SECTION 403 HIGH-RISE
BUILDINGS
403.1 Applicability.
The provisions of this section shall apply to buildings
with an occupied floor located more than 75 feet (22
860 mm) above the lowest level of fire department vehicle
access.
Exception: The provisions
of this section shall not apply to the following buildings
and structures:
1. Airport traffic control
towers in accordance with Section
412.
2. Open parking garages
in accordance with Section 406.3.
3. Buildings with an
occupancy in Group A-5 in accordance with Section
303.1.
4. Low-hazard special
industrial occupancies in accordance with Section
503.1.1.
5. Buildings with an
occupancy in Group H-1, H-2 or H-3 in accordance with
Section 415.
[F] 403.2 Automatic
sprinkler system. Buildings and structures shall
be equipped throughout with an automatic sprinkler system
in accordance with Section 903.3.1.1
and a secondary water supply where required by Section
903.3.5.2.
Exception: An automatic
sprinkler system shall not be required in spaces or
areas of:
1. Open parking garages
in accordance with Section 406.3.
2. Telecommunications
equipment buildings used exclusively for telecommunications
equipment, associated electrical power distribution
equipment, batteries and standby engines, provided
that those spaces or areas are equipped throughout
with an automatic fire detection system in accordance
with Section 907.2 and are
separated from the remainder of the building by fire
barriers consisting of not less than 1-hour fire-resistance-rated
walls and 2-hour fire-resistance-rated floor/ceiling
assemblies.
403.3 Reduction in fire-resistance
rating. The fire-resistance-rating reductions listed
in Sections 403.3.1 and 403.3.2 shall be allowed in
buildings that have sprinkler control valves equipped
with supervisory initiating devices and water-flow initiating
devices for each floor.
403.3.1 Type of construction.
The following reductions in the minimum construction
type allowed in Table 601
shall be allowed as provided in Section 403.3:
1. For buildings not
greater than 420 feet (128 m) in height, Type IA
construction shall be allowed to be reduced to Type
I B.
Exception: The required
fire-resistance rating of columns supporting floors
shall not be allowed to be reduced.
2. In other than Groups
F-1, M and S-1, Type I B construction shall be allowed
to be reduced to Type II A.
3. The height and area
limitations of the reduced construction type shall
be allowed to be the same as for the original construction
type.
403.3.2 Shaft enclosures.
For buildings not greater than 420 feet (128 m) in
height, the required fire-resistance rating of the
fire barriers enclosing vertical shafts, other than
exit enclosures and elevator hoist way enclosures,
shall be reduced to 1 hour where automatic sprinklers
are installed within the shafts at the top and at
alternate floor levels.
403.4 Emergency escape
and rescue. Emergency escape and rescue openings
required by Section 1026 are
not required.
[F] 403.5 Automatic
fire detection. Smoke detection shall be provided
in accordance with Section
907.2.12.1.
[F] 403.6 Emergency
voice/alarm communication systems. An emergency
voice/alarm communication system shall be provided in
accordance with Section 907.2.12.2.
[F] 403.7 Fire department
communications system. A two-way fire department
communications system shall be provided for fire department
use in accordance with Section
907.2.12.3.
[F] 403.8 Fire command.
A fire command center complying with Section
911 shall be provided in a location approved by
the fire department.
403.9 Elevators.
Elevator operation and installation shall be in accordance
with Chapter 30.
[F] 403.10 Standby power.
A standby power system complying with Section
2702 shall be provided for standby power loads specified
in Section 403.10.2.
403.10.1 Special requirements
for standby power systems. If the standby system
is a generator set inside a building, the system shall
be located in a separate room enclosed with 2-hour
fire barriers constructed in accordance with Section
706 or horizontal assemblies constructed in accordance
with Section 711, or both. System
supervision with manual start and transfer features
shall be provided at the fire command center.
[F] 403.10.2 Standby
power loads. The following are classified as standby
power loads:
1. Power and lighting
for the fire command center required by Section
403.8;
2. Electrically powered
fire pumps; and
3. Ventilation and
automatic fire detection equipment for smoke proof
enclosures. Standby power shall be provided for
elevators in accordance with
Sections 1007.4 and 3003.
[F] 403.11 Emergency
power systems. An emergency power system complying
with Section 2702 shall be provided
for emergency power loads specified in Section 403.11.1.
[F] 403.11.1 Emergency
power loads. The following are classified as emergency
power loads:
1. Exit signs and means
of egress illumination required by Chapter 10;
2. Elevator car lighting;
3. Emergency voice/alarm
communications systems;
4. Automatic fire detection
systems; and
5. Fire alarm systems.
403.12 Stairway door
operation. Stairway doors other than the exit discharge
doors shall be permitted to be locked from stairway
side. Stairway doors that are locked from the stairway
side shall be capable of being unlocked simultaneously
without unlatching upon a signal from the fire command
center.
403.12.1 Stairway
communications system. A telephone or other two-way
communications system connected to an approved constantly
attended station shall be provided at not less than
every fifth floor in each required stairway where
the doors to the stairway are locked.
403.13 Smoke proof exit
enclosures. Every required stairway serving floors
more than 75 feet (22 860 mm) above the lowest level
of fire department vehicle access shall comply with
Sections 909.20 and 1020.1.7.
403.14 Seismic considerations.
For seismic considerations, see Chapter 16.
|