| [F] SECTION 3311 STANDPIPES
3311.1 Where required.
Buildings four stories or more in height shall be provided
with not less than one standpipe for use during construction.
Such standpipes shall be installed where the progress of construction
is not more than 40 feet (12 192 mm) in height above the lowest
level of fire department access. Such standpipe shall be provided
with fire department hose connections at accessible locations
adjacent to usable stairs. Such standpipes shall be extended
as construction progresses to within one floor of the highest
point of construction having secured decking or flooring.
3311.2 Buildings being demolished.
Where a building is being demolished and a standpipe
exists within such a building, such standpipe shall be maintained
in an operable condition so as to be available for use by
the fire department. Such standpipe shall be demolished with
the building but shall not be demolished more than one floor
below the floor being demolished.
3311.3 Detailed requirements.
Standpipes shall be installed in accordance with the provisions
of Chapter 9.
Exception: Standpipes
shall be either temporary or permanent in nature, and with
or without a water supply, provided that such standpipes conform
to the requirements of Section 905 as
to capacity, outlets and materials.
3311.4 Water supply. Water
supply for fire protection, either temporary or permanent,
shall be made available as soon as combustible material accumulates.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|