SECTION
1405 INSTAllATION OF WAll COVERINGS
1405.1
General. Exterior wall coverings shall be designed and
constructed in accordance with the applicable provisions
of this section.
1405.2
Weather protection. Exterior walls shall provide weather
protection for the building. The materials of the minimum
nominal thickness specified in Table
1405.2 shall be acceptable as approved weather coverings.
1405.3 Flashing. Flashing shall be installed in such
a manner so as to prevent moisture from entering the wall
or to redirect it to the exterior. Flashing shall be installed
at the perimeters of exterior door and window assemblies,
penetrations and terminations of exterior wall assemblies,
exterior wall intersections with roofs, chimneys, porches,
decks, balconies and similar projections and at built-in
gutters and similar locations where moisture could enter
the wall. Flashing with projecting flanges shall be installed
on both sides and the ends of copings, under sills and continuously
above projecting trim.
1405.3.1
Exterior wall pockets. In exterior walls of buildings
or structures, wall pockets or crevices in which moisture
can accumulate shall be avoided or protected with caps
or drips, or other approved means shall be provided to
prevent water damage.
1405.3.2 Masonry. Flashing and weep holes shall
be located in the first course of masonry above finished
ground level above the foundation wall or slab, and other
points of support, including structural floors, shelf
angles and lintels where anchored veneers are designed
in accordance with Section 1405.5.
1405.4 Wood veneers. Wood veneers on exterior walls
of buildings of Type I, II, III and IV construction shall
be not less than 1 inch (25 mm) nominal thickness, 0.438-inch
(11.1 mm) exterior hardboard siding or 0.375-inch (9.5 mm)
exterior-type wood structural panels or particleboard and
shall conform to the following:
1. The veneer shall not exceed three stories in height,
measured from the grade plane. Where fire-retardant-treated
wood is used, the height shall not exceed four stories.
2. The veneer is attached to or furred from a noncombustible
backing that is fire-resistance rated as required by other
provisions of this code.
3. Where open or spaced wood veneers (without concealed
spaces) are used, they shall not project more than 24
inches (610 mm) from the building wall.
1405.5 Anchored masonry veneer. Anchored masonry veneer
shall comply with the provisions of Sections 1405.5, 1405.6,
1405.7 and 1405.8 and Sections 6.1
and 6.2 of ACI 530/ASCE 5/TMS 402.
1405.5.1 Tolerances. Anchored masonry veneers in
accordance with Chapter 14 are not required to meet the
tolerances in Article 3.3 Gl of ACI 530.l/ASCE 6/TMS 602.
1405.5.2 Seismic requirements. Anchored masonry
veneer located in Seismic Design Category C, E or F shall
conform to the requirements of Section
6.2.2.10 of ACI5301 ASCE51 TMS 402. Anchored masonry
veneer located in Seismic Design Category D shall conform
to the requirements for Seismic Design Category E or F.
1405.6 Stone veneer. Stone veneer units not exceeding
10 inches (254 mm) in thickness shall be anchored directly
to masonry, concrete or to stud construction by one of the
following methods:
1.With concrete or masonry backing, anchor ties shall
be not less than 0.1055-inch (2.68 mm) corrosion-resistant
wire, or approved equal, formed beyond the base of the
backing. The legs of the loops shall be not less than
6 inches (152 mm) in length bent at right angles and laid
in the mortar joint, and spaced so that the eyes or loops
are 12 inches (305 mm) maximum on center (o.c.) in both
directions. There shall be provided not less than a 0.1055-inch
(2.68 mm) corrosion-resistant wire tie, or approved equal,
threaded through the exposed loops for every 2 square
feet (0.2 m2) of stone veneer. This tie shall
be a loop having legs not less than 15 inches (381 mm)
in length bent so that it will lie in the stone veneer
mortar joint. The last 2 inches (51 mm) of each wire leg
shall have a right-angle bend. One-inch (25 mm) minimum
thickness of cement grout shall be placed between the
backing and the stone veneer.
2.With stud backing, a 2-inch by 2-inch (51 by 51 mm)
0.0625-inch (1.59 mm) corrosion-resistant wire mesh with
two layers of water-resistive barrier in accordance with
Section 1404.2 shall be applied
directly to wood studs spaced a maximum of 16 inches (406
mm) o.c. On studs, the mesh shall be attached with 2-inch-long
(51 mm) corrosion-resistant steel wire furring nails at
4 inches (102 mm) o.c. providing a minimum 1.125-inch
(29 mm) penetration into each stud and with 8d common
nails at 8 inches (203 mm) o.c. into top and bottom plates
or with equivalent wire ties. There shall be not less
than a 0.1055-inch (2.68 mm) corrosion-resistant wire,
or approved equal, looped through the mesh for every 2
square feet (0.2 m2) of stone veneer. This
tie shall be a loop having legs not less than 15 inches
(381 mm) in length, so bent that it will lie in the stone
veneer mortar joint. The last 2 inches (51 mm) of each
wire leg shall have a right-angle bend. One-inch (25 mm)
minimum thickness of cement grout shall be placed between
the backing and the stone veneer.
1405.7 Slab-type veneer. Slab-type veneer units not
exceeding 2 inches (51 mm) in thickness shall be anchored
directly to masonry, concrete or stud construction. For
veneer units of marble, travertine, granite or other stone
units of slab form ties of corrosion-resistant dowels in
drilled holes shall be located in the middle third of the
edge of the units, spaced a maximum of 24 inches (610 m)
apart around the periphery of each unit with not less than
four ties per veneer unit. Units shall not exceed 20 square
feet (1.9 m2) in area. If the dowels are not
tight fitting, the holes shall be drilled not more than
0.063 inch (1.6 mm) larger in diameter than the dowel, with
the hole countersunk to a diameter and depth equal to twice
the diameter of the dowel in order to provide a tight-fitting
key of cement mortar at the dowel locations when the mortar
in the joint has set. Veneer ties shall be corrosion-resistant
metal capable of resisting, in tension or compression, a
force equal to two times the weight of the attached veneer.
If made of sheet metal, veneer ties shall be not smaller
in area than 0.0336 by 1 inch (0.853 by 25 mm) or, if made
of wire, not smaller in diameter than 0.1483-inch (3.76
mm) wire.
1405.8 Terra cotta. Anchored terra cotta or ceramic
units not less than 1.625 inches (41 mm) thick shall be
anchored directly to masonry, concrete or stud construction.
Tied terra cotta or ceramic veneer units shall be not less
than 1.625 inches (41 mm) thick with projecting dovetail
webs on the back surface spaced approximately 8 inches (203
mm) o.c. The facing shall be tied to the backing wall with
corrosion-resistant metal anchors of not less than No.8
gage wire installed at the top of each piece in horizontal
bed joints not less than 12 inches (305 mm) nor more than
18 inches (457 mm) o.c.; these anchors shall be secured
to 0.25-inch (6.4 mm) corrosion-resistant pencil rods that
pass through the vertical aligned loop anchors in the backing
wall. The veneer ties shall have sufficient strength to
support the full weight of the veneer in tension. The facing
shall be set with not less than a 2- inch (51 mm) space
from the backing wall and the space shall be filled solidly
with portland cement grout and pea gravel. Immediately prior
to setting, the backing wall and the facing shall be drenched
with clean water and shall be distinctly damp when the grout
is poured.
1405.9 Adhered masonry veneer. Adhered masonry veneer
shall comply with the applicable requirements in Section
1405.9.1 and Sections 6.1 and 6.3
of ACI 530/ASCE 5/TMS 402.
1405.9.1 Interior adhered masonry veneers. Interior
adhered masonry veneers shall have a maximum weight of
20 psf (0.958 kg/m2) and shall be installed
in accordance with Section 1405.9. Where the interior
adhered masonry veneer is supported by wood construction,
the supporting members shall be designed to limit deflection
to 1/600 of the span of the supporting
members.
1405.10 Metal veneers. Veneers of metal shall be fabricated
from approved corrosion-resistant materials or shall be
protected front and back with porcelain enamel, or otherwise
be treated to render the metal resistant to corrosion. Such
veneers shall not be less than 0.0149-inch (0.378 mm) nominal
thickness sheet steel mounted on wood or metal furring strips
or approved sheathing on the wood construction.
1405.10.1 Attachment. Exterior metal veneer shall
be securely attached to the supporting masonry or framing
members with corrosion-resistant fastenings, metal ties
or by other approved devices or methods. The spacing of
the fastenings or ties shall not exceed 24 inches (610
mm) either vertically or horizontally, but where units
exceed 4 square feet (0.4 m2) in area there
shall be not less than four attachments per unit. The
metal attachments shall have a cross-sectional area not
less than provided by W 1.7 wire. Such attachments and
their supports shall be capable of resisting a horizontal
force in accordance with the wind loads specified in Section
1609, but in no case less than 20 psf (0.958 kg/rn2).
1405.10.2
Weather protection. Metal supports for exterior
metal veneer shall be protected by painting, galvanizing
or by other equivalent coating or treatment. Wood studs,
furring strips or other wood supports for exterior metal
veneer shall be approved pressure-treated wood or protected
as required in Section 1403.2.
Joints and edges exposed to the weather shall be caulked
with approved durable waterproofing material or by
other approved means to prevent penetration of moisture.
1405.10.3
Backup. Masonry backup shall not be required for metal
veneer except as is necessary to meet the fire-resistance
requirements of this code.
1405.10.4 Grounding. Grounding of metal veneers
on buildings shall comply with the requirements of Chapter
27 of this code or the ICC Electrical Code.
1405.11 Glass veneer. The area of a single section of
thin exterior structural glass veneer shall not exceed 10
square feet (0.93 m2) where it is not more than
15 feet (4572 mm) above the level of the sidewalk or grade
level directly below, and shall not exceed 6 square feet
(0.56 m2) where it is more than 15 feet (4572
mm) above that level.
1405.11.1 Length and height.
The length or height of any section of thin exterior structural
glass veneer shall not exceed 48 inches (1219 mm).
1405.11.2 Thickness. The thickness of thin exterior
structural glass veneer shall be not less than 0.344 inch
(8.7 mm).
1405.11.3 Application. Thin exterior structural
glass veneer shall be set only after backing is thoroughly
dry and after application of an approved bond coat uniformly
over the entire surface of the backing so as to effectively
seal the surface. Glass shall be set in place with an
approved mastic cement in sufficient quantity so that
at least 50 percent of the area of each glass unit is
directly bonded to the backing by mastic not less than
0.25 inch (6.4 mm) thick and not more than 0.625 inch
(15.9 mm) thick. The bond coat and mastic shall be evaluated
for compatibility and shall bond firmly together.
1405.11.4 Installation at sidewalk level. Where
glass extends to a sidewalk surface, each section shall
rest in an approved metal molding, and be set at least
0.25 inch (6.4 mm) above the highest point of the sidewalk.
The space between the molding and the sidewalk shall be
thoroughly caulked and made water tight.
1405.11.4.1
Installation above sidewalk level. Where thin exterior
structural glass veneer is installed above the level
of the top of a bulkhead facing, or at a level more
than 36 inches (914 mm) above the sidewalk level, the
mastic cement binding shall be supplemented with approved
nonferrous metal shelf angles located in the horizontal
joints in every course. Such shelf angles shall be not
less than 0.0478-inch (1.2 mm) thick and not less than
2 inches (51 mm) long and shall be spaced at approved
intervals, with not less than two angles for each glass
unit. Shelf angles shall be secured to the wall or backing
with expansion bolts, toggle bolts or by other approved
methods.
1405.11.5 Joints. Unless otherwise specifically
approved by the building official, abutting edges of thin
exterior structural glass veneer shall be ground square.
Mitered joints shall not be used except where specifically
approved for wide angles. Joints shall be uniformly buttered
with an approved jointing compound and horizontal joints
shall be held to not less than 0.063 inch (1.6 mm) by
an approved nonrigid substance or device. Where thin exterior
structural glass veneer abuts nonresilient material at
sides or top, expansion joints not less than 0.25 inch
(6.4 mm) wide shall be provided.
1405.11.6 Mechanical fastenings. Thin exterior
structural glass veneer installed above the level of the
heads of show windows and veneer installed more than 12
feet (3658 mm) above sidewalk level shall, in addition
to the mastic cement and shelf angles, be held in place
by the use of fastenings at each vertical or horizontal
edge, or at the four corners of each glass unit. Fastenings
shall be secured to the wall or backing with expansion
bolts, toggle bolts or by other methods. Fastenings shall
be so designed as to hold the glass veneer in a vertical
plane independent of the mastic cement. Shelf angles providing
both support and fastenings shall be permitted.
1405.11.7 Flashing.
Exposed edges of thin exterior structural glass veneer
shall be flashed with overlapping corrosion-resistant
metal flashing and caulked with a waterproof compound
in a manner to effectively prevent the entrance of moisture
between the glass veneer and the backing.
1405.12
Exterior windows and doors. Windows and doors installed
in exterior walls shall conform to the testing and performance
requirements of Section 1714.5.
1405.12.1 Installation.
Windows and doors shall be installed in accordance with
approved manufacturer's instructions. Fastener size
and spacing shall be provided in such instructions and
shall be calculated based on maximum loads and spacing
used in the tests.
1405.12.2 Window sills.
In Occupancy Groups R-2 and R-3, one- and two-family
and multiple-family dwellings, where the opening of
the sill portion of an operable window is located more
than 72 inches (1829 mm) above the finished grade or
other surface below, the lowest part of the clear opening
of the window shall be a minimum of 24 inches (610 mm)
above the finished floor surface of the room in which
the window is located. Glazing between the floor and
a height of 24 inches (610 mm) shall be fixed or have
openings such that a4-inch (102 mm) diameter sphere
cannot pass through.
Exception:
Openings that are provided with window guards that
comply with ASTM F 2006 or F 2090.
1405.13
Vinyl siding. Vinyl siding conforming to the requirements
of this section and complying with ASTM D 3679 shall be
permitted on exterior walls of buildings of Type V construction
located in areas where the basic wind speed specified
in Chapter 16 does not exceed 100 miles per hour (45 m/s)
and the building height is less than or equal to 40 feet
(12 192 mm) in Exposure C. Where construction is located
in areas where the basic wind speed exceeds 100 miles
per hour (45 m/s), or building heights are in excess of
40 feet (12 192 mm), tests or calculations indicating
compliance with Chapter 16 shall be submitted. Vinyl siding
shall be secured to the building so as to provide weather
protection for the exterior walls of the building.
1405.13.1 Application.
The siding shall be applied over sheathing or materials
listed in Section 2304.6. Siding
shall be applied to conform with the water-resistive
barrier requirements in Section 1403.
Siding and accessories shall be installed in accordance
with approved manufacturer's instructions. Unless otherwise
specified in the approved manufacturer's instructions,
nails used to fasten the siding and accessories shall
have a minimum 0.313-inch (7.9 mm) head diameter and
0.125-inch (3.18 mm) shank diameter. The nails shall
be corrosion resistant and shall be long enough to penetrate
the studs or nailing strip at least 0.75 inch (19 mm).
Where the siding is installed horizontally, the fastener
spacing shall not exceed 16 inches (406 mm) horizontally
and 12 inches (305 mm) vertically. Where the siding
is installed vertically, the fastener spacing shall
not exceed 12 inches (305 mm) horizontally and 12 inches
(305 mm) vertically.
1405.14
Cement plaster. Cement plaster applied to exterior walls
shall conform to the requirements specified in Chapter 25.
1405.15
Fiber cement siding. Fiber cement siding complying
with Section 1404.10 shall be
permitted on exterior walls of Type I, II, III, IV and V
construction for wind pressure resistance or wind speed
exposures as indicated in the manufacturer's compliance
report and approved installation instructions. Where specified,
the siding shall be installed over sheathing or materials
listed in Section 2304.6 and shall
be installed to conform to the water-resistive barrier requirements
in Section 1403. Siding and accessories
shall be installed in accordance with approved manufacturer's
instructions. Unless otherwise specified in the approved
manufacturer's instructions, nails used to fasten the siding
to wood studs shall be corrosion-resistant round head smooth
shank and shall be long enough to penetrate the studs at
least 1 inch (25 mm). For metal framing, all-weather screws
shall be used and shall penetrate the metal framing at least
three full threads.
1405.16 Fastening. Weather boarding and wall coverings
shall be securely fastened with aluminum, copper, zinc,
zinc-coated or other approved corrosion-resistant fasteners
in accordance with the nailing schedule in Table
2304.9.1 or the approved manufacturer's installation
instructions. Shingles and other weather coverings shall
be attached with appropriate standard-shingle nails to furring
strips securely nailed to studs, or with approved mechanically
bonding nails, except where sheathing is of wood not less
than 1-inch (25 mm) nominal thickness or of wood structural
panels as specified in Table
2308.9.3(3).
1405.17 Fiber cement siding.
1405.17.1 Panel siding. Panels shall be installed
with the long dimension parallel to framing. Vertical
joints shall occur over framing members and shall be sealed
with caulking or covered with battens. Horizontal joints
shall be flashed with Z-flashing and blocked with solid
wood framing.
1405.17.2 Horizontal lap siding. Lap siding shall
be lapped a minimum of 11/4 inches
(32 mm) and shall have the ends sealed with caulking,
covered with an H-section joint cover or located over
a strip of flashing. Lap siding courses shall be permitted
to be installed with the fastener heads exposed or concealed,
according to approved manufacturers' instructions.