| SECTION 2308 CONVENTIONAL
LIGHT-FRAME CONSTRUCTION
2308.1 General. The requirements
of this section are intended for conventional light-frame
construction. Other methods are permitted to be used, provided
a satisfactory design is submitted showing compliance with
other provisions of this code. Interior nonload-bearing partitions,
ceilings and curtain walls of conventional light-frame construction
are not subject to the limitations of this section. Alternatively,
compliance with AF&PA WFCM shall be permitted subject
to the limitations therein and the limitations of this code.
Detached one- and two-family dwellings and multiple single-family
dwellings (townhouses) not more than three stories above grade
plane in height with a separate means of egress and their
accessory structures shall comply with the International Residential
Code.
2308.1.1 Portions exceeding
limitations of conventional construction. When portions
of a building of otherwise conventional construction exceed
the limits of Section 2308.2, these portions and the supporting
load path shall be designed in accordance with accepted
engineering practice and the provisions of this code. For
the purposes of this section, the term portions
shall mean parts of buildings containing volume and area
such as a room or a series of rooms.
2308.2 Limitations. Buildings
are permitted to be constructed in accordance with the provisions
of conventional light-frame construction, subject to the following
limitations, and to further limitations of Sections 2308.11
and 2308.12.
1. Buildings shall be limited
to a maximum of three stories above grade. For the purposes
of this section, for buildings in Seismic Design Category
D or E as determined in Section 1613,
cripple stud walls shall be considered to be a story.
Exception: Solid blocked
cripple walls not exceeding 14 inches (356 mm) in height need
not be considered a story.
2. Bearing wall floor-to-floor
heights shall not exceed a stud height of 10 feet (3048
mm) plus a height of floor framing not to exceed 16 inches
(406 mm).
3. Loads as determined in Chapter
16 shall not exceed the following:
3.1. Average dead loads shall
not exceed 15 psf (718 N/m2) for combined roof
and ceiling, exterior walls, floors and partitions.
Exceptions:
1. Subject to the limitations
of Sections 2308.11.2 and 2308.12.2, stone or masonry
veneer up to the lesser of 5 inches (127 mm) thick or
50 psf (2395 N/m2) and installed in accordance
with Chapter 14 is permitted to a height of 30 feet (9144
mm) above a noncombustible foundation, with an additional
8 feet (2438 mm) permitted for gable ends.
2. Concrete or masonry fireplaces,
heaters and chimneys shall be permitted in accordance
with the provisions of this code.
3.2. Live loads shall not
exceed 40 psf (1916 N/m2) for floors.
3.3. Ground snow loads
shall not exceed 50 psf (2395 N/m2).
4. Wind speeds shall not
exceed 100 miles per hour (mph) (44 m/s) (3-second gust).
Exception: Wind speeds
shall not exceed 110 mph (48.4 m/s) (3-second gust) for buildings
in Exposure Category B.
5. Roof trusses and rafters
shall not span more than 40 feet (12 192 mm) between points
of vertical support.
6. The use of the provisions
for conventional light-frame construction in this section
shall not be permitted for Occupancy Category IV buildings
assigned to Seismic Design Category B, C, D, E or F, as
determined in Section 1613.
7. Conventional light-frame
construction is limited in irregular structures in Seismic
Design Category D or E, as specified in Section 2308.12.6.
2308.2.1 Basic wind speed
greater than 100 mph (3-second gust). Where the basic
wind speed exceeds 100 mph (3-second gust), the provisions
of either AF& PAWFCM, or the SBCCI SSTD 10 are permitted
to be used.
2308.2.2 Buildings in Seismic
Design Category B, C ,D or E. Buildings of conventional
light-frame construction in Seismic Design Category B or
C, as determined in Section 1613,
shall comply with the additional requirements in Section
2308.11. Buildings of conventional light-frame construction
in Seismic Design Category D or E, as determined in Section
1613, shall comply with the additional requirements
in Section 2308.12.
2308.3 Braced wall lines.
Buildings shall be provided with exterior and interior braced
wall lines as described in Section 2308.9.3 and installed
in accordance with Sections 2308.3.1 through 2308.3.4.
2308.3.1 Spacing. Spacing
of braced wall lines shall not exceed 35 feet (10 668 mm)
o.c. in both the longitudinal and transverse directions
in each story.
2308.3.2 Braced wall panel
connections. Forces shall be transferred from the roofs
and floors to braced wall panels and from the braced wall
panels in upper stories to the braced wall panels in the
story below by the following:
1. Braced wall panel top
and bottom plates shall be fastened to joists, rafters
or full-depth blocking. Braced wall panels shall be extended
and fastened to roof framing at intervals not to exceed
50 feet (15 240 mm) between parallel braced wall lines.
Exception: Where roof
trusses are used, lateral forces shall be transferred from
the roof diaphragm to the braced wall by blocking of the ends
of the trusses or by other approved methods.
2. Bottom plate fastening
to joist or blocking below shall be with not less than
3-16d nails at 16 inches (406 mm) o.c.
3. Blocking shall be nailed
to the top plate below with not less than 3-8d toenails
per block.
4. Joists parallel to the
top plates shall be nailed to the top plate with not less
than 8d toenails at 6 inches (152 mm) o.c. In addition,
top plate laps shall be nailed with not less than 8-16d
face nails on each side of each break in the top plate.
2308.3.3 Sill anchorage.
Where foundations are required by Section 2308.3.4, braced
wall line sills shall be anchored to concrete or masonry
foundations. Such anchorage shall conform to the requirements
of Section 2308.6 except that such anchors shall be spaced
at not more than 4 feet (1219 mm) o.c. for structures over
two stories in height. The anchors shall be distributed
along the length of the braced wall line. Other anchorage
devices having equivalent capacity are permitted.
2308.3.3.1 Anchorage to
all-wood foundations. Where all-wood foundations are
used, the force transfer from the braced wall lines shall
be determined based on calculation and shall have a capacity
greater than or equal to the connections required by Section
2308.3.3.
2308.3.4 Braced wall line
support. Braced wall lines shall be supported by continuous
foundations.
Exception: For structures
with a maximum plan dimension not over 50 feet (15 240 mm),
continuous foundations are required at exterior walls only.
2308.4 Design of elements.
Combining of engineered elements or systems and conventionally
specified elements or systems is permitted subject to the
following limits:
2308.4.1 Elements exceeding
limitations of conventional construction. When a building
of otherwise conventional construction contains structural
elements exceeding the limits of Section 2308.2, these elements
and the supporting load path shall be designed in accordance
with accepted engineering practice and the provisions of
this code.
2308.4.2 Structural elements
or systems not described herein. When a building of
otherwise conventional construction contains structural
elements or systems not described in Section 2308, these
elements or systems shall be designed in accordance with
accepted engineering practice and the provisions of this
code. The extent of such design need only demonstrate compliance
of the nonconventional elements with other applicable provisions
of this code and shall be compatible with the performance
of the conventionally framed system.
2308.5 Connections and fasteners.
Connections and fasteners used in conventional construction
shall comply with the requirements of Section
2304.9.
2308.6 Foundation plates or
sills. Foundations and footings shall be as specified
in Chapter 18. Foundation plates or sills resting on concrete
or masonry foundations shall comply with Section
2304.3.1. Foundation plates or sills shall be bolted or
anchored to the foundation with not less than 1/2-inch-diameter
(12.7 mm) steel bolts or approved anchors. Bolts shall be
embedded at least 7 inches (178 mm) into concrete or masonry,
and spaced not more than 6 feet (1829 mm) apart. There shall
be a minimum of two bolts or anchor straps per piece with
one bolt or anchor strap located not more than 12 inches (305
mm) or less than 4 inches (102 mm) from each end of each piece.
A properly sized nut and washer shall be tightened on each
bolt to the plate.
2308.7 Girders. Girders
for single-story construction or girders supporting loads
from a single floor shall not be less than 4 inches by 6 inches
(102 mm by 152 mm) for spans 6 feet (1829 mm) or less, provided
that girders are spaced not more than 8 feet (2438 mm) o.c.
Spans for built-up 2-inch (51 mm) girders shall be in accordance
with Table 2308.9.5 or 2308.9.6.
Other girders shall be designed to support the loads specified
in this code. Girder end joints shall occur over supports.
Where a girder is spliced over a support, an adequate tie
shall be provided. The ends of beams or girders supported
on masonry or concrete shall not have less than 3 inches (76
mm) of bearing.
2308.8 Floor joists. Spans
for floor joists shall be in accordance with Table
2308.8(1) or 2308.8(2).
For other grades and or species, refer to the AF&PA Span
Tables for Joists and Rafters.
2308.8.1 Bearing. Except
where supported on a 1-inch by 4-inch (25.4 mm by 102 mm)
ribbon strip and nailed to the adjoining stud, the ends
of each joist shall not have less than 11/2
inches (38 mm) of bearing on wood or metal, or less than
3 inches (76 mm) on masonry.
2308.8.2 Framing details.
Joists shall be supported laterally at the ends and at each
support by solid blocking except where the ends of the joists
are nailed to a header, band or rim joist or to an adjoining
stud or by other means. Solid blocking shall not be less
than 2 inches (51mm) in thickness and the full depth of
the joist. Notches on the ends of joists shall not exceed
one-fourth the joist depth. Holes bored in joists shall
not be within 2 inches (51 mm) of the top or bottom of the
joist, and the diameter of any such hole shall not exceed
one-third the depth of the joist. Notches in the top or
bottom of joists shall not exceed one-sixth the depth and
shall not be located in the middle third of the span. Joist
framing from opposite sides of a beam, girder or partition
shall be lapped at least 3 inches (76 mm) or the opposing
joists shall be tied together in an approved manner. Joists
framing into the side of a wood girder shall be supported
by framing anchors or on ledger strips not less than 2 inches
by 2 inches (51 mm by 51 mm).
2308.8.2.1 Engineered
wood products. Cuts, notches and holes bored in trusses,
structural composite lumber, structural glue-laminated
members or I-joists are not permitted except where permitted
by the manufacturers recommendations or where the
effects of such alterations are specifically considered
in the design of the member by a registered design professional.
2308.8.3 Framing around
openings. Trimmer and header joists shall be doubled,
or of lumber of equivalent cross section, where the span
of the header exceeds 4 feet (1219 mm). The ends of header
joists more than 6 feet (1829 mm) long shall be supported
by framing anchors or joist hangers unless bearing on a
beam, partition or wall. Tail joists over 12 feet (3658
mm) long shall be supported at the header by framing anchors
or on ledger strips not less than 2 inches by 2 inches (51
mm by 51 mm).
2308.8.4 Supporting bearing
partitions. Bearing partitions parallel to joists shall
be supported on beams, girders, doubled joists, walls or
other bearing partitions. Bearing partitions perpendicular
to joists shall not be offset from supporting girders, walls
or partitions more than the joist depth unless such joists
are of sufficient size to carry the additional load.
2308.8.5 Lateral support.
Floor, attic and roof framing with a nominal depth-to-thickness
ratio greater than or equal to 5:1 shall have one edge held
in line for the entire span. Where the nominal depth-to-thickness
ratio of the framing member exceeds 6:1, there shall be
one line of bridging for each 8 feet (2438 mm) of span,
unless both edges of the member are held in line. The bridging
shall consist of not less than 1-inch by 3-inch (25mmby
76 mm) lumber, double nailed at each end, of equivalent
metal bracing of equal rigidity, full-depth solid blocking
or other approved means. A line of bridging shall also be
required at supports where equivalent lateral support is
not otherwise provided.
2308.8.6 Structural floor
sheathing. Structural floor sheathing shall comply with
the provisions of Section 2304.7.1.
2308.8.7 Under-floor ventilation.
For under-floor ventilation, see Section
1203.3.
2308.9 Wall framing.
2308.9.1 Size, height and
spacing. The size, height and spacing of studs shall
be in accordance with Table
2308.9.1 except that utility-grade studs shall not be
spaced more than 16 inches (406 mm) o.c., or support more
than a roof and ceiling, or exceed 8 feet (2438 mm) in height
for exterior walls and load-bearing walls or 10 feet (3048
mm) for interior nonload-bearing walls.
2308.9.2 Framing details.
Studs shall be placed with their wide dimension perpendicular
to the wall. Not less than three studs shall be installed
at each corner of an exterior wall.
Exception: At corners,
two studs are permitted, provided wood spacers or backup cleats
of 3/8-inch-thick (9.5 mm) wood structural
panel, 3/8-inch (9.5mm) Type M Exterior
Glue particleboard, 1-inch-thick (25 mm) lumber or other
approved devices that will serve as an adequate backing for
the attachment of facing materials are used. Where fire-resistance
ratings or shear values are involved, wood spacers, backup
cleats or other devices shall not be used unless specifically
approved for such use.
2308.9.2.1 Top plates.
Bearing and exterior wall studs shall be capped with double
top plates installed to provide overlapping at corners
and at intersections with other partitions. End joints
in double top plates shall be offset at least 48 inches
(1219 mm), and shall be nailed with not less than eight
16d face nails on each side of the joint. Plates shall
be a nominal 2 inches (51 mm) in depth and have a width
at least equal to the width of the studs.
Exception: A single top
plate is permitted, provided the plate is adequately tied
at joints, corners and intersecting walls by at least the
equivalent of 3-inch by 6-inch (76 mm by 152 mm) by 0.036-inch-thick
(0.914 mm) galvanized steel that is nailed to each wall or
segment of wall by six 8d nails or equivalent, provided the
rafters, joists or trusses are centered over the studs with
a tolerance of no more than 1 inch (25 mm).
2308.9.2.2 Top plates
for studs spaced at 24 inches (610 mm). Where bearing
studs are spaced at 24-inch (610 mm) intervals and top
plates are less than two 2-inch by 6-inch (51 mm by 152
mm) or two 3-inch by 4-inch (76mmby 102 mm) members and
where the floor joists, floor trusses or roof trusses
that they support are spaced at more than 16-inch (406
mm) intervals, such joists or trusses shall bear
within 5 inches (127 mm) of the studs beneath or a third
plate shall be installed.
2308.9.2.3 Nonbearing
walls and partitions. In nonbearing walls and partitions,
studs shall be spaced not more than 28 inches (711 mm)
o.c. and are permitted to be set with the long dimension
parallel to the wall. Interior nonbearing partitions shall
be capped with no less than a single top plate installed
to provide overlapping at corners and at intersections
with other walls and partitions. The plate shall be continuously
tied at joints by solid blocking at least 16 inches (406
mm) in length and equal in size to the plate or by 1/2-inch
by 11/2-inch (12.7 mm by 38 mm)
metal ties with spliced sections fastened with two 16d
nails on each side of the joint.
2308.9.2.4 Plates or sills.
Studs shall have full bearing on a plate or sill not
less than 2 inches (51 mm) in thickness having a width
not less than that of the wall studs.
2308.9.3 Bracing. Braced
wall lines shall consist of braced wall panels that meet
the requirements for location, type and amount of bracing
as shown in Figure 2308.9.3,
specified in Table 2308.9.3(1)
and are in line or offset from each other by not more than
4 feet (1219 mm). Braced wall panels shall start not more
than 121/2-feet (3810 mm) from each
end of a braced wall line. Braced wall panels shall be clearly
indicated on the plans. Construction of braced wall panels
shall be by one of the following methods:
1. Nominal 1-inch by 4-inch
(25 mm by 102 mm) continuous diagonal braces let into
top and bottom plates and intervening studs, placed
at an angle not more than 60 degrees (1.0 rad) or less
than 45 degrees (0.79 rad) from the horizontal and attached
to the framing in conformance with Table
2304.9.1.
2. Wood boards of 5/8
inch (15.9 mm) net minimum thickness applied diagonally
on studs spaced not over 24 inches (610 mm) o.c.
3. Wood structural panel
sheathing with a thickness not less than 5/16
inch (7.9 mm) for a 16-inch (406 mm) stud spacing and
not less than 3/8 inch (9.5 mm)
for a 24- inch (610 mm) stud spacing in accordance with
Tables 2308.9.3(2)
and 2308.9.3(3).
4. Fiberboard sheathing
panels not less than 1/2 inch
(12.7 mm) thick applied vertically or horizontally on
studs spaced not over 16 inches (406 mm) o.c. where
installed with fasteners in accordance with Section
2306.4.4 and Table
2306.4.4.
5. Gypsum board [sheathing
1/2-inch-thick (12.7 mm) by 4-feet-wide
(1219 mm) wallboard or veneer base] on studs spaced
not over 24 inches (610 mm) o.c. and nailed at 7 inches
(178 mm) o.c. with nails as required by Table
2306.4.5.
6. Particleboard wall sheathing
panels where installed in accordance with Table
2308.9.3(4).
7. Portland cement plaster
on studs spaced 16 inches (406 mm) o.c. installed in
accordance with Section 2510.
8. Hardboard panel siding
where installed in accordance with Section
2303.1.6 and Table
2308.9.3(5). For cripple wall bracing, see Section
2308.9.4.1. For Methods 2, 3, 4, 6, 7 and 8, each panel
must be at least 48 inches (1219 mm) in length, covering
three stud spaces where studs are spaced 16 inches (406
mm) apart and covering two stud spaces where studs are
spaced 24 inches (610 mm) apart. For Method 5, each
panel must be at least 96 inches (2438 mm) in length
where applied to one face of a panel and 48 inches (1219
mm) where applied to both faces. All vertical joints
of panel sheathing shall occur over studs and adjacent
panel joints shall be nailed to common framing members.
Horizontal joints shall occur over blocking or other
framing equal in size to the studding except where waived
by the installation requirements for the specific sheathing
materials. Sole plates shall be nailed to the floor
framing and top plates shall be connected to the framing
above in accordance with Section 2308.3.2. Where joists
are perpendicular to braced wall lines above, blocking
shall be provided under and in line with the braced
wall panels.
2308.9.3.1 Alternative
bracing. Any bracing required by Section 2308.9.3
is permitted to be replaced by the following:
1. In one-story buildings,
each panel shall have a length of not less than 2 feet
8 inches (813 mm) and a height of not more than 10 feet
(3048 mm). Each panel shall be sheathed on one face
with 3/8-inch-minimum-thickness (9.5 mm) wood structural
panel sheathing nailed with 8d common or galvanized
box nails in accordance with Table
2304.9.1 and blocked at wood structural panel edges.
Two anchor bolts installed in accordance with Section
2308.6 shall be provided in each panel. Anchor bolts
shall be placed at each panel outside quarter points.
Each panel end stud shall have a tie-down device fastened
to the foundation, capable of providing an approved
uplift capacity of not less than 1,800 pounds (8006
N). The tie-down device shall be installed in accordance
with the manufacturers recommendations. The panels
shall be supported directly on a foundation or on floor
framing supported directly on a foundation that is continuous
across the entire length of the braced wall line. This
foundation shall be reinforced with not less than one
No. 4 bar top and bottom.
Where the continuous
foundation is required to have a depth greater than
12 inches (305 mm), a minimum 12- inch by 12-inch (305
mm by 305 mm) continuous footing or turned down slab
edge is permitted at door openings in the braced wall
line. This continuous footing or turned down slab edge
shall be reinforced with not less than one No. 4 bar
top and bottom. This reinforcement shall be lapped 15
inches (381 mm) with the reinforcement required in the
continuous foundation located directly under the braced
wall line.
2. In the first story of
two-story buildings, each wall panel shall be braced
in accordance with Section 2308.9.3.1, Item 1, except
that the wood structural panel sheathing shall be provided
on both faces, three anchor bolts shall be placed at
one-quarter points, and tie-down device uplift capacity
shall not be less than 3,000 pounds (13 344 N).
2308.9.3.2 Alternate bracing
wall panel adjacent to a door or window opening. Any
bracing required by Section 2308.9.3 is permitted to be
replaced by the following when used adjacent to a door
or window opening with a full-length header:
1. In one-story buildings,
each panel shall have a length of not less than 16 inches
(406 mm) and a height of not more than 10 feet (3048
mm). Each panel shall be sheathed on one face with a
single layer of 3/8 inch (9.5
mm) minimum thickness wood structural panel sheathing
nailed with 8d common or galvanized box nails in accordance
with Figure 2308.9.3.2.
The wood structural panel sheathing shall extend up
over the solid sawn or glued-laminated header and shall
be nailed in accordance with Figure
2308.9.3.2. A built-up header consisting of at least
two 2 x 12s and fastened in accordance with Item 24
of Table 2304.9.1 shall
be permitted to be used. A spacer, if used, shall be
placed on the side of the built-up beam opposite the
wood structural panel sheathing. The header shall extend
between the inside faces of the first full-length outer
studs of each panel. The clear span of the header between
the inner studs of each panel shall be not less than
6 feet (1829 mm) and not more than 18 feet (5486 mm)
in length. A strap with an uplift capacity of not less
than 1,000 pounds (4,400 N) shall fasten the header
to the inner studs opposite the sheathing. One anchor
bolt not less than 5/8 inch (15.9
mm) diameter and installed in accordance with Section
2308.6 shall be provided in the center of each sill
plate. The studs at each end of the panel shall have
a tie-down device fastened to the foundation with an
uplift capacity of not less than 4,200 pounds (18 480
N). Where a panel is located on one side of the opening,
the header shall extend between the inside face of the
first full-length stud of the panel and the bearing
studs at the other end of the opening. A strap with
an uplift capacity of not less than 1,000 pounds (4400
N) shall fasten the header to the bearing studs. The
bearing studs shall also have a tie-down device fastened
to the foundation with an uplift capacity of not less
than 1,000 pounds (4400 N). The tie-down devices shall
be an embedded strap type, installed in accordance with
the manufacturers recommendations. The panels
shall be supported directly on a foundation that is
continuous across the entire length of the braced wall
line. This foundation shall be reinforced with not less
than one No. 4 bar top and bottom.
Where the continuous foundation
is required to have a depth greater than 12 inches (305
mm), a minimum 12-inch by 12-inch (305 mm by 305 mm)
continuous footing or turned down slab edge is permitted
at door openings in the braced wall line. This continuous
footing or turned down slab edge shall be reinforced
with not less than one No. 4 bar top and bottom. This
reinforcement shall be lapped not less than 15 inches
(381 mm) with the reinforcement required in the continuous
foundation located directly under the braced wall line.
2. In the first story of
two-story buildings, each wall panel shall be braced
in accordance with Item 1 above, except that each panel
shall have a length of not less than 24 inches (610
mm).
2308.9.4 Cripple walls.
Foundation cripple walls shall be framed of studs not less
in size than the studding above with a minimum length of
14 inches (356 mm), or shall be framed of solid blocking.
Where exceeding 4 feet (1219 mm) in height, such walls shall
be framed of studs having the size required for an additional
story.
2308.9.4.1 Bracing.
For the purposes of this section, cripple walls having
a stud height exceeding 14 inches (356 mm) shall be considered
a story and shall be braced in accordance with Table
2308.9.3(1) for Seismic Design Category A, B or C.
See Section 2308.12.4 for Seismic Design Category D or
E.
2308.9.4.2 Nailing of
bracing. Spacing of edge nailing for required wall
bracing shall not exceed 6 inches (152 mm) o.c. along
the foundation plate and the top plate of the cripple
wall. Nail size, nail spacing for field nailing and more
restrictive boundary nailing requirements shall be as
required elsewhere in the code for the specific bracing
material used.
2308.9.5 Openings in exterior
walls.
2308.9.5.1 Headers.
Headers shall be provided over each opening in exterior-bearing
walls. The spans in Table
2308.9.5 are permitted to be used for one- and two-family
dwellings. Headers for other buildings shall be designed
in accordance with Section 2301.2,
Item 1 or 2. Headers shall be of two pieces of nominal
2-inch (51 mm) framing lumber set on edge as permitted
by Table 2308.9.5 and
nailed together in accordance with Table
2304.9.1 or of solid lumber of equivalent size.
2308.9.5.2 Header support.
Wall studs shall support the ends of the header in accordance
with Table 2308.9.5.
Each end of a lintel or header shall have a length of
bearing of not less than 11/2 inches
(38 mm) for the full width of the lintel.
2308.9.6 Openings in interior
bearing partitions. Headers shall be provided over each
opening in interior bearing partitions as required in Section
2308.9.5. The spans in Table
2308.9.6 are permitted to be used. Wall studs shall
support the ends of the header in accordance with Table
2308.9.5 or 2308.9.6, as appropriate.
2308.9.7 Openings in interior
nonbearing partitions. Openings in nonbearing partitions
are permitted to be framed with single studs and headers.
Each end of a lintel or header shall have a length of bearing
of not less than 11/2 inches (38 mm)
for the full width of the lintel.
2308.9.8 Pipes in walls.
Stud partitions containing plumbing, heating or other pipes
shall be so framed and the joists underneath so spaced as
to give proper clearance for the piping. Where a partition
containing such piping runs parallel to the floor joists,
the joists underneath such partitions shall be doubled and
spaced to permit the passage of such pipes and shall be
bridged. Where plumbing, heating or other pipes are placed
in or partly in a partition, necessitating the cutting of
the soles or plates, a metal tie not less than 0.058 inch
(1.47 mm) (16 galvanized gage) and 11/2
inches (38 mm) wide shall be fastened to each plate across
and to each side of the opening with not less than six 16d
nails.
2308.9.9 Bridging. Unless
covered by interior or exterior wall coverings or sheathing
meeting the minimum requirements of this code, stud partitions
or walls with studs having a height-to-least-thickness ratio
exceeding 50 shall have bridging not less than 2 inches
(51 mm) in thickness and of the same width as the studs
fitted snugly and nailed thereto to provide adequate lateral
support. Bridging shall be placed in every stud cavity and
at a frequency such that no stud so braced shall have a
height-to- east-thickness ratio exceeding 50 with the height
of the stud measured between horizontal framing and bridging
or between bridging, whichever is greater.
2308.9.10 Cutting and notching.
In exterior walls and bearing partitions, any wood stud
is permitted to be cut or notched to a depth not exceeding
25 percent of its width. Cutting or notching of studs to
a depth not greater than 40 percent of the width of the
stud is permitted in nonbearing partitions supporting no
loads other than the weight of the partition.
2308.9.11 Bored holes. A
hole not greater in diameter than 40 percent of the stud
width is permitted to be bored in any wood stud. Bored holes
not greater than 60 percent of the width of the stud are
permitted in nonbearing partitions or in any wall where
each bored stud is doubled, provided not more than two such
successive doubled studs are so bored. In no case shall
the edge of the bored hole be nearer than 5/8
inch (15.9 mm) to the edge of the stud. Bored holes shall
not be located at the same section of stud as a cut or notch.
2308.10 Roof and ceiling framing.
The framing details required in this section apply to
roofs having a minimum slope of three units vertical in 12
units horizontal (25- percent slope) or greater. Where the
roof slope is less than three units vertical in 12 units horizontal
(25-percent slope), members supporting rafters and ceiling
joists such as ridge board, hips and valleys shall be designed
as beams.
2308.10.1 Wind uplift.
Roof assemblies shall have rafter and truss ties to the
wall below. Resultant uplift loads shall be transferred
to the foundation using a continuous load path. The rafter
or truss to wall connection shall comply with Tables
2304.9.1 and 2308.10.1.
2308.10.2 Ceiling joist
spans. Allowable spans for ceiling joists shall be in
accordance with Table 2308.10.2(1)
or 2308.10.2(2). For
other grades and species, refer to the AF&PA Span Tables
for Joists and Rafters.
2308.10.3 Rafter spans.
Allowable spans for rafters shall be in accordance with
Table 2308.10.3(1),
2308.10.3(2), 2308.10.3(3),
2308.10.3(4), 2308.10.3(5)
or 2308.10.3 (6). For
other grades and species, refer to the AF&PA Span Tables
for Joists and Rafters.
2308.10.4 Ceiling joist
and rafter framing. Rafters shall be framed directly
opposite each other at the ridge. There shall be a ridge
board at least 1-inch (25 mm) nominal thickness at ridges
and not less in depth than the cut end of the rafter. At
valleys and hips, there shall be a single valley or hip
rafter not less than 2-inch (51 mm) nominal thickness and
not less in depth than the cut end of the rafter.
2308.10.4.1 Ceiling joist
and rafter connections. Ceiling joists and rafters
shall be nailed to each other and the assembly shall be
nailed to the top wall plate in accordance with Tables
2304.9.1 and 2308.10.1.
Ceiling joists shall be continuous or securely joined
where they meet over interior partitions and fastened
to adjacent rafters in accordance with Tables
2308.10.4.1 and 2304.9.1
to provide a continuous rafter tie across the building
where such joists are parallel to the rafters. Ceiling
joists shall have a bearing surface of not less than 11/2
inches (38 mm) on the top plate at each end. Where ceiling
joists are not parallel to rafters, an equivalent rafter
tie shall be installed in a manner to provide a continuous
tie across the building, at a spacing of not more than
4 feet (1219 mm) o.c. The connections shall be in accordance
with Tables 2308.10.4.1
and 2304.9.1, or connections
of equivalent capacities shall be provided. Where ceiling
joists or rafter ties are not provided at the top of the
rafter support walls, the ridge formed by these rafters
shall also be supported by a girder conforming to Section
2308.4. Rafter ties shall be spaced not more than 4 feet
(1219 mm) o.c. Rafter tie connections shall be based on
the equivalent rafter spacing in Table
2308.10.4.1. Where rafter ties are spaced at 32 inches
(813 mm) o.c., the number of 16d common nails shall be
two times the number specified for rafters spaced 16 inches
(406 mm) o.c., with a minimum of 4-16d common nails where
no snow loads are indicated. Where rafter ties are spaced
at 48 inches (1219 mm) o.c., the number of 16d common
nails shall be two times the number specified for rafters
spaced 24 inches (610 mm) o.c., with a minimum of 6-16d
common nails where no snow loads are indicated. Rafter/ceiling
joist connections and rafter/tie connections shall be
of sufficient size and number to prevent splitting from
nailing.
2308.10.4.2 Notches and
holes. Notching at the ends of rafters or ceiling
joists shall not exceed one-fourth the depth. Notches
in the top or bottom of the rafter or ceiling joist shall
not exceed one-sixth the depth and shall not be located
in the middle one-third of the span, except that a notch
not exceeding one-third of the depth is permitted in the
top of the rafter or ceiling joist not further from the
face of the support than the depth of the member. Holes
bored in rafters or ceiling joists shall not be within
2 inches (51 mm) of the top and bottom and their diameter
shall not exceed one-third the depth of the member.
2308.10.4.3 Framing around
openings. Trimmer and header rafters shall be doubled,
or of lumber of equivalent cross section, where the span
of the header exceeds 4 feet (1219 mm). The ends of header
rafters more than 6 feet (1829 mm) long shall be supported
by framing anchors or rafter hangers unless bearing on
a beam, partition or wall.
2308.10.5 Purlins. Purlins
to support roof loads are permitted to be installed to reduce
the span of rafters within allowable limits and shall be
supported by struts to bearing walls. The maximum span of
2-inch by 4-inch (51mmby 102 mm) purlins shall be 4 feet
(1219 mm). The maximum span of the 2-inch by 6-inch (51
mm by 152 mm) purlin shall be 6 feet (1829 mm), but in no
case shall the purlin be smaller than the supported rafter.
Struts shall not be smaller than 2-inch by 4-inch (51 mm
by 102 mm) members. The unbraced length of struts shall
not exceed 8 feet (2438 mm) and the minimum slope of the
struts shall not be less than 45 degrees (0.79 rad) from
the horizontal.
2308.10.6 Blocking.
Roof rafters and ceiling joists shall be supported laterally
to prevent rotation and lateral displacement in accordance
with the provisions of Section 2308.8.5.
2308.10.7 Engineered wood
products. Prefabricated wood I-joists, structural glued-laminated
timber and structural composite lumber shall not be notched
or drilled except where permitted by the manufacturers
recommendations or where the effects of such alterations
are specifically considered in the design of the member
by a registered design professional.
2308.10.8 Roof sheathing.
Roof sheathing shall be in accordance with Tables
2304.7(3) and 2304.7(5)
for wood structural panels, and Tables
2304.7(1) and 2304.7(2)
for lumber and shall comply with Section
2304.7.2.
2308.10.8.1 Joints.
Joints in lumber sheathing shall occur over supports unless
approved end-matched lumber is used, in which case each
piece shall bear on at least two supports.
2308.10.9 Roof planking.
Planking shall be designed in accordance with the general
provisions of this code. In lieu of such design, 2-inch
(51 mm) tongue-and groove planking is permitted in accordance
with Table 2308.10.9.
Joints in such planking are permitted to be randomly spaced,
provided the system is applied to not less than three continuous
spans, planks are center matched and end matched or splined,
each plank bears on at least one support, and joints are
separated by at least 24 inches (610 mm) in adjacent pieces.
2308.10.10 Wood trusses.
Wood trusses shall be designed in accordance with Section
2303.4.
2308.10.11 Attic ventilation.
For attic ventilation, see Section
1203.2.
2308.11 Additional requirements
for conventional construction in Seismic Design Category B
or C. Structures of conventional light-frame construction
in Seismic Design Category B or C, as determined in Section
1613, shall comply with Sections 2308.11.1 through 2308.11.3,
in addition to the provisions of Sections 2308.1 through 2308.10.
2308.11.1 Number of stories.
Structures of conventional light-frame construction shall
not exceed two stories in height in Seismic Design Category
C.
2308.11.2 Concrete or masonry.
Concrete or masonry walls or masonry veneer shall not extend
above the basement.
Exceptions:
1. Masonry veneer is permitted
to be used in the first two stories above grade plane
or the first three stories above grade plane where the
lowest story has concrete or masonry walls in Seismic
Design Category B, provided that structural use panel
wall bracing is used and the length of bracing provided
is one- and one-half times the required length as determined
in Table 2308.9.3(1).
2. Masonry veneer is permitted
to be used in the first story above grade plane or the
first two stories above grade plane where the lowest story
has concrete or masonry walls in Seismic Design Category
B or C.
3. Masonry veneer is permitted
to be used in the first two stories above grade plane
in Seismic Design Categories B and C, provided the following
criteria are met:
3.1. Type of brace per
Section 2308.9.3 shall be Method 3 and the allowable
shear capacity in accordance with Table
2306.4.1 shall be a minimum of 350 plf (5108 N/m)
3.2. The bracing of the
top story shall be located at each end and at least
every 25 feet (7620 mm) o.c. but not less than 40 percent
of the braced wall line. The bracing of the first story
shall be located at each end and at least every 25 feet
(7620 mm) o.c. but not less than 35 percent of the braced
wall line.
3.3. Hold-down connectors
shall be provided at the ends of braced walls for the
second floor to first floor wall assembly with an allowable
design of 2,000 pounds (8896 N) Hold-down connectors
shall be provided at the ends of each wall segment of
the braced walls for the first floor to foundation with
an allowable design of 3,900 pounds (17 347 N). In all
cases, the hold-down connector force shall be transferred
to the foundation.
3.4. Cripple walls shall
not be permitted.
2308.11.3 Framing and connection
details. Framing and connection details shall conform
to Sections 2308.11.3.1 through 2308.11.3.3.
2308.11.3.1 Anchorage.
Braced wall lines shall be anchored in accordance with
Section 2308.6 at foundations.
2308.11.3.2 Stepped footings.
Where the height of a required braced wall panel extending
from foundation to floor above varies more than 4 feet
(1219 mm), the following construction shall be used:
1. Where the bottom of
the footing is stepped and the lowest floor framing
rests directly on a sill bolted to the footings, the
sill shall be anchored as required in Section 2308.3.3.
2. Where the lowest floor
framing rests directly on a sill bolted to a footing
not less than 8 feet (2438 mm) in length along a line
of bracing, the line shall be considered to be braced.
The double plate of the cripple stud wall beyond the
segment of footing extending to the lowest framed floor
shall be spliced to the sill plate with metal ties,
one on each side of the sill and plate. The metal ties
shall not be less than 0.058 inch [1.47 mm (16 galvanized
gage)] by 1.5 inches (38 mm) wide by 48 inches (1219
mm) with eight 16d common nails on each side of the
splice location (see Figure
2308.11.3.2). The metal tie shall have a minimum
yield of 33,000 pounds per square inch (psi) (227 MPa).
3. Where cripple walls
occur between the top of the footing and the lowest
floor framing, the bracing requirements for a story
shall apply.
2308.11.3.3 Openings in
horizontal diaphragms. Openings in horizontal diaphragms
with a dimension perpendicular to the joist that is greater
than 4 feet (1.2 m) shall be constructed in accordance
with the following:
1. Blocking shall be provided
beyond headers.
2. Metal ties not less
than 0.058 inch [1.47 mm (16 galvanized gage)] by 1.5
inches (38 mm) wide with eight 16d common nails on each
side of the header-joist intersection shall be provided
(see Figure 2308.11.3.3).
The metal ties shall have a minimum yield of 33,000
psi (227 MPa).
2308.12 Additional requirements
for conventional construction in Seismic Design Category D
or E. Structures of conventional light-frame construction
in Seismic Design Category D or E, as determined in Section
1613, shall conform to Sections 2308.12.1 through 2308.12.9,
in addition to the requirements for Seismic Design Category
B or C in Section 2308.11.
2308.12.1 Number of stories.
Structures of conventional light-frame construction shall
not exceed one story in height in Seismic Design Category
D or E.
2308.12.2 Concrete or masonry.
Concrete or masonry walls or masonry veneer shall not extend
above the basement.
Exception: Masonry veneer
is permitted to be used in the first story above grade plane
in Seismic Design Category D, provided the following criteria
are met:
1. Type of brace in accordance
with Section 2308.9.3 shall be Method 3 and the allowable
shear capacity in accordance with Table
2306.4.1 shall be a minimum of 350 plf (5108 N/m).
2. The bracing of the first
story shall be located at each end and at least every
25 feet (7620 mm) o.c. but not less than 45 percent of
the braced wall line.
3. Hold-down connectors shall
be provided at the ends of braced walls for the first
floor to foundation with an allowable design of 2,100
pounds (9341 N).
4. Cripple walls shall not
be permitted.
2308.12.3 Braced wall line
spacing. Spacing between interior and exterior braced
wall lines shall not exceed 25 feet (7620 mm).
2308.12.4 Braced wall line
sheathing. Braced wall lines shall be braced by one
of the types of sheathing prescribed by Table
2308.12.4 as shown in Figure
2308.9.3. The sum of lengths of braced wall panels at
each braced wall line shall conform to Table
2308.12.4. Braced wall panels shall be distributed along
the length of the braced wall line and start at not more
than 8 feet (2438 mm) from each end of the braced wall line.
Panel sheathing joints shall occur over studs or blocking.
Sheathing shall be fastened to studs, top and bottom plates
and at panel edges occurring over blocking. Wall framing
to which sheathing used for bracing is applied shall be
nominal 2 inch wide [actual 11/2 inch (38 mm)] or larger
members. Cripple walls having a stud height exceeding 14
inches (356 mm) shall be considered a story for the purpose
of this section and shall be braced as required for braced
wall lines in accordance with Table 2308.12.4. Where interior
braced wall lines occur without a continuous foundation
below, the length of parallel exterior cripple wall bracing
shall be one and one-half times the lengths required by
Table 2308.12.4. Where
the cripple wall sheathing type used is Type S-W and this
additional length of bracing cannot be provided, the capacity
of Type S-W sheathing shall be increased by reducing the
spacing of fasteners along the perimeter of each piece of
sheathing to 4 inches (102 mm) o.c.
2308.12.5 Attachment of
sheathing. Fastening of braced wall panel sheathing
shall not be less than that prescribed in Table
2308.12.4 or 2304.9.1.
Wall sheathing shall not be attached to framing members
by adhesives.
2308.12.6 Irregular structures.
Conventional light-frame construction shall not be used
in irregular portions of structures in Seismic Design Category
D or E. Such irregular portions of structures shall be designed
to resist the forces specified in Chapter 16 to the extent
such irregular features affect the performance of the conventional
framing system. A portion of a structure shall be considered
to be irregular where one or more of the conditions described
in Items 1 through 6 below are present.
1. Where exterior braced
wall panels are not in one plane vertically from the foundation
to the uppermost story in which they are required, the
structure shall be considered to be irregular [see Figure
2308.12.6(1)].
Exception: Floors with
cantilevers or setbacks not exceeding four times the nominal
depth of the floor joists [see Figure
2308.12.6(2)] are permitted to support braced wall panels
provided:
1. Floor joists are 2 inches
by 10 inches (51mm by 254 mm) or larger and spaced not
more than 16 inches (406 mm) o.c.
2. The ratio of the back
span to the cantilever is at least 2:1.
3. Floor joists at ends
of braced wall panels are doubled.
4. A continuous rim joist
is connected to the ends of cantilevered joists. The
rim joist is permitted to be spliced using a metal tie
not less than 0.058 inch (1.47 mm) (16 galvanized gage)
and 11/2 inches (38 mm) wide fastened with six 16d common
nails on each side. The metal tie shall have a minimum
yield of 33,000 psi (227 MPa).
5. Joists at setbacks or
the end of cantilevered joists shall not carry gravity
loads from more than a single story having uniform wall
and roof loads, nor carry the reactions from headers
having a span of 8 feet (2438 mm) or more.
2. Where a section of floor
or roof is not laterally supported by braced wall lines
on all edges, the structure shall be considered to be
irregular [see Figure
2308.12.6(3)].
Exception: Portions of
roofs or floors that do not support braced wall panels above
are permitted to extend up to 6 feet (1829 mm) beyond
a braced wall line [see Figure
2308.12.6(4)].
3. Where the end of a required
braced wall panel extends more than 1 foot (305 mm)over
an opening in the wall below, the structure shall be considered
to be irregular. This requirement is applicable to braced
wall panels offset in plane and to braced wall panels
offset out of plane as permitted by the exception to Item
1 above in this section [see Figure
2308.12.6(5)]. Exception: Braced wall panels are permitted
to extend over an opening not more than 8 feet (2438 mm)
in width where the header is a 4-inch by 12-inch (102
mm by 305 mm) or larger member.
4. Where portions of a floor
level are vertically offset such that the framing members
on either side of the offset cannot be lapped or tied
together in an approved manner, the structure shall be
considered to be irregular [see Figure
2308.12.6(6)].
Exception: Framing supported
directly by foundations need not be lapped or tied directly
together.
5. Where braced wall lines
are not perpendicular to each other, the structure shall
be considered to be irregular [see Figure
2308.12.6(7)].
6. Where openings in floor
and roof diaphragms having a maximum dimension greater
than 50 percent of the distance between lines of bracing
or an area greater than 25 percent of the area between
orthogonal pairs of braced wall lines are present, the
structure shall be considered to be irregular [see Figure
2308.12.6(8)].
2308.12.7 Anchorage of exterior
means of egress components. Exterior egress balconies,
exterior exit stairways and similar means of egress components
shall be positively anchored to the primary structure at
not over 8 feet (2438 mm) o.c. or shall be designed for
lateral forces. Such attachment shall not be accomplished
by use of toenails or nails subject to withdrawal.
2308.12.8 Steel plate washers.
Steel plate washers shall be placed between the foundation
sill plate and the nut. Such washers shall be a minimum
of 0.229 inch by 3 inches by 3 inches (5.82 mm by 76 mm
by 76 mm) in size. The hole in the plate washer is permitted
to be diagonally slotted with a width of up to 3/16 inch
(4.76 mm) larger than the bolt diameter and a slot length
not to exceed 13/4 inches (44 mm), provided a standard cut
washer is placed between the plate washer and the nut.
2308.12.9 Anchorage in Seismic
Design Category E. Steel bolts with a minimum nominal
diameter of 5/8 inch (15.9 mm) shall be used in Seismic
Design Category E.
|