SECTION 2110 GLASS UNIT MASONRY
2110.1 Scope. This section
covers the empirical requirements for nonload-bearing glass
unit masonry elements in exterior or interior walls.
2110.1.1 Limitations. Solid
or hollow approved glass block shall not be used in fire
walls, party walls, fire barriers or fire partitions, or
for load-bearing construction. Such blocks shall be erected
with mortar and reinforcement in metal channel- type frames,
structural frames, masonry or concrete recesses, embedded
panel anchors as provided for both exterior and interior
walls or other approved joint materials. Wood strip framing
shall not be used in walls required to have a fire-resistance
rating by other provisions of this code.
Exceptions:
1.Glass-block assemblies having
a fire protection rating of not less than 3/4
hour shall be permitted as opening protectives in accordance
with Section 715 in fire barriers
and fire partitions that have a required fire-resistance
rating of 1 hour or less and do not enclose exit stairways
or exit passageways.
2.Glass-block assemblies as
permitted in Section 404.5, Exception
2.
2110.2 Units. Hollow or
solid glass-block units shall be standard or thin units.
2110.2.1 Standard units.
The specified thickness of standard units shall be at least
3 7/8 inches (98 mm).
2110.2.2 Thin units.
The specified thickness of thin units shall be 3 1/8
inches (79 mm) for hollow units or 3 inches (76 mm) for
solid units.
2110.3 Panel size.
2110.3.1 Exterior standard-unit
panels. The maximum area of each individual exterior
standard-unit panel shall be 144 square feet (13.4 m2)
when the design wind pressure is 20 psf (958 N/m2).
The maximum panel dimension between structural supports
shall be 25 feet (7620 mm) in width or 20 feet (6096 mm)
in height. The panel areas are permitted to be adjusted
in accordance with Figure
2110.3.1 for other wind pressures.
2110.3.2 Exterior thin-unit
panels. The maximum area of each individual exterior
thin-unit panel shall be 85 square feet (7.9 m2).
The maximum dimension between structural supports shall
be 15 feet (4572 mm) in width or 10 feet (3048 mm) in height.
Thin units shall not be used in applications where the design
wind pressure exceeds 20 psf (958 N/m2).
2110.3.3 Interior panels.
The maximum area of each individual standard-unit panel
shall be 250 square feet (23.2 m2). The maximum
area of each thin-unit panel shall be 150 square feet (13.9
m2). The maximum dimension between structural
supports shall be 25 feet (7620 mm) in width or 20 feet
(6096 mm) in height.
2110.3.4 Solid units.
The maximum area of solid glass-block wall panels in both
exterior and interior walls shall not be more than 100 square
feet (9.3 m2).
2110.3.5 Curved panels.
The width of curved panels shall conform to the requirements
of Sections 2110.3.1, 2110.3.2 and 2110.3.3, except additional
structural supports shall be provided at locations where
a curved section joins a straight section, and at inflection
points in multicurved walls.
2110.4 Support.
2110.4.1 General requirements.
Glass unit masonry panels shall be isolated so that in-plane
loads are not imparted to the panel.
2110.4.2 Vertical. Maximum
total deflection of structural members supporting glass
unitmasonry shall not exceed l/600.
2110.4.2.1 Support on wood
construction. Glass unit masonry having an installed
weight of 40 psf (195 kg/m2) or less and a maximum
height of 12 feet (3658 mm) shall be permitted to be supported
on wood construction.
2110.4.2.2 Expansion joint.
A vertical expansion joint in glass unit masonry shall be
provided to isolate the glass unit masonry supported by
wood construction from that supported by other types
of construction.
2110.4.3 Lateral. Glass
unit masonry panels more than one unit wide or one unit
high shall be laterally supported along their tops and sides.
Lateral support shall be provided by panel anchors along
the top and sides spaced not more than 16 inches (406 mm)
o.c. or by channel-type restraints. Glass unit masonry panels
shall be recessed at least 1 inch (25 mm) within channels
and chases. Channel-type restraints shall be oversized to
accommodate expansion material in the opening and packing
and sealant between the framing restraints and the glass
unit masonry perimeter units. Lateral supports for glass
unit masonry panels shall be designed to resist applied
loads, or a minimum of 200 pounds per lineal feet (plf)
(2919 N/m) of panel, whichever is greater.
Exceptions:
1.Lateral support at the top
of glass unit masonry panels that are no more than one unit
wide shall not be required.
2.Lateral support at the sides
of glass unit masonry panels that are no more than one unit
high shall not be required.
2110.4.3.1 Single unit
panels. Single unit glass unit masonry panels shall
conform to the requirements of Section 2110.4.3, except
lateral support shall not be provided by panel anchors.
2110.5 Expansion joints.
Glass unit masonry panels shall be provided with expansion
joints along the top and sides at structural supports. Expansion
joints shall have sufficient thickness to accommodate displacements
of the supporting structure, but shall not be less than 3/8
inch (9.5 mm) in thickness. Expansion joints shall be entirely
free of mortar or other debris and shall be filled with resilient
material. The sills of glass-block panels shall be coated
with approved water-based asphaltic emulsion, or other elastic
waterproofing material, prior to laying the first mortar course.
2110.6 Mortar. Mortar
for glass unit masonry shall comply with Section
2103.8.
2110.7 Reinforcement. Glass
unit masonry panels shall have horizontal joint reinforcement
spaced not more than 16 inches (406 mm) on center, located
in the mortar bed joint, and extending the entire length of
the panel but not across expansion joints. Longitudinal wires
shall be lapped a minimum of 6 inches (152 mm) at splices.
Joint reinforcement shall be placed in the bed joint immediately
below and above openings in the panel. The reinforcement shall
have not less than two parallel longitudinal wires of size
W1.7 (MW11), and have welded cross wires of size W1.7 (MW11).
|