SECTION
707 SHAFT ENCLOSURES
707.1
General. The provisions of this section shall apply to
vertical shafts where such shafts are required to protect
openings and penetrations through floor/ceiling and roof/ceiling
assemblies. Shaft enclosures shall be constructed as fire
barriers in accordance with Section 706
or horizontal assemblies in accordance with Section
711, or both.
707.2
Shaft enclosure required. Openings through a floor/ceiling
assembly shall be protected by a shaft enclosure complying
with this Section.
Exceptions:
1.
A shaft enclosure is not required for openings totally within
an individual residential dwelling unit and connecting four
stories or less.
2.
A shaft enclosure is not required in a building equipped
throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1 for an
escalator opening or stairway that is not a portion of the
means of egress protected according to Item 2.1 or 2.2:
2.1.
Where the area of the floor opening between stories does
not exceed twice the horizontal projected area of the
escalator or stairway and the opening is protected by
a draft curtain and closely spaced sprinklers in accordance
with NFP A 13. In other than Groups Band M, this application
is limited to openings that do not connect more than four
stories.
2.2.
Where the opening is protected by approved power-operated
automatic shutters at every penetrated floor. The shutters
shall be of noncombustible construction and have a fire-resistance
rating of not less than 1.5 hours. The shutter shall be
so constructed as to close immediately upon the actuation
of a smoke detector installed in accordance with Section
907.11 and shall completely shut off the well opening.
Escalators shall cease operation when the shutter begins
to close. The shutter shall operate at a speed of not
more than 30 feet per minute (152.4 mm/s) and shall be
equipped with a sensitive leading edge to arrest its progress
where in contact with any obstacle, and to continue its
progress on release there from.
3.
A shaft enclosure is not required for penetrations by pipe,
tube, conduit, wire, cable and vents protected in accordance
with Section 712.4.
4. A shaft enclosure is not required for penetrations
by ducts protected in accordance with Section
712.4. Grease ducts shall be protected in accordance
with the International Mechanical Code.
5. In other than Group H occupancies, a shaft
enclosure is not required for floor openings complying with
the provisions for atriums in Section
404.
6. A shaft enclosure is not required for approved
masonry chimneys where annular space protection is provided
at each floor level in accordance with Section
717.2.5.
7. In other than Groups I-2 and I-3, a shaft
enclosure is not required for a floor opening or an air
transfer opening that complies with the following:
7.1.
Does not connect more than two stories.
7.2. Is not part of the required means of egress system,
except as permitted in Section 1020.1.
7.3. Is not concealed within the building construction.
7.4. Is not open to a corridor in Group I and R occupancies.
7.5. Is not open to a corridor on non sprinklered floors
in any occupancy.
7.6. Is separated from floor openings and air transfer
openings serving other floors by construction conforming
to required shaft enclosures.
7.7. Is limited to the same smoke compartment.
8.
A shaft enclosure is not required for automobile ramps in
open and enclosed parking garages constructed in accordance
with Sections 406.3 and 406.4,
respectively.
9. A shaft enclosure is not required for floor
openings between a mezzanine and the floor below.
10. A shaft enclosure is not required for joints protected
by a fire-resistant joint system in accordance with Section
713.
11. A shaft enclosure shall not be required for floor openings
created by unenclosed stairs or ramps in accordance with
Exception 8 or 9 in Section 1020.1.
12. Floor openings protected by floor fire doors in accordance
with Section 711.8.
13. Where permitted by other sections of this code.
707.3 Materials. The shaft
enclosure shall be of materials permitted by the building
type of construction.
707.4
Fire-resistance rating. Shaft enclosures shall have a
fire-resistance rating of not less than 2 hours where connecting
four stories or more, and not less than 1 hour where connecting
less than four stories. The number of stories connected by
the shaft enclosure shall include any basements but not any
mezzanines. Shaft enclosures shall have a fire-resistance
rating not less than the floor assembly penetrated, but need
not exceed 2 hours.
707.5 Continuity. Shaft
enclosures shall be constructed as fire barriers in accordance
with Section 706 or horizontal assemblies
constructed in accordance with Section 711,
or both, and shall have continuity in accordance with Section
706.5 for fire barriers or Section
711.4 for horizontal assemblies as applicable.
707.6 Exterior walls.
Where exterior walls serve as a part of a required shaft enclosure,
such walls shall comply with the requirements of Section
704 for exterior walls and the fire-resistance-rated enclosure
requirements shall not apply.
Exception:
Exterior walls required to be fire-resistance rated in
accordance with Section 1014.5.1
for exterior egress balconies, Section
1020.1.4 for exit enclosures and Section
1023.6 for exterior exit ramps and stairways.
707.7
Openings. Openings in a shaft enclosure shall be protected
in accordance with Section 715 as required
for fire barriers. Doors shall be self- or automatic closing
by smoke I detection in accordance with Section
715.3.7.3.
707.7.1
Prohibited openings. Openings other than those necessary
for the purpose of the shaft shall not be permitted in shaft
enclosures.
707.8 Penetrations. Penetrations
in a shaft enclosure shall be protected in accordance with
Section 712 as required for fire barriers.
707.8.1
Prohibited penetrations. Penetrations other than those
necessary for the purpose of the shaft shall not be permitted
in shaft enclosures.
707.9
Joints. Joints in a shaft enclosure shall comply with
Section 713.
707.10
Ducts and air transfer openings. Penetrations of a shaft
enclosure by ducts and air transfer openings shall comply
with Section 716.
707.11
Enclosure at the bottom. Shafts that do not extend to
the bottom of the building or structure shall:
1.
Be enclosed at the lowest level with construction of the
same fire-resistance rating as the lowest floor through
which the shaft passes, but not less than the rating required
for the shaft enclosure;
2. Terminate
in a room having a use related to the purpose of the shaft.
The room shall be separated from the remainder of the building
by a fire barrier having a fire-resistance rating and opening
protectives at least equal to the protection required for
the shaft enclosure; or
3.
Be protected by approved fire dampers installed in accordance
with their listing at the lowest floor level within the
shaft enclosure.
Exceptions:
1.
The fire-resistance-rated room separation is not required,
provided there are no openings in or penetrations of the
shaft enclosure to the interior of the building except
at the bottom. The bottom of the shaft shall be closed off
around the penetrating items with materials permitted by
Section 717.3.1 for drafts topping,
or the room shall be provided with an approved automatic
fire suppression system.
2. A
shaft enclosure containing a refuse chute or laundry chute
shall not be used for any other purpose and shall terminate
in a room protected in accordance with Section 707.13.4.
3.
The fire-resistance-rated room separation and the protection
at the bottom of the shaft are not required, provided there
are no combustibles in the shaft and there are no openings
or other penetrations through the shaft enclosure to the
interior of the building.
707.12 Enclosure at the top.
A shaft enclosure that does not extend to the underside of
the roof sheathing, deck or slab of the building shall be
enclosed at the top with construction of the same fire-resistance
rating as the topmost floor penetrated by the shaft, but not
less than the fire-resistance rating required for the shaft
enclosure.
707.13
Refuse and laundry chutes. Refuse and laundry chutes,
access and termination rooms and incinerator rooms shall meet
the requirements of Sections 707.13.1 through 707.13.6.
Exception:
Chutes serving and contained within a single dwelling unit.
707.13.1
Refuse and laundry chute enclosures. A shaft enclosure
containing a refuse or laundry chute shall not be used for
any other purpose and shall be enclosed in accordance with
Section 707.4. Openings into the shaft, including those
from access rooms and termination rooms, shall be protected
in accordance with this section and Section
715. Openings into chutes shall not be located in corridors.
Doors shall be self- or automatic closing upon the actuation
of a smoke detector in accordance with Section
715.4.7.3, except that heat -activated closing devices
shall be permitted between the shaft and the termination
room.
707.13.2
Materials. A shaft enclosure containing a refuse or
laundry chute shall be constructed of materials as permitted
by the building type of construction.
707.13.3
Refuse and laundry chute access rooms. Access openings
for refuse and laundry chutes shall be located in rooms
or compartments enclosed by a fire barrier that has a fire-resistance
rating of not less than 1 hour. Openings into the access
rooms shall be protected by opening protectives having afire
protection rating of not less than 3/4
hour. Doors shall be self- or automatic closing upon the
detection of smoke in accordance with Section
715.4.7.3.
707.13.4
Termination room. Refuse and laundry chutes shall discharge
into an enclosed room separated from the remainder of the
building by a fire barrier that has a fire-resistance rating
of not less than 1 hour. Openings into the termination room
shall be protected by opening protectives having a fire
protection rating of not less than 3/4
hour. Doors shall be self- or automatic closing upon the
detection of smoke in accordance with Section
715.4.7.3. Refuse chutes shall not terminate in an incinerator
room. Refuse and laundry rooms that are not provided with
chutes need only comply with Table
508.2.
707.13.5
Incinerator room. Incinerator rooms shall comply with
Table 508.2.
707.13.6
Automatic sprinkler system. An approved automatic sprinkler
system shall be installed in accordance with Section
903.2.10.2.
707.14
Elevator, dumbwaiter and other hoistways. Elevator, dumbwaiter
and other hoistway enclosures shall be constructed in accordance
with Section 707 and Chapter 30.
707.14.1
Elevator lobby. An enclosed elevator lobby shall I be
provided at each floor where an elevator shaft enclosure
connects more than three stories. The lobby shall separate
the elevator shaft enclosure doors from each floor by fire
partitions equal to the fire-resistance rating of the corridor
and the required opening protection. Elevator lobbies shall
have at least one means of egress complying with Chapter
10 and other provisions within this code.
Exceptions:
1.
Enclosed elevator lobbies are not required at the I street
floor, provided the entire street floor is equipped with
an automatic sprinkler system in accordance with Section
903.3.1.1.
2.
Elevators not required to be located in a shaft in accordance
with Section 707.2 are not required to have enclosed elevator
lobbies.
3.
Where additional doors are provided at the hoistway opening
in accordance with Section 3002.6.
Such doors shall be tested in accordance with UL 1784
without an artificial bottom seal.
4.
In other than Group 1-3, and buildings having occupied
floors located more than 75 feet (22 860 mm) above the
lowest level of fire department vehicle access, enclosed
elevator lobbies are not required where the building is
protected by an automatic sprinkler system installed in
accordance with Section 903.3.1.1
or 903.3.1.2.
5.
Smoke partitions shall be permitted in lieu of fire partitions
to separate the elevator lobby at each floor where the
building is equipped throughout with an automatic sprinkler
system installed in accordance with Section
903.3.1.1 or 903.3.1.2.
6.
Enclosed elevator lobbies are not required where the elevator
hoistway is pressurized in accordance with Section 707.14.2.
707.14.2
Enclosed elevator lobby pressurization alternative.
Where elevator hoistway pressurization is provided in lieu
of required enclosed elevator lobbies, the pressurization
system shall comply with this section.
707.14.2.1 Pressurization requirements. Elevator
hoistways shall be pressurized to maintain a minimum positive
pressure of 0.04 inches of water column and a maximum
positive pressure of 0.06 inches of water column with
respect to adjacent occupied space on all floors. This
pressure shall be measured at the midpoint of each hoistway
door, with all ground floor level hoistway doors open
and all other hoistway doors closed. The supply air intake
shall be from an outside, uncontaminated source located
a minimum distance of 20 feet (6096 mm) from any air exhaust
system or outlet.
707.14.2.2 Ducts for system. Any duct system that
is part of the pressurization system shall be protected
with the same fire-resistance rating as required for the
elevator shaft enclosure.
707.14.2.3
Fan system. The fan system provided for the pressurization
system shall be as required by this section.
707.14.2.3.1
Fire resistance. When located within the building,
the fan system that provides the pressurization shall
be protected with the same fire-resistance rating required
for the elevator shaft enclosure.
707.14.2.3.2
Smoke detection. The fan system shall be equipped
with a smoke detector that will automatically shut down
the fan system when smoke is detected within the system.
707.14.2.3.3
Separate systems. A separate fan system shall be
used for each bank of elevators.
707.14.2.3.4 Fan capacity.
The supply fan shall either be adjustable with a capacity
of at least 1,000 cfm (.4719 m3/s) per door,
or that specified by a registered design professional
to meet the requirements of a designed pressurization
system.
707.14.2.4 Standby power. The pressurization system
shall be provided with standby power from the same source
as other required emergency systems for the building.
707.14.2.5 Activation of pressurization system.
The elevator pressurization system shall be activated
upon activation of the building fire alarm system or upon
activation of the elevator lobby smoke detectors.
|