2308.8.1 Bearing. Except
where supported on a 1-inch by 4-inch (25.4 mm by 102 mm)
ribbon strip and nailed to the adjoining stud, the ends
of each joist shall not have less than 11/2
inches (38 mm) of bearing on wood or metal, or less than
3 inches (76 mm) on masonry.
2308.8.2 Framing details.
Joists shall be supported laterally at the ends and at each
support by solid blocking except where the ends of the joists
are nailed to a header, band or rim joist or to an adjoining
stud or by other means. Solid blocking shall not be less
than 2 inches (51mm) in thickness and the full depth of
the joist. Notches on the ends of joists shall not exceed
one-fourth the joist depth. Holes bored in joists shall
not be within 2 inches (51 mm) of the top or bottom of the
joist, and the diameter of any such hole shall not exceed
one-third the depth of the joist. Notches in the top or
bottom of joists shall not exceed one-sixth the depth and
shall not be located in the middle third of the span. Joist
framing from opposite sides of a beam, girder or partition
shall be lapped at least 3 inches (76 mm) or the opposing
joists shall be tied together in an approved manner. Joists
framing into the side of a wood girder shall be supported
by framing anchors or on ledger strips not less than 2 inches
by 2 inches (51 mm by 51 mm).
2308.8.2.1 Engineered
wood products. Cuts, notches and holes bored in trusses,
structural composite lumber, structural glue-laminated
members or I-joists are not permitted except where permitted
by the manufacturers recommendations or where the
effects of such alterations are specifically considered
in the design of the member by a registered design professional.
2308.8.3 Framing around
openings. Trimmer and header joists shall be doubled,
or of lumber of equivalent cross section, where the span
of the header exceeds 4 feet (1219 mm). The ends of header
joists more than 6 feet (1829 mm) long shall be supported
by framing anchors or joist hangers unless bearing on a
beam, partition or wall. Tail joists over 12 feet (3658
mm) long shall be supported at the header by framing anchors
or on ledger strips not less than 2 inches by 2 inches (51
mm by 51 mm).
2308.8.4 Supporting bearing
partitions. Bearing partitions parallel to joists shall
be supported on beams, girders, doubled joists, walls or
other bearing partitions. Bearing partitions perpendicular
to joists shall not be offset from supporting girders, walls
or partitions more than the joist depth unless such joists
are of sufficient size to carry the additional load.
2308.8.5 Lateral support.
Floor, attic and roof framing with a nominal depth-to-thickness
ratio greater than or equal to 5:1 shall have one edge held
in line for the entire span. Where the nominal depth-to-thickness
ratio of the framing member exceeds 6:1, there shall be
one line of bridging for each 8 feet (2438 mm) of span,
unless both edges of the member are held in line. The bridging
shall consist of not less than 1-inch by 3-inch (25mmby
76 mm) lumber, double nailed at each end, of equivalent
metal bracing of equal rigidity, full-depth solid blocking
or other approved means. A line of bridging shall also be
required at supports where equivalent lateral support is
not otherwise provided.
2308.8.6 Structural floor
sheathing. Structural floor sheathing shall comply with
the provisions of Section 2304.7.1.
2308.8.7 Under-floor ventilation.
For under-floor ventilation, see Section
1203.3.