SECTION 406 MOTOR-VEHICLE-RELATED OCCUPANCIES
406.1 Private garages and
carports.
406.1.1 Classification.
Buildings or parts of buildings classified as Group U occupancies
because of the use or character of the occupancy shall
not exceed 1,000 square feet (93 m2) in area
or one story in height except as provided in Section 406.1.2.
Any building or portion thereof that exceeds the limitations
specified in this section shall be classified in the occupancy
group other than Group U that it most nearly resembles.
406.1.2 Area increase.
Group U occupancies used for the storage of private or pleasure-type
motor vehicles where no repair work is completed or fuel
is dispensed are permitted to be 3,000 square feet (279
m2) when the following provisions are met:
1.For
a mixed occupancy building, the exterior wall and opening
protection for the Group U portion of the building shall
be as required for the major occupancy of the building.
For such a mixed occupancy building, the allowable floor
area of the building shall be as permitted
for the major occupancy contained therein.
2.For
a building containing only a Group U occupancy, the exterior
wall shall not be required to have a fire-resistance
rating and the area of openings shall not be limited when
the fire separation distance is 5 feet (1524 mm) or more.
More than one 3,000-square-foot (279 m2) Group
U occupancy shall be permitted to be in the same building,
provided each 3,000-square-foot (279 m2) area
is separated by fire walls complying with Section
705.
406.1.3 Garages
and carports. Carports shall be open on at least two sides.
Carport floor surfaces shall be of approved noncombustible
material. Carports not open on at least two sides shall be
considered a garage and shall comply with the provisions of
this section for garages.
Exception: Asphalt surfaces
shall be permitted at ground level in carports. The area of
floor used for parking of automobiles or other vehicles shall
be sloped to facilitate the movement of liquids to a drain
or toward the main vehicle entry doorway.
406.1.4 Separation. Separations
shall comply with the following:
1.The
private garage shall be separated from the dwelling
unit and its attic area by means of a minimum 1/2-inch
(12.7 mm) gypsum board applied to the garage side. Garages
beneath habitable rooms shall be separated from all habitable
rooms above by not less than a 5/8-inch
Type X gypsum board or equivalent. Door openings between
a private garage and the dwelling unit shall be equipped
with either solid wood doors or solid or honeycomb core
steel doors not less than 13/8
inches (34.9
mm) thick, or doors in compliance with Section
715.4.3. Openings from a private garage directly into
a room used for sleeping purposes shall not be permitted.
Doors shall be I
self-closing
and self-latching.
2.Ducts
in a private garage and ducts penetrating the walls or ceilings
separating the dwelling unit from the garage shall be constructed
of a minimum 0.019-inch (0.48
mm) sheet steel and shall have no openings into the garage.
3.A
separation is not required between a Group R-3 and U carport,
provided the carport is entirely open on two or more sides
and there are not enclosed areas above.
406.2
Parking garages.
406.2.1 Classification.
Parking garages shall be classified as either open, as defined
in Section 406.3, or enclosed and shall meet the appropriate
criteria in Section 406.4. Also see Section
509 for special provisions for parking garages.
406.2.2 Clear height.
The clear height of each floor level in vehicle and pedestrian
traffic areas shall not be less than 7 feet (2134 mm). Vehicle
and pedestrian areas accommodating van-accessible parking
required by Section 1106.5 shall
conform to ICC Al 17.1. 406.2.3
Guards. Guards shall be provided in accordance with Section
1012 at exterior and interior vertical openings on floor
and roof areas where vehicles are parked or moved and where
the vertical distance to the ground or surface directly below
exceeds 30 inches (762 mm).
406.2.4 Vehicle
barriers. Parking areas shall be provided with exterior
or interior walls or vehicle barriers, except at pedestrian
or vehicular accesses, designed in accordance with Section
1607.7. Vehicle barriers not less than 2 feet (607 mm)
high shall be placed at the end of drive lanes, and at the
end of parking spaces where the difference in adjacent floor
elevation is greater than 1 foot (305 mm).
Exception: Vehicle storage
compartments in a mechanical access parking garage.
406.2.5 Ramps.
Vehicle ramps shall not be considered as required exits unless
pedestrian facilities are provided. Vehicle ramps that are
utilized for vertical circulation as well as for parking shall
not exceed a slope of 1:15 (6.67 percent).
406.2.6 Floor surface. Parking surfaces shall be of
concrete or similar noncombustible and nonabsorbent materials.
Exception: Asphalt parking
surfaces are permitted at ground level. The area of floor
used for parking of automobiles or other vehicles shall be
sloped to facilitate the movement of liquids to a drain or
toward the main vehicle entry doorway.
406.2.7 Mixed separation.
Parking garages shall be separated from other occupancies
in accordance with Section 508.3.
406.2.8 Special hazards.
Connection of a parking garage with any room in which there
is a fuel-fired appliance shall be by means of a vestibule
providing a two-doorway separation.
Exception:
A single door shall be allowed provided the sources of ignition
in the appliance are at least 18 inches (457 mm) above the
floor.
406.2.9
Attached to rooms. Openings from a parking garage directly
into a room used for sleeping purposes shall not be permitted.
406.3
Open parking garages.
406.3.1
Scope. Except where specific provisions are made in
the following subsections, other requirements of this code
shall apply.
406.3.2
Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in this
code, have the meanings shown herein.
MECHANICAL-ACCESS
OPEN PARKING GARAGES. Open parking garages employing parking
machines, lifts, elevators or other mechanical devices for
vehicles moving from and to street level and in which public
occupancy is prohibited above the street level.
OPEN
PARKING GARAGE. A structure or portion of a structure
with the openings as described in Section 406.3.3.1 on two
or more sides that is used for the parking or storage of private
motor vehicles as described in Section 406.3.4.
RAMP-ACCESS
OPEN PARKING GARAGES. Open parking garages employing a
series of continuously rising floors or a series of interconnecting
ramps between floors permitting the movement of vehicles under
their own power from and to the street level.
406.3.3
Construction. Open parking garages shall be of Type
I, II or IV construction. Open parking garages shall meet
the design requirements of Chapter 16. For vehicle barriers,
see Section 406.2.4.
406.3.3.1
Openings. For natural ventilation purposes, the exterior
side of the structure shall have uniformly distributed
openings on two or more sides. The area of such openings
in exterior walls on a tier must be at least 20 percent
of the total perimeter wall area of each tier. The aggregate
length of the openings considered to be providing natural
ventilation shall constitute a minimum of 40 percent of
the perimeter of the tier. Interior walls shall be at
least 20 percent open with uniformly distributed openings.
Exception: Openings are not required to be distributed
over 40 percent of the building perimeter where the required
openings are uniformly distributed over two opposing sides
of the building.
406.3.4 Uses. Mixed uses shall be allowed in the same
building as an open parking garage subject to the provisions
of Sections 508.3,
402.7.1, 406.3.13, 509.3, 509.4
and 509.7.
406.3.5 Area and height. Area and height of open parking
garages shall be limited as set forth in Chapter 5 for Group
S-2 occupancies and as further provided for in Section
508.3.
406.3.5.1 Single use. When the open parking garage
is used exclusively for the parking or storage of private
motor vehicles, with no other uses in the building, the
area and height shall be permitted to comply with Table
406.3.5, along with increases allowed by Section 406.3.6.
Exception: The grade-level tier is permitted to contain
an office, waiting and toilet rooms having a total combined
area of not more than 1,000 square feet (93 m2).
Such area need not be separated from the open parking garage.
In open parking garages having a spiral or sloping floor,
the horizontal projection of the structure at any cross section
shall not exceed the allowable area per parking tier. In the
case of an open parking garage having a continuous spiral
floor, each 9 feet 6 inches (2896 mm) of height, or portion
thereof, shall be considered a tier. The clear height of a
parking tier shall not be less than 7 feet (2134 mm), except
that a lower clear height is permitted in mechanical-access
open parking garages where approved by the building official.
406.3.6 Area and
height increases. The allowable area and height of open
parking garages shall be increased in accordance with the
provisions of this section. Garages with sides open on three-fourths
of the building's perimeter are permitted to be increased
by 25 percent in area and one tier in height. Garages with
sides open around the entire building's perimeter are permitted
to be increased by 50 percent in area and one tier in height.
For a side to be considered open under the above provisions,
the total area of openings along the side shall not be less
than 50 percent of the interior area of the side at each tier
and such openings shall be equally distributed along the
length of the tier.
Allowable tier areas in Table
406.3.5 shall be increased for open parking garages
constructed to heights less than the table maximum. The
gross tier area of the garage shall not exceed that permitted
for the higher structure. At least three sides of each such
larger tier shall have continuous horizontal openings not
less than 30 inches (762 mm) in clear height extending for
at least 80 percent of the length of the sides and no part
of such larger tier shall be more than 200 feet (60 960
mm) horizontally from such an opening. In addition, each
such opening shall face a street or yard accessible to a
street with a width of at least 30 feet (9144 mm) for the
full length of the opening, and standpipes shall be provided
in each such tier.
Open parking garages of Type
II construction, with all sides open, shall be unlimited
in allowable area where the height does not exceed 75 feet
(22 860 mm). For a side to be considered open, the total
area of openings along the side shall not be less than 50
percent of the interior area of the side at each tier and
such openings shall be equally distributed along the length
of the tier. All portions of tiers shall be within 200 feet
(60 960 mm) horizontally from such openings or other natural
ventilation openings as defined in section 406.3.3.1. These
openings shall be permitted to be provided in courts with
a minimum width of 30 feet (9144 mm) for the full width
of the openings.
406.3.7 Fire separation
distance. Exterior walls and openings in exterior walls
shall comply with Tables 601
and 602. The distance to an
adjacent lot line shall be determined in accordance with
Table 602 and Section
704.
406.3.8 Means of egress.
Where persons other than parking attendants are permitted,
open parking garages shall meet the means of egress requirements
of Chapter 10. Where no persons other than parking attendants
are permitted, there shall not be less than two 36-inch-wide
(914 mm) exit stairways. Lifts shall be permitted to be
installed for use of employees only, provided they are completely
enclosed by noncombustible materials.
406.3.9
Standpipes. Standpipes shall be installed where required
by the provisions of Chapter 9.
406.3.10 Sprinkler systems.
Where required by other provisions of this code, automatic
sprinkler systems and standpipes shall be installed in accordance
with the provisions of Chapter 9.
406.3.11 Enclosure of vertical
openings. Enclosure shall not be required for vertical
openings except as specified in Section 406.3.8.
406.3.12 Ventilation.
Ventilation, other than the percentage of openings specified
in Section 406.3.3.1, shall not be required.
406.3.13 Prohibitions.
The following uses and alterations are not permitted:
1.Vehicle
repair work.
2.Parking
of buses, trucks and similar vehicles.
3.Partial
or complete closing of required openings in exterior walls
by tarpaulins or any other means.
4.Dispensing
of fuel.
406.4
Enclosed parking garages.
406.4.1
Heights and areas. Enclosed vehicle parking garages
and portions thereof that do not meet the definition of
open parking garages shall be limited to the allowable heights
and areas specified in Table 503
as modified by Sections 504, 506
and 507. Roof parking is permitted.
406.4.2
Ventilation. A mechanical ventilation system shall be
provided in accordance with the International Mechanical
Code.
406.5 Motor fuel-dispensing
facilities.
406.5.1 Construction.
Motor fuel-dispensing facilities shall be constructed in
accordance with the International Fire Code and this
section.
406.5.2 Canopies. Canopies
under which fuels are dispensed shall have a clear, unobstructed
height of not less than 13 feet 6 inches (4115 mm) to the
lowest projecting element in the vehicle drive-through area.
Canopies and their supports over pumps shall be of noncombustible
materials, fire-retardant-treated wood complying with Chapter
23, wood of Type IV sizes or of construction providing 1-hour
fire resistance. Combustible materials used in or on a canopy
shall comply with one of the following:
1.
Shielded from the pumps by a noncombustible element of
the canopy, or wood of Type IV sizes;
2.
Plastics covered by aluminum facing having a minimum thickness
of 0.010 inch (0.30 mm) or corrosion-resistant steel having
a minimum base metal thickness of 0.016 inch (0.41 mm).
The plastic shall have a flame spread index of 25 or less
and a smoke-developed index of 450 or less when tested
in the form intended for use in accordance with ASTM E
84 and a self-ignition temperature of 650°F (343°C) or
greater when tested in accordance with ASTM D 1929; or
3.
Panels constructed of light-transmitting plastic materials
shall be permitted to be installed in canopies erected
over motor vehicle fuel-dispensing station fuel dispensers,
provided the panels are located at least 10 feet (3048
mm) from any building on the same lot and face yards or
streets not less than 40 feet (12 192 mm) in width on
the other sides. The aggregate areas of plastics shall
not exceed 1,000 square feet (93 m2). The maximum
area of any individual panel shall not exceed 100 square
feet (9.3 m2),
406.5.2.1
Canopies used to support gaseous hydrogen systems.
Canopies that are used to shelter dispensing operations
where flammable compressed gases are located on the
roof of the canopy shall be in accordance with the following:
1.The
canopy shall meet or exceed Type I construction requirements.
2.Operations
located under canopies shall be limited I to refueling
only.
3.The
canopy shall be constructed in a manner that prevents
the accumulation of hydrogen gas.
406.6
Repair garages.
406.6.1 General. Repair
garages shall be constructed in accordance with the International
Fire Code and this section. This occupancy shall not
include motor fuel-dispensing facilities, as regulated in
Section 406.5.
406.6.2 Mixed uses.
Mixed uses shall be allowed in the same building as a repair
garage subject to the provisions of Section
508.3.
406.6.3 Ventilation.
Repair garages shall be mechanically ventilated in accordance
with the International Mechanical Code. The ventilation
system shall be controlled at the entrance to the garage.
406.6.4 Floor surface.
Repair garage floors shall be of concrete or similar noncombustible
and nonabsorbent materials.
Exception: Slip-resistant,
nonabsorbent, interior floor finishes having a critical radiant
flux not more than 0.45 W/cm2,
as determined by
NFPA253, shall be permitted.
406.6.5 Heating equipment.
Heating equipment shall be installed in accordance with the
International Mechanical Code.
[F] 406.6.6 Gas detection
system. Repair garages used for repair of vehicles fueled
by nonodorized gases, such as hydrogen and nonodorized LNG,
shall be provided with an approved flammable gas-detection
system.
[F] 406.6.6.1 System
design. The flammable gas-detection system shall be
calibrated to the types of fuels or gases used by vehicles
to be repaired. The gas detection system shall be designed
to activate when the level of flammable gas exceeds 25 percent
of the lower explosive limit. Gas detection shall also be
provided in lubrication or chassis repair pits of garages
used for repairing nonodorized LNG-fueled vehicles.
[F] 406.6.6.2 Operation.
Activation of the gas detection system shall result in
all of the following:
1.
Initiation of distinct audible and visual alarm signals
in the repair garage.
2. Deactivation
of all heating systems located in the repair garage.
3. Activation
of the mechanical ventilation system, where
the system is interlocked with gas detection.
[F] 406.6.6.3 Failure
of the gas detection system. Failure of the gas detection
system shall result in the deactivation of the heating
system, activation of the mechanical ventilation system
when the system is interlocked with the gas detection
system and cause a trouble signal to sound in an approved
location.
|