|
|
|
|
|
SECTION 415 GROUPS
H-1, H-2, H-3, H-4 AND H-5
[[F] 415.8 Group H-5.
[F] 415.8.1 General.
In addition to the requirements set forth elsewhere
in this code, Group H-5 shall comply with the provisions
of Section 415.8 and the International Fire Code.
[F] 415.8.2 Fabrication
areas.
[F]
415.8.2.1 Hazardous materials in fabrication areas.
[F] 415.8.2.1.1
Aggregate quantities. The aggregate quantities
of hazardous materials stored and used in a single
fabrication area shall not
exceed the quantities set forth in Table
415.8.2.1.1.
Exception: The quantity
limitations for any hazard category in Table
415.8.2.1.1 shall not apply where the fabrication
area contains quantities of hazardous materials not exceeding
the maximum allowable quantities per control area established
by Tables 307.1(1) and
307.1(2).
[F] 415.8.2.1.2
Hazardous production materials. The maximum
quantities of hazardous production materials (HPM)
stored in a single
fabrication area shall not exceed the maximum allowable
quantities per control area established by Tables
307.1(1) and 307.1(2).
[F] 415.8.2.2
Separation. Fabrication areas, whose sizes are
limited by the quantity of hazardous materials allowed
by Table 415.8.2.1.1,
shall be separated
from each other, from corridors and from other parts
of the building by not less than l-hour fire barriers.
Exceptions:
1. Doors
within such fire barrier walls, including doors to corridors,
shall be only self-closing fire door assemblies having
a fire protection rating of not less than 3/4
hour. 2. Windows
between fabrication areas and corridors are permitted
to be fixed glazing listed and labeled for a fire protection
rating of at least 3/4 hour in
accordance with Section 715.
[F] 415.8.2.3
Location of occupied levels. Occupied levels of
fabrication areas shall be located at or above the
first story above grade plane.
[F] 415.8.2.4
Floors. Except for surfacing, floors within
fabrication areas shall be of noncombustible construction.Openings
through floors of fabrication areas are permitted
to be unprotected where the interconnected levels
are used solely for mechanical equipment directly
related to such fabrication areas (see also Section
415.8.2.5). Floors forming a part of an
occupancy separation shall be liquid tight.
[F] 415.8.2.5
Shafts and openings through floors. Elevator
shafts, vent shafts and other openings through
floors shall be enclosed when required by Section
707. Mechanical, duct and piping penetrations
within a fabrication area shall not extend through
more than two floors. The annular space around
penetrations for cables, cable trays, tubing,
piping, conduit or ducts shall be sealed at the
floor level to restrict the movement of air. The
fabrication area, including the areas through
which the ductwork and piping extend, shall be
considered a single conditioned environment.
[F] 415.8.2.6
Ventilation. Mechanical exhaust ventilation
at the rate of not less than 1 cubic foot per
minute per square foot (0.044 L/s/m2)
of floor area shall be provided throughout the
portions of the fabrication area where HPM are
used or stored. The exhaust air duct system of
one fabrication area shall not connect to another
duct system outside that fabrication area within
the building. A ventilation system shall be provided
to capture and exhaust gases, fumes and vapors
at workstations. Two or more operations at a workstation
shall not be connected to the same exhaust system
where either one or the combination of the substances
removed could constitute a fire, explosion or
hazardous chemical reaction within the exhaust
duct system. Exhaust ducts penetrating occupancy
separations shall be contained in a shaft of equivalent
fire-resistance-rated construction. Exhaust ducts
shall not penetrate fire walls. Fire dampers
shall not be installed in exhaust ducts .
[F] 415.8.2.7
Transporting hazardous production materials to
fabrication areas. HPM shall be transported
to fabrication areas through enclosed piping or
tubing systems that comply with Section 415.8.6.1,
through service corridors complying with Section
415.8.4, or in corridors as permitted in the exception
to Section 415.8.3. The handling or transporting
of HPM within service corridors shall comply with
the International Fire Code.
[F] 415.8.2.8
Electrical.
[F] 415.8.2.8.1
General. Electrical equipment and devices
within the fabrication area shall comply with
the ICC Electrical Code. The requirements
for hazardous locations need not be applied
where the average air change is at least four
times that set forth in Section 415.8.2.6 and
where the number of air changes at any location
is not less than three times that required by
Section 415.8.2.6. The use of recalculated air
shall be permitted.
[F] 415.8.2.8.2
Workstations. Workstations shall not be
energized without adequate exhaust ventilation.
See Section 415.8.2.6 for workstation exhaust
ventilation requirements.
[F] 415.8.3
Corridors. Corridors shall comply with Chapter 10
and shall be separated from fabrication areas as specified
in Section 415.8.2.2. Corridors shall not contain HPM
and shall not be used for transporting such materials,
except through closed piping systems as provided in
Section 415.8.6.3.
Exception: Where existing
fabrication areas are altered or modified, HPM is allowed
to be transported in existing corridors, subject to the
following conditions:
1. Corridors.
Corridors adjacent to the fabrication area where the
alteration work is to be done shall comply with Section
1017 for a length determined as follows:
1.1 The length
of the common wall of the corridor and the fabrication
area; and
1.2. For the distance
along the corridor to the point of entry of HPM
into the corridor serving that fabrication area.
2. Emergency alarm
system. There shall be an emergency telephone system,
a local manual alarm station or other approved
alarm-initiating device within corridors at not
more than ISO-foot (45 720 mm) intervals and at
each exit and doorway. The signal shall be relayed
to an approved central, proprietary or remote station
service or the emergency control station and shall
also initiate a local audible alarm.
3. Pass throughs.
Self-closing doors having a fire protection rating
of not less than 1 hour shall separate pass-throughs
from existing corridors. Pass-throughs shall be
constructed as required for the corridors and protected
by an approved automatic fire-extinguishing system.
[F] 415.8.4
Service corridors.
[F] 415.8.4.1 Occupancy.
Service corridors shall be classified as Group
H-5.
[F] 415.8.4.2 Use
conditions. Service corridors shall be separated
from corridors as required by Section 415.8.2.2.
Service corridors shall not be used as a required
corridor.
[F] 415.8.4.3 Mechanical
ventilation. Service corridors shall be mechanically
ventilated as required by Section 415.8.2.6 or at
not less than six air changes per hour, whichever
is greater.
[F] 415.8.4.4 Means
of egress. The maximum distance of travel from
any point in a service corridor to an exit, exit
access corridor or door into a fabrication area
shall not exceed 75 feet (22 860 mm). Dead ends
shall not exceed 4 feet (1219 mm) in length. There
shall be not less than two exits, and not more than
one-half of the required means of egress shall require
travel into a fabrication area. Doors from service
corridors shall swing in the direction of egress
travel and shall be self-closing.
[F] 415.8.4.5 Minimum
width. The minimum clear width of a service
corridor shall be 5 feet (1524 mm), or 33 inches
(838 mm) wider than the widest cart or truck used
in the corridor, whichever is greater.
[F] 415.8.4.6 Emergency
alarm system. Emergency alarm systems shall
be provided in accordance with this section and
Sections 414.7.1 and 414.7.2.
The maximum allowable quantity per control area
provisions shall not apply to emergency alarm systems
required for HPM.
[F] 415.8.4.6.1
Service corridors. An emergency alarm system
shall be provided in service corridors, with at
least one alarm device in each service corridor.
[F] 415.8.4.6.2
Exit access corridors and exit enclosures.
Emergency alarms for exit access corridors and
exit enclosures shall comply with Section
414.7.2.
[F] 415.8.4.6.3
Liquid storage rooms, RPM rooms and gas rooms.
Emergency alarms for liquid storage rooms, HPM
rooms and gas rooms shall comply with Section
414.7.1.
[F] 415.8.4.6.4
Alarm-initiating devices. An approved emergency
telephone system, local alarm manual pull stations,
or other approved alarm-initiating devices are
allowed to be used as emergency alarm-initiating
devices.
[F] 415.8.4.6.5
Alarm signals. Activation of the emergency
alarm system shall sound a local alarm and transmit
a signal to the emergency control station.
[F] 415.8.5 Storage
of hazardous production materials.
[F] 415.8.5.1
General. Storage of HPM in fabrication areas
shall be within approved or listed storage cabinets
or gas cabinets or within a workstation. The
storage of HPM in quantities greater than those
listed in Section 1804.2
of the International Fire Code shall be in liquid
storage rooms, HPM rooms or gas rooms as appropriate
for the materials stored. The storage of other
hazardous materials shall be in accordance with
other applicable provisions of this code and
the International Fire Code.
[F] 415.8.5.2
Construction.
[F] 415.8.5.2.1
RPM rooms and gas rooms. HPM rooms and
gas rooms shall be separated from other areas
by not less than a 2-hour fire barrier where
the area is 300 square feet (27.9 m2)
or more and not less than a l-hour fire barrier
where the area is less than 300 square feet
(27.9 m2),
[F] 415.8.5.2.2
Liquid storage rooms. Liquid storage
rooms shall be constructed in accordance with
the following requirements:
1. Rooms
in excess of 500 square feet (46.5 m2)
shall have at least one exterior door approved
for fire department access.
2. Rooms
shall be separated from other areas by fire
barriers having a fire-resistance rating
of not less than 1-hour for rooms up to
150 square feet (13.9 m2)
in area and not less than 2 hours where
the room is more than 150 square feet (13.9
m2)
in area.
3. Shelving,
racks and wainscoting in such areas shall
be of noncombustible construction or wood
of not less than 1 inch (25 mm) nominal
thickness. 4. Rooms
used for the storage of Class I flammable
liquids shall not be located in a basement.
[F] 415.8.5.2.3
Floors. Except for surfacing, floors of
HPM rooms and liquid storage rooms shall be
of noncombustible liquid-tight construction.
Raised grating over floors shall be of noncombustible
materials.
[F] 415.8.5.3
Location. Where HPM rooms, liquid storage
rooms and gas rooms are provided, they shall have
at least one exterior wall and such wall shall
be not less than 30 feet (9144 mm) from lot lines,
including lot lines adjacent to public ways.
[F] 415.8.5.4
Explosion control. Explosion control shall
be provided where required by Section
414.5.1.
[F] 415.8.5.5
Exits. Where two exits are required from HPM
rooms, liquid storage rooms and gas rooms, one
shall be directly to the outside of the building.
[F] 415.8.5.6
Doors. Doors in a fire barrier wall, including
doors to corridors, shall be self-closing fire
door assemblies having a fire-protection rating
of not less than 3/4 hour.
[F] 415.8.5.7
Ventilation. Mechanical exhaust ventilation
shall be provided in liquid storage rooms, HPM
rooms and gas rooms at the rate of not less than
1 cubic foot per minute per square foot (0.044
L/s/m2)
of floor area or six air changes per hour, whichever
is greater, for categories of material. Exhaust
ventilation for gas rooms shall be designed to
operate at a negative pressure in relation to
the surrounding areas and direct the exhaust ventilation
to an exhaust system.
[F] 415.8.5.8
Emergency alarm system. An approved emergency
alarm system shall be provided for HPM rooms,
liquid storage rooms and gas rooms. Emergency
alarm-initiating devices shall be installed outside
of each interior exit door of such rooms. Activation
of an emergency alarm-initiating device shall
sound a local alarm and transmit a signal to the
emergency control station. An approved emergency
telephone system, local alarm manual pull stations
or other approved alarm-initiating devices are
allowed to be used as emergency alarm-initiating
devices.
[F] 415.8.6
Piping and tubing.
[F] 415.8.6.1 General.
Hazardous production materials piping and tubing
shall comply with this section and ASME B31.3.
[F] 415.8.6.2 Supply
piping and tubing.
[F] 415.8.6.2.1
RPM having a health-hazard ranking of 3 or 4.
Systems supplying HPM liquids or gases having
a health-hazard ranking on or 4 shall be welded
throughout, except for connections, to the systems
that are within a ventilated enclosure if the
material is a gas, or an approved method of drainage
or containment is provided for the connections
if the material is a liquid.
[F] 415.8.6.2.2
Location in service corridors. Hazardous production
materials supply piping or tubing in service corridors
shall be exposed to view.
[F] 415.8.6.2.3
Excess flow control. Where HPM gases or liquids
are carried in pressurized piping above 15 pounds
per square inch gauge (psig) (103.4 kPa), excess
flow control shall be provided. Where the piping
originates from within a liquid storage room,
HPM room or gas room, the excess flow control
shall be located within the liquid storage room,
HPM room or gas room. Where the piping originates
from a bulk source, the excess flow control shall
be located as close to the bulk source as practical.
[F] 415.8.6.3 Installations
in corridors and above other
occupancies. The installation of HPM piping and
tubing within the space defined by the walls of corridors
and the floor or roof above, or in concealed spaces
above other occupancies, shall be in accordance with
Section 415.8.6.2 and the following conditions:
1. Automatic
sprinklers shall be installed within the space
unless the space is less than 6 inches (152 mm)
in the least dimension.
2. Ventilation
not less than six air changes per hour shall be
provided. The space shall not be used to convey
air from any other area.
3. Where
the piping or tubing is used to transport HPM
liquids, a receptor shall be installed below such
piping or tubing. The receptor shall be designed
to collect any discharge or leakage and drain
it to an approved location. The I-hour enclosure
shall not be used as part of the receptor.
4. HPM
supply piping and tubing and nonmetallic waste
lines shall be separated from the corridor and
from occupancies other than Group H-5 by fire
barriers that have a fire-resistance rating of
not
less than 1
hour. Where gypsum wallboard is used, joints on
the piping side of the enclosure are not required
to be taped, provided the joints occur over framing
members. Access openings into the enclosure shall
be protected by approved fire protection-rated
assemblies.
5. Readily accessible
manual or automatic remotely activated fail-safe
emergency shutoff valves shall be installed on
piping and tubing other than waste lines at the
following locations:
5.1. At
branch connections into the fabrication area.
5.2. At entries
into corridors.
Exception: Transverse
crossings of the corridors by supply piping that is enclosed
within a ferrous pipe or tube for the width of the corridor
need not comply with Items 1 through 5.
[F] 415.8.6.4
Identification. Piping, tubing and HPM waste lines
shall be identified in accordance with ANSI A13.1
to indicate the material being transported.
[F] 415.8.7
Continuous gas detection systems. A continuous
gas detection system shall be provided for HPM gases
when the physiological warning threshold level of the
gas is at a higher level than the accepted PEL for the
gas and for flammable gases in accordance with this
section.
[F] 415.8.7.1
Where required. A continuous gas-detection system
shall be provided in the areas identified in Sections
415.8.7.1.1 through 415.8.7.1.4.
[F] 415.8.7.1.1
Fabrication areas. A continuous gas-detection
system shall be provided in fabrication areas when
gas is used in the fabrication area.
[F] 415.8.7.1.2
RPM rooms. A continuous gas-detection system
shall be provided in HPM rooms when gas is used
in the room.
[F] 415.8.7.1.3
Gas cabinets, exhausted enclosures and gas rooms.
A continuous gas-detection system shall be provided
in gas cabinets and exhausted enclosures. A continuous
gas-detection system shall be provided in gas rooms
when gases are not located in gas cabinets or exhausted
enclosures.
[F] 415.8.7.1.4
Corridors. When gases are transported in piping
placed within the space defined by the walls of
a corridor and the floor or roof above the corridor,
a continuous gas-detection system shall be provided
where piping is located and in the corridor.
Exception: A continuous
gas-detection system is not required for occasional transverse
crossings of the corridors by supply piping that is enclosed
in a ferrous pipe or tube for the width of the corridor.
[F] 415.8.7.2
Gas-detection system operation. The continuous gas-detection
system shall be capable of monitoring the room, area
or equipment in which the gas is located at or below
the PEL or ceiling limit of the gas for which detection
is provided. For flammable gases, the monitoring detection
threshold level shall be vapor concentrations in excess
of 20 percent of the lower explosive limit (LEL). Monitoring
for highly toxic and toxic gases shall also comply with
the requirements for such material in the International
Fire Code.
[F] 415.8.7.2.1
Alarms. The gas detection system shall initiate
a local alarm and transmit a signal to the emergency
control station when a short-term hazard condition
is detected. The alarm shall be both visual and
audible and shall provide warning both inside and
outside the area where the gas is detected. The
audible alarm shall be distinct from all other alarms.
[F] 415.8.7.2.2
Shutoff of gas supply. The gas detection system
shall automatically close the shutoff valve at the
source on gas supply piping and tubing related to
the system being monitored for which gas is detected
when a short-term hazard condition is detected.
Automatic closure of shutoff valves shall comply
with the following:
1. Where
the gas-detection sampling point initiating
the gas detection system alarm is within a gas cabinet
or exhausted enclosure, the shutoff valve in the
gas cabinet or exhausted enclosure for the specific
gas detected shall automatically close.
2. Where
the gas-detection sampling point initiating
the gas detection system alarm is within a room
and compressed gas containers are not in gas cabinets
or an exhausted enclosure, the shutoff valves on
all gas lines for the specific gas detected shall
automatically close.
3. Where
the gas-detection sampling point initiating
the gas detection system alarm is within a piping
distribution manifold enclosure, the shutoff valve
supplying the manifold for the compressed gas container
of the specific gas detected shall automatically
close.
Exception: Where the
gas-detection sampling point initiating the gas detection
system alarm is at the use location or within a gas valve
enclosure of a branch line downstream of a piping distribution
manifold, the shutoff valve for the branch line located
in the piping distribution manifold enclosure shall automatically
close.
[F] 415.8.8 Manual
fire alarm system. An approved manual fire alarm
system shall be provided throughout buildings containing
Group H-5. Activation of the alarm system shall initiate
a local alarm and transmit a signal to the emergency
control station. The fire alarm system shall be designed
and installed in accordance with Section
907.
415.8.9 Emergency
control station. An emergency control station
shall be provided in accordance with Sections 415.8.9.1
through 415.8.9.3.
415.8.9.1 Location.
The emergency control station shall be located on
the premises at an approved location outside the
fabrication area.
415.8.9.2 Staffing.
Trained personnel shall continuously staff the
emergency control station.
415.8.9.3 Signals.
The emergency control station shall receive signals
from emergency equipment and alarm and detection
systems. Such emergency equipment and alarm and
detection systems shall include, but not be limited
to, the following where such equipment or systems
are required to be provided either in this chapter
or else where in this code:
I. Automatic
fire sprinkler system alarm and monitoring
systems.
2. Manual
fire alarm systems.
3. Emergency
alarm systems.
4. Continuous
gas-detection systems.
5. Smoke
detection systems.
6. Emergency
power system.
7. Automatic
detection and alarm systems for pyrophoric liquids
and Class 3 water-reactive liquids
required in Section 1805.2.3.5
of the International Fire Code.
8. Exhaust
ventilation flow alarm devices for pyrophoric
liquids and Class 3 water-reactive liquids
cabinet exhaust ventilation systems required in
Section 1805.2.3.5
of the International Fire Code.
[F] 415.8.10
Emergency power system. An emergency power system
shall be provided in Group H-5 occupancies where required
in Section 415.8.10.1. The emergency power system shall
be designed to supply power automatically to required
electrical systems when the normal electrical supply
system is interrupted.
[F] 415.8.10.1
Required electrical systems. Emergency power shall
be provided for electrically operated equipment and
connected control circuits for the following systems:
1. HPM
exhaust ventilation systems.
2. HPM
gas cabinet ventilation systems.
3. HPM
exhausted enclosure ventilation systems.
4. HPM
gas room ventilation systems.
5. HPM
gas detection systems.
6. Emergency
alarm systems.
7. Manual
fire alarm systems.
8.
Automatic
sprinkler system monitoring and alarm systems.
9. Automatic
alarm and detection systems for pyrophoric liquids
and Class 3 water-reactive liquids required in
Section 1805.2.3.5
of the International Fire Code.
10. Flow
alarm switches for pyrophoric liquids and Class
3 water-reactive liquids cabinet exhaust ventilation
systems required in Section
1805.2.3.5 of the International Fire Code.
11. Electrically
operated systems required elsewhere in this code
or in the International Fire Code
applicable to the
use, storage or handling of HPM.
[F] 415.8.10.2
Exhaust ventilation systems. Exhaust ventilation
systems are allowed to be designed to operate at not
less than one-half the normal fan speed on the emergency
power system where it is demonstrated that the level
of exhaust will maintain a safe atmosphere.
[F] 415.8.11
Automatic sprinkler system protection in exhaust ducts
for RPM.
[F] 415.8.11.1 Exhaust
ducts for RPM. An approved automatic sprinkler
system shall be provided in exhaust ducts conveying
gases, vapors, fumes, mists or dusts generated
from HPM in accordance with this section and the
International Mechanical Code.
[F] 415.8.11.2 Metallic
and noncombustible nonmetallic exhaust ducts.
An approved automatic sprinkler system shall be
provided in metallic and noncombustible nonmetallic
exhaust ducts when all of the following conditions
apply:
1. Where
the largest cross-sectional diameter is equal
to or greater than 10 inches (254 mm).
2. The dusts
are within the building.
3. The
ducts are conveying flammable gases, vapors
or fumes.
[F] 415.8.11.3 Combustible
nonmetallic exhaust ducts. Automatic sprinkler
system protection shall be provided in combustible
nonmetallic exhaust ducts where the largest cross-sectional
diameter of the duct is equal to or greater than 10
inches (254 mm).
Exceptions:
1. Ducts listed
or approved for applications without automatic fire
sprinkler system protection.
2. Ducts not
more than 12 feet (3658 mm) in length installed below
ceiling level.
[F] 415.8.11.4
Automatic sprinkler locations. Sprinkler systems shall
be installed at 12-foot (3658 mm) intervals in horizontal
ducts and at changes in direction. In vertical ducts,
sprinklers shall be installed at the top and at alternate
floor levels.
|
|
|
All
Rights Reserved. This 2006 International Building Code® is a
copyrighted work owned by the International Code Council, Inc. Without
advance written permission from the copyright owner, no part of
this book may be reproduced, distributed, or transmitted in any
form or by any means, including, without limitation, electronic,
optical or mechanical means (by way of example and not limitation,
photocopying, or recording by or in an information storage retrieval
system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051West Flossmoor Road,
Country Club Hills, IL 60478-5795. Phone 1-888-ICC-SAFE (422-7233).
Trademarks: International Code Council, the International
Code Council logo and the International Building Code
are trademarks of the International Code Council, Inc.
|
|