|
SECTION
905 STANDPIPE SYSTEMS
[F] 905.1 General. Standpipe
systems shall be provided in new buildings and structures
in accordance with this section. Fire hose threads used in
connection with standpipe systems shall be approved and shall
be compatible with fire department hose threads. The location
of fire department hose connections shall be approved. In
buildings used for high-piled combustible storage, fire protection
shall be in accordance with the International Fire Code.
[F]
905.2 Installation standard. Standpipe systems shall be
installed in accordance with this section and NFPA 14.
[F] 905.3 Required installations.
Standpipe systems shall be installed where required by Sections
905.3.1 through 905.3.7 and in the locations indicated in
Sections 905.4, 905.5 and 905.6. Standpipe systems are allowed
to be combined with automatic sprinkler systems.
Exception: Standpipe systems are not required in Group
R-3 occupancies.
[F] 905.3.1 Building height.
Class III standpipe systems shall be installed throughout
buildings where the floor level of the highest story is
located more than 30 feet (9144 mm) above the lowest level
of fire department vehicle access, or where the floor level
of the lowest story is located more than 30 feet (9144 mm)
below the highest level of fire department vehicle access.
Exceptions:
1.
Class I standpipes are allowed in buildings equipped throughout
with an automatic sprinkler system in accordance with
Section 903.3.1.1 or 903.3.1.2.
2.
Class I manual standpipes are allowed in open parking
garages where the highest floor is located not more than
150 feet (45 720 mm) above the lowest level of fire department
vehicle access.
3.
Class I manual dry standpipes are allowed in open parking
garages that are subject to freezing temperatures, provided
that the hose connections are located as required for
Class II standpipes in accordance with Section 905.5.
4.
Class I standpipes are allowed in basements equipped throughout
with an automatic sprinkler system.
5. In determining the lowest level of fire department
vehicle access, it shall not be required to consider:
5.1.
Recessed loading docks for four vehicles or less; and
5.2.
Conditions where topography makes access from the fire
department vehicle to the building impractical or impossible.
[F]
905.3.2 Group A. Class I automatic wet standpipes shall
be provided in nonsprinklered Group A buildings having an
occupant load exceeding 1,000 persons.
Exceptions:
1.Open-air-seating spaces
without enclosed spaces.
2.Class I automatic dry and semiautomatic dry standpipes
or manual wet standpipes are allowed in buildings where
the highest floor surface used for human occupancy is
75 feet (22 860 mm) or less above the lowest level of
fire department vehicle access.
[F] 905.3.3 Covered mall
buildings. A covered mall building shall be equipped
throughout with a standpipe system where required by Section
905.3.1. Covered mall buildings I not required to be equipped
with a standpipe system by Section 905.3.1 shall be equipped
with Class I hose connections connected to a system sized
to deliver water at 250 gallons per minute (946.4 L/min)
at the most hydraulically remote outlet. Hose connections
shall be provided at each of the following locations:
1.Within the mall at the entrance to each exit passageway
or corridor.
2.At each floor-level landing within enclosed stairways
opening directly on the mall.
3.At exterior public entrances
to the mall.
[F]
905.3.4 Stages. Stages greater than 1,000 square feet
in area (93 m2) shall be equipped with a Class
III wet standpipe system with 11/2-inch
and 21/2-inch (38 mm and 64 mm) hose
connections on each side of the stage.
Exception:
Where the building or area is equipped throughout with an
automatic sprinkler system, a 11/2-inch
(38 mm) hose connection shall be installed in accordance with
NFPA 13 or in accordance with NFPA 14 for Class II or III
standpipes.
[F] 905.3.4.1 Hose and cabinet. The 11/2-inch
(38 mm) hose connections shall be equipped with sufficient
lengths of 11/2-inch (38 mm) hose
to provide fire protection for the stage area. Hose connections
shall be equipped with an approved adjustable fog nozzle
and be mounted in a cabinet or on a rack.
[F] 905.3.5 Underground
buildings. Underground buildings shall be equipped throughout
with a Class I automatic wet or manual wet standpipe system.
[F] 905.3.6 Helistops and
heliports. Buildings with a helistop or heliport that
are equipped with a standpipe shall extend the standpipe
to the roof level on which the helistop or heliport is located
in accordance with Section 1107.5
of the International Fire Code.
[F] 905.3.7 Marinas and
boatyards. Marinas and boatyards shall be equipped throughout
with standpipe systems in accordance with NFPA 303.
[F] 905.4 Location of Class
I standpipe hose connections. Class I standpipe hose connections
shall be provided in all of the following locations:
1. In every required stairway, a hose connection shall
be provided for each floor level above or below grade.
Hose connections shall be located at an intermediate floor
level landing between floors, unless otherwise approved
by the fire code official.
2. On each side of the wall
adjacent to the exit opening of a horizontal exit.
Exception: Where floor areas adjacent to a horizontal
exit are reachable from exit stairway hose connections by
a 30- foot (9144 mm) hose stream from a nozzle attached to
100 feet (30480 mm) of hose, a hose connection shall not be
required at the horizontal exit.
3.In every exit passageway at the entrance from the exit
passageway to other areas of a building.
4.In covered mall buildings, adjacent to each exterior
public entrance to the mall and adjacent to each entrance
from an exit passageway or exit corridor to the mall.
5.Where the roof has a slope less than four units vertical
in 12 units horizontal (33.3-percent slope), each standpipe
shall be provided with a hose connection located either
on the roof or at the highest landing of stairways with
stair access to the roof. An additional hose connection
shall be provided at the top of the most hydraulically
remote standpipe for testing purposes.
6.Where the most remote portion of a nonsprinklered floor
or story is more than 150 feet (45 720 mm) from a hose
connection or the most remote portion of a sprinklered
floor or story is more than 200 feet (60 960 mm) from
a hose connection, the fire code official is authorized
to require that additional hose connections be provided
in approved locations.
[F]
905.4.1 Protection. Risers and laterals of Class I standpipe
systems not located within an enclosed stairway or pressurized
enclosure shall be protected by a degree of fire resistance
equal to that required for vertical enclosures in the building
in which they are located.
Exception: In buildings equipped throughout with an approved
automatic sprinkler system, laterals that are not located
within an enclosed stairway or pressurized enclosure are not
required to be enclosed within fire-resistance-rated construction.
[F]
905.4.2 Interconnection. In buildings where more than
one standpipe is provided, the standpipes shall be interconnected
in accordance with NFPA 14.
[F] 905.5 Location of Class
II standpipe hose connections. Class II standpipe hose
connections shall be accessible and located so that all portions
of the building are within 30 feet (9144 mm) of a nozzle attached
to 100 feet (30480 mm) of hose.
[F]
905.5.1 Groups A-1 and A-2. In Group A-1 and A-2 occupancies
with occupant loads of more than 1,000, hose connections
shall be located on each side of any stage, on each side
of the rear of the auditorium, on each side of the balcony
and on each tier of dressing rooms.
[F]
905.5.2 Protection. Fire-resistance-rated protection
of risers and laterals of Class II standpipe systems is
not required.
[F] 905.5.3 Class II system
T-inch hose. A minimum 1-inch (25 mm) hose shall be
permitted to be used for hose stations in light-hazard occupancies
where investigated and listed for this service and where
approved by the fire code official.
[F]
905.6 Location of Class III standpipe hose connections.
Class III standpipe systems shall have hose connections located
as required for Class I standpipes in Section 905.4 and shall
have Class II hose connections as required in Section 905.5.
[F]
905.6.1 Protection. Risers and laterals of Class III
standpipe systems shall be protected as required for Class
I systems in accordance with Section 905.4.1.
[F]
905.6.2 Interconnection. In buildings where more than
one Class III standpipe is provided, the standpipes shall
be interconnected at the bottom.
[F]
905.7 Cabinets. Cabinets containing fire-fighting equipment
such as standpipes, fire hoses, fire extinguishers or fire
department valves shall not be blocked from use or obscured
from view.
[F]
905.7.1 Cabinet equipment identification. Cabinets shall
be identified in an approved manner by a permanently attached
sign with letters not less than 2 inches (51 mm) high in
a color that contrasts with the background color, indicating
the equipment contained therein.
Exceptions:
1. Doors not large enough to accommodate a written sign
shall be marked with a permanently attached pictogram
of the equipment contained therein.
2. Doors that have either an approved visual identification
clear glass panel or a complete glass door panel are not
required to be marked.
[F]
905.7.2 Locking cabinet doors. Cabinets shall be unlocked.
Exceptions:
1. Visual identification panels of glass or other approved
transparent frangible material that is easily broken and
allows access.
2. Approved locking arrangements.
3. Group 1-3.
[F]
905.8 Dry standpipes. Dry standpipes shall not be installed.
Exception:
Where subject to freezing and in accordance with NFPA
14.
[F] 905.9 Valve supervision.
Valves controlling water supplies shall be supervised in the
open position so that a change in the normal position of the
valve will generate a supervisory signal at the supervising
station required by Section 903.4.
Where a fire alarm system is provided, a signal shall also
be transmitted to the control unit.
Exceptions:
1.
Valves to underground key or hub valves in roadway boxes
provided by the municipality or public utility do not require
supervision.
2.
Valves locked in the normal position and inspected as provided
in this code in buildings not equipped with a fire alarm
system.
[F]
905.10 During construction. Standpipe systems required
during construction and demolition operations shall be provided
in accordance with Section 3311.
|