|
SECTION 508 MIXED USE AND OCCUPANCY
508.1 General.
Where a building or portion thereof contains two or more occupancies
or uses, the building or portion thereof shall comply with
the applicable provisions of this section.
508.2
Incidental uses. Incidental use areas shall comply with
the provisions of this section.
Exception: Incidental
use areas within and serving a dwelling unit are not required
to comply with this section.
508.2.1 Occupancy classification.
An incidental use area shall be classified in accordance
with the occupancy of that portion of the building in which
it is located or the building shall be classified as a mixed
occupancy and shall comply with Section 508.3.
508.2.2 Separation.
Incidental use areas shall be separated or protected, or
both, in accordance with Table
508.2.
508.2.2.1 Construction.
Where Table 508.2 requires
a fire-resistance-rated separation, the incidental use
area shall be separated from the remainder of the building
by a fire barrier constructed in accordance with Section
706 or a horizontal assembly constructed in accordance
with Section 711, or both. Where
Table 508.2 permits an automatic
fire-extinguishing system without a fire barrier, the
incidental use area shall be separated from the remainder
of the building by construction capable of resisting the
passage of smoke. The partitions shall extend from the
floor to the underside of the fire-resistance-rated floor/ceiling
assembly or fire-resistance-rated roof/ceiling assembly
above or to the underside of the floor or roof sheathing,
or sub deck above. Doors shall be self- or automatic closing
upon detection of smoke. Doors shall not have air transfer
openings and shall not be undercut in excess of the clearance
permitted in accordance with NFPA80.
508.2.3 Protection.
Where an automatic fire-extinguishing system or an automatic
sprinkler system is provided in accordance with Table
508.2, only the incidental use areas need be equipped
with such a system.
508.3 Mixed occupancies.
Each portion of a building shall be individually classified
in accordance with Section 302.1.
Where
a building contains more than one occupancy group, the building
or portion thereof shall comply with Sections 508.3.1, 508.3.2,
508.3.3 or a combination of these sections.
Exceptions:
1.
Occupancies separated in accordance with
Section 509.
2.
Where required by Table 415.3.2,
areas of Group H -1, H - 2 or H - 3 occupancies shall
be located in a separate and detached building or structure.
508.3.1 Accessory occupancies.
Accessory occupancies are those occupancies subsidiary to
the main occupancy of the building or portion thereof. Aggregate
accessory occupancies shall not occupy more than 10 percent
of the area of the story in which they are located and shall
not exceed the tabular values in Table
503, without height and area increases in accordance
with Sections 504 and 506
for such accessory occupancies.
Exceptions:
1. Accessory assembly areas having a floor area less
than 750 square feet (69.7 m2) are not considered
separate occupancies.
2. Assembly areas that are accessory to Group E occupancies
are not considered separate occupancies except when applying
the assembly occupancy requirements of Chapter 11.
3.Accessory
religious educational rooms and religious auditoriums with
occupant loads of less than 100 are not considered separate
occupancies.
508.3.1.1 Occupancy classification. Accessory occupancies
shall be individually classified in accordance with Section
302.1. Code requirements shall apply to each portion
of the building based on the occupancy classification
of that accessory space, except that the most restrictive
applicable provisions of Section 403
and Chapter 9 shall apply to the entire building or portion
thereof.
508.3.1.2 Allowable area and height. The allowable
area and height of the building shall be based on the
allowable area and height for the main occupancy in accordance
with Section 503.1. The height
of any accessory occupancy shall not exceed the tabular
values in Table 503, without
height and area increases in accordance with Sections
504 and 506 for such accessory
occupancies.
508.3.1.3 Separation. No separation is required
between accessory occupancies or the main occupancy.
Exception: Group H-2, H-3, H-4 or
H-5 occupancies shall be separated from all other occupancies
in accordance with Section 508.3.3.
508.3.2 Nonseparated occupancies. Buildings or portions
of buildings that comply with the provisions of this section
shall qualify as nonseparated occupancies.
508.3.2.1 Occupancy classification. Nonseparated
occupancies shall be individually classified in accordance
with Section 302.1. Code requirements
shall apply to each portion of the building based on the
occupancy classification of that space except that the
most restrictive applicable provisions of Section
403 and Chapter 9 shall apply to the entire building
or portion thereof.
508.3.2.2 Allowable area and height. The allowable
area and height of the building or portion thereof shall
be based on the most restrictive allowances for the occupancy
groups under consideration for the type of construction
of the building in accordance with Section
503.1.
508.3.2.3 Separation. No separation is required
between occupancies.
Exception: Group H-2, H-3, H-4 or
H-5 occupancies shall be separated from all other occupancies
in accordance with Section 508.3.3.
508.3.3 Separated occupancies.
Buildings or portions of buildings that comply with the
provisions of this section shall qualify as separated occupancies.
508.3.3.1 Occupancy classification. Separated occupancies
shall be individually classified in accordance with Section
302.1. Each fire area shall comply with this code
based on the occupancy classification of that portion
of the building.
508.3.3.2 Allowable area. In each story, the building
area shall be such that the sum of the ratios of the actual
floor area of each occupancy divided by the allowable
area of each occupancy shall not exceed one.
508.3.3.3 Allowable height. Each occupancy shall
comply with the height limitations based on the type of
construction of the building in accordance with Section
503.1. The height, in both feet and stories, of each
fire area shall be measured from grade plane. This measurement
shall include the height, in both feet and stories, of
intervening fire areas.
Exception: Special provisions permitted
by Section 509.
508.3.3.4
Separation. Individual occupancies shall be separated
from adjacent occupancies in accordance with Table
508.3.3
508.3.3.4.1
Construction. Required separations shall be fire
barriers constructed in accordance with Section
706 or horizontal assemblies constructed in accordance
with Section 711, or both, so
as to completely separate adjacent occupancies.
|