[F] 2702.2.1 Group A occupancies.
Emergency power shall be provided for voice communication
systems in Group A occupancies in accordance with Section
907.2.1.2.
[F] 2702.2.2 Smoke control
systems. Standby power shall be provided for smoke
control systems in accordance with Section
909.11.
[F] 2702.2.3 Exit signs.
Emergency power shall be provided for exit signs in accordance
with Section 1011.5.3.
[F] 2702.2.4 Means of
egress illumination. Emergency power shall be provided
for means of egress illumination in accordance with Section
1006.3.
[F] 2702.2.5 Accessible
means of egress elevators. Standby power shall be
provided for elevators that are part of an accessible
means of egress in accordance with
Section 1007.4.
[F] 2702.2.6 Accessible
means of egress platform lifts. Standby power in accordance
with this section or ASME A18.1 shall be provided for
platform lifts that are part of an accessible means of
egress in accordance with Section
1007.5.
[F] 2702.2.7 Horizontal
sliding doors. Standby power shall be provided for
horizontal sliding doors in accordance with Section
1008.1.3.3.
[F] 2702.2.8 Semiconductor
fabrication facilities. Emergency power shall be provided
for semiconductor fabrication facilities in accordance
with Section 415.8.10.
[F] 2702.2.9 Membrane
structures. Standby power shall be provided for auxiliary
inflation systems in accordance with Section
3102.8.2. Emergency power shall be provided for exit
signs in temporary tents and membrane structures in accordance
with the International Fire Code.
[F] 2702.2.10 Hazardous
materials. Emergency or standby power shall be provided
in occupancies with hazardous materials in accordance
with Section 414.5.4.
[F] 2702.2.11 Highly toxic
and toxic materials. Emergency power shall be provided
for occupancies with highly toxic or toxic materials in
accordance with the International Fire Code.
[F] 2702.2.12 Organic
peroxides. Standby power shall be provided for occupancies
with silane gas in accordance with the International Fire
Code.
[F] 2702.2.13 Pyrophoric
materials. Emergency power shall be provided for occupancies
with silane gas in accordance with the International Fire
Code.
[F] 2702.2.14 Covered
mall buildings. Standby power shall be provided for
voice/alarm communication systems in covered mall buildings
in accordance with Section
402.13.
[F] 2702.2.15 High-rise
buildings. Emergency and standby power shall be provided
in high-rise buildings in accordance with Sections
403.10 and 403.11.
[F] 2702.2.16 Underground
buildings. Emergency and standby power shall be provided
in underground buildings in accordance with Sections
405.9 and 405.10.
[F] 2702.2.17Group I-3
occupancies. Emergency power shall be provided for
doors in Group I-3 occupancies in accordance with Section
408.4.2.
[F] 2702.2.18 Airport
traffic control towers. Standby power shall be provided
in airport traffic control towers in accordance with Section
412.1.5.
[F] 2702.2.19 Elevators.
Standby power for elevators shall be provided as set forth
in Section 3003.1.
[F] 2702.2.20 Smoke proof
enclosures. Standby power shall be provided for smoke
proof enclosures as required by Section
909.20.