| SECTION 803 WALL AND CEILING
FINISHES
803.1 General. Interior
wall and ceiling finishes shall be classified in accordance
with ASTM E 84. Such interior finish materials shall be grouped
in the following classes in accordance with their flame spread
and smoke-developed indexes.
Class A: Flame spread
0-25; smoke-developed 0-450.
Class B: Flame spread
26-75; smoke- developed 0-450.
Class C: Flame spread
76-200; smoke-developed 0-450.
Exception: Materials,
other than textiles, tested in accordance with Section 803.2.
803.2. Interior wall or ceiling
finishes other than textiles. Interior wall or ceiling
finishes, other than textiles, shall be permitted to be tested
in accordance with NFPA 286. Finishes tested in accordance
with NFPA286 shall comply with Section 803.2.1.
803.2.1 Acceptance criteria.
During the 40 kW exposure, the interior finish shall comply
with Item 1. During the 160 kW exposure, the interior finish
shall comply with Item 2. During the entire test, the interior
finish shall comply with Items 3 and 4.
1.During the 40kW exposure,
flames shall not spread to the ceiling.
2. During the 160 kW exposure,
the interior finish shall comply with the following:
2.1. Flame shall not spread
to the outer extremity of the sample on any wall or
ceiling.
2.2. Flashover, as defined
in NFPA 286, shall not occur.
3. The peak rate of heat
release throughout the NFPA 286 test shall not exceed
800 kW.
4. The total smoke released
throughout the NFPA 286 test shall not exceed 1,000 m2.
803.3 Stability. Interior
finish materials regulated by this chapter shall be applied
or otherwise fastened in such a manner that such materials
will not readily become detached where subjected to room temperatures
of 200°F (93°C) for not less than 30 minutes.
803.4 Application. Where
these materials are applied on walls, ceilings or structural
elements required to have a fire-resistance rating or to be
of noncombustible construction, they shall comply with the
provisions of this section.
803.4.1 Direct attachment
and furred construction. Where walls and ceilings are
required by any provision in this code to be of fire-resistance-rated
or noncombustible construction, the interior finish material
shall be applied directly against such construction or to
furring strips not exceeding 1.75 inches (44 mm) applied
directly against such surfaces. The intervening spaces between
such furring strips shall be filled with inorganic or Class
A material or shall be fireblocked at a maximum of 8 feet
(2438 mm) in any direction in accordance with Section
717.
803.4.2 Set-out construction.
Where walls and ceilings are required to be of fire-resistance-rated
or noncombustible construction and walls are set out or
ceilings are dropped distances greater than specified in
Section 803.4.1, Class A finish materials shall be used
except where interior finish materials are protected on
both sides by an automatic sprinkler system or attached
to noncombustible backing or furring strips installed as
specified in Section 803.4.1. The hangers and assembly members
of such dropped ceilings that are below the main ceiling
line shall be of noncombustible materials, except that in
Type III and V construction, fire-retardant-treated wood
shall be permitted. The construction of each set-out wall
shall be of fire-resistance-rated construction as required
elsewhere in this code.
803.4.3 Heavy timber construction.
Wall and ceiling finishes of all classes as permitted in
this chapter that are installed directly against the wood
decking or planking of Type IV construction or to wood furring
strips applied directly to the wood decking or planking
shall be fireblocked as specified in Section 803.4.1.
803.4.4 Materials. An
interior wall or ceiling finish that is not more than 0.25
inch (6.4 mm) thick shall be applied directly against a
noncombustible backing.
Exceptions:
1. Class A materials.
2. Materials where the qualifying
tests were made with the material suspended or furred out
from the noncombustible backing.
803.5 Interior finish requirements
based on group. Interior wall and ceiling finish shall
have a flame spread index not greater than that specified
in Table 803.5 for the group
and location designated. Interior wall and ceiling finish
materials, other than textiles, tested in accordance with
NFPA 286 and meeting the acceptance criteria of Section 803.2.1,
shall be permitted to be used where a Class A classification
in accordance with ASTM E 84 is required.
803.6 Textiles. Where
used as interior wall or ceiling finish materials, textiles,
including materials having woven or nonwoven, napped, tufted,
looped or similar surface and carpet and similar textile materials,
shall comply with the requirements of Section 803.6.1, 803.6.2
or 803.6.3.
803.6.1 Surface burning
characteristic test. Textile wall and ceiling coverings
shall have a Class A flame spread index in accordance with
ASTM E 84 and be protected by automatic sprinklers installed
in accordance with Section 903.3.1.1
or 903.3.1.2.
803.6.2 Room corner test,
textiles. Textile wall coverings shall meet the criteria
of Section 803.6.2.1 when tested in the manner intended
for use in accordance with the Method B protocol of NFPA
265 using the product-mounting system, including adhesive.
803.6.2.1 Method B test
protocol. During the 40 kW exposure, the interior
finish shall comply with Item 1. During the 150 kW exposure,
the interior finish shall comply with Item 2. During the
entire test, the interior finish shall comply with Item
3.
1. During the 40 kW exposure,
flames shall not spread to the ceiling.
2. During the 150 kW exposure,
the interior finish shall comply with the following:
2.1. Flame shall not spread
to the outer extremities of the samples on the 8-foot
by 12-foot (203 mm by 305 mm) walls.
2.2. Flashover, as described
in NFPA 265, shall not occur.
3. The total smoke released
throughout the NFPA 265 test shall not exceed 1000 m2.
803.6.3 Room corner test,
ceiling and wall finish. Textile wall and ceiling coverings
shall meet the criteria of Section 803.2.1 when tested in
the manner intended for use in accordance with NFPA 286
using the product-mounting system, including adhesive.
803.7 Expanded vinyl wall
coverings. Expanded vinyl wall coverings shall comply
with the requirements for textile wall and ceiling materials
and their use shall comply with Section 803.6.
Exception: Expanded vinyl
wall or ceiling coverings complying with Section 803.2 shall
not be required to comply with Section 803.1 or 803.6.
803.8 Insulation. Thermal
and acoustical insulation shall comply with Section
719.
803.9 Acoustical ceiling systems.
The quality, design, fabrication and erection of metal
suspension systems for acoustical tile and layin panel ceilings
in buildings or structures shall conform with generally accepted
engineering practice, the provisions of this chapter and other
applicable requirements of this code.
803.9.1 Materials and installation.
Acoustical materials complying with the interior finish
requirements of Section 803 shall be installed in accordance
with the manufacturers recommendations and applicable
provisions for applying interior finish.
803.9.1.1 Suspended acoustical
ceilings. Suspended acoustical ceiling systems shall
be installed in accordance with the provisions of ASTM
C 635 and ASTM C 636.
803.9.1.2 Fire-resistance-rated
construction. Acoustical ceiling systems that are
part of fire-resistance-rated construction shall be installed
in the same manner used in the assembly tested and shall
comply with the provisions of Chapter 7.
|