SECTION 406 MOTOR-VEHICLE-RELATED OCCUPANCIES
406.1.2 Area increase.
Group U occupancies used for the storage of private or pleasure-type
motor vehicles where no repair work is completed or fuel is
dispensed are permitted to be 3,000 square feet (279 m2)
when the following provisions are met:
1.For
a mixed occupancy building, the exterior wall and opening
protection for the Group U portion of the building shall be
as required for the major occupancy of the building. For such
a mixed occupancy building, the allowable floor area of the
building shall be as permitted
for the major occupancy contained therein.
2.For
a building containing only a Group U occupancy, the exterior
wall shall not be required to have a fire-resistance
rating and the area of openings shall not be limited when
the fire separation distance is 5 feet (1524 mm) or more.
More than one 3,000-square-foot (279 m2) Group
U occupancy shall be permitted to be in the same building,
provided each 3,000-square-foot (279 m2) area is
separated by fire walls complying with Section
705.
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|