,
when required, shall be placed nearest the inside face
of the wall a distance, d, from the outside face (soil
side) of the wall. The distance, d, is equal to the
wall thickness, t, minus 1.25 inches (32 mm) plus one-half
the bar diameter, db [d = t (1.25
+ db/2)]. The reinforcement shall be placed
within a tolerance of ± 3/8 inch
(9.5 mm) where d is less than or equal to 8 inches (203
mm) or ±1/2 inch (2.7 mm) where
d is greater than 8 inches (203 mm).
3. In lieu of the reinforcement
shown in Table 1805.5(5),
smaller reinforcing bar sizes with closer spacings that
provide an equivalent cross-sectional area of reinforcement
per unit length of wall are permitted.
4. Concrete cover for reinforcement
measured from the inside face of the wall shall not
be less than 3/4 inch (19.1 mm).
Concrete cover for reinforcement measured from the outside
face of the wall shall not be less than 1.5 inches (38
mm) for No. 5 bars and smaller and not less than 2 inches
(51 mm) for larger bars.
5. Concrete shall have
a specified compressive strength, fc , of
not less than 2,500 psi (17.2 MPa) at 28 days.
6. The unfactored axial
load per linear foot of wall shall not exceed 1.2 tfc
, where t is the specified wall thickness in
inches.
1805.5.2.2 Masonry foundation
walls. Masonry foundation walls shall comply with
the following:
1. Vertical reinforcement
shall have a minimum yield strength of 60,000 psi (414
MPa).
2. The specified location
of the reinforcement shall equal or exceed the effective
depth distance, d, noted in Tables
1805.5(2), 1805.5(3)
and 1805.5(4) and
shall be measured from the face of the exterior (soil)
side of the wall to the center of the vertical reinforcement.
The reinforcement shall be placed within the tolerances
specified in ACI 530.1/ASCE 6/TMS 402, Article 3.4 B7
of the specified location.
3. Grout shall comply with
Section 2103.12.
4. Concrete masonry units
shall comply with ASTM C 90.
5. Clay masonry units shall
comply with ASTM C 652 for hollow brick, except compliance
with ASTM C 62 or ASTM C 216 is permitted when solid
masonry units are installed in accordance with Table
1805.5(1) for plain masonry.
6. Masonry units shall
be installed with Type M or S mortar in accordance with
Section 2103.8.
7. The unfactored axial
load per linear foot of wall shall not exceed 1.2 tf
m where t is the specified well thickness in inches
and f m is the specified compressive strength of masonry
in pounds per square inch.
1805.5.3 Alternative foundation
wall reinforcement. In lieu of the reinforcement provisions
for masonry foundation walls in Table
1805.5(2), 1805.5(3)
or 1805.5(4), alternative
reinforcing bar sizes and spacings having an equivalent
cross-sectional area of reinforcement per linear foot (mm)
of wall are permitted to be used, provided the spacing of
reinforcement does not exceed 72 inches (1829 mm) and reinforcing
bar sizes do not exceed No. 11.
1805.5.4 Hollow masonry
walls. At least 4 inches (102 mm) of solid masonry shall
be provided at girder supports at the top of hollow masonry
unit foundation walls.
1805.5.5 Seismic requirements.
Tables 1805.5(1) through
1805.5(5) shall be subject
to the following limitations in Sections 1805.5.5.1 and
1805.5.5.2 based on the seismic design category assigned
to the structure as defined in Section
1613.
1805.5.5.1 Seismic requirements
for concrete foundation walls. Concrete foundation
walls designed using Table 1805.5(5) shall be subject
to the following limitations:
1. Seismic Design Categories
A and B. No additional seismic requirements, except
provide not less than two No. 5 bars around window and
door openings. Such bars shall extend at least 24 inches
(610 mm) beyond the corners of the openings.
2. Seismic Design Categories
C, D, E and F. Tables shall not be used except as allowed
for plain concrete members in
Section 1908.1.15.
1805.5.5.2 Seismic requirements
for masonry foundation walls. Masonry foundation walls
designed using Tables 1805.5(1)
through 1805.5(4) shall
be subject to the following limitations:
1. Seismic Design Categories
A and B. No additional seismic requirements.
2. Seismic Design Category
C. A design using Tables
1805.5(1) through 1805.5(4)
is subject to the seismic requirements of Section
2106.4.
3. Seismic Design Category
D. A design using Tables
1805.2(2) through 1805.5(4)
is subject to the seismic requirements of Section
2106.5.
4. Seismic Design Categories
E and F. A design using Tables
1805.2(2) through 1805.5(4)
is subject to the seismic requirements of Section
2106.6.
1805.5.6 Foundation wall
drainage. Foundation walls shall be designed to support
the weight of the full hydrostatic pressure of undrained
backfill unless a drainage system is installed in accordance
with Sections 1807.4.2 and 1807.4.3.
1805.5.7 Pier and curtain
wall foundations. Except in Seismic Design Categories
D, E and F, pier and curtain wall foundations are permitted
to be used to support light-frame construction not more
than two stories in height, provided the following requirements
are met:
1. All load-bearing walls
shall be placed on continuous concrete footings bonded
integrally with the exterior wall footings.
2. The minimum actual thickness
of a load-bearing masonry wall shall not be less than
4 inches (102 mm) nominal or 3.625 inches (92 mm) actual
thickness, and shall be bonded integrally with piers spaced
6 feet (1829 mm) on center (o.c.).
3. Piers shall be constructed
in accordance with Chapter 21 and the following:
3.1. The unsupported height
of the masonry piers shall not exceed 10 times their
least dimension.
3.2. Where structural clay
tile or hollow concrete masonry units are used for piers
supporting beams and girders, the cellular spaces shall
be filled solidly with concrete or Type M or S mortar.
Exception: Unfilled hollow
piers are permitted where the unsupported height of the pier
is not more than four times its least dimension. 3.3. Hollow
piers shall be capped with 4 inches (102 mm) of solid masonry
or concrete or the cavities of the top course shall be filled
with concrete or grout.
4. The maximum height of
a 4-inch (102 mm) load-bearing masonry foundation wall
supporting wood frame walls and floors shall not be more
than 4 feet (1219 mm) in height.
5. The unbalanced fill for
4-inch (102 mm) foundation walls shall not exceed 24 inches
(610 mm) for solid masonry, nor 12 inches (305 mm) for
hollow masonry.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|